Public water system record

St John Water District 1

Serves Laplace, Reserve and Edgard, St. John the Baptist Parish, LA · 10,484 people served

Federal records show 1 health-based violation and 2 monitoring/reporting issues for St John Water District 1 in the last ten years. The most serious issue in this window was a resolved Interim Enhanced Surface Water Treatment Rule violation.

  • LA1095003
  • LAPLACE
  • LA
  • 10,484 served

System profile

Source water Surface water
ZIP 70068
EPA system ID LA1095003

Verify this system on EPA ECHO →

Health-based violations, last 10 years
1
Resolved
1
Unresolved
0
Any acute record
Yes
Monitoring issues, last 10 years
2

Key facts

  • St John Water District 1 draws water from 1 surface water intake.
  • Most recent formal enforcement: compliance order (no penalty) by Louisiana, August 2009.
  • Record on file since 1992, with 54 health-based violations before October 19, 2016.
  • Lead pipe inventory: 0 lead and 0 unknown out of 4,108 service lines.

Check whether St John Water District 1 serves your address

Address suggestions by Mapbox

Health-based violations

Since October 2016

Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.

Contaminant Rule family Start date Status Acute
Interim Enhanced Surface Water Treatment Rule
Treatment technique failure
120 Jun 1, 2019 Resolved Yes

Monitoring and reporting issues

Since October 2016

Missed tests or reports, not contaminants found above a limit.

Issue Start date Status
Lead and Copper Rule
Monitoring and reporting
Sep 27, 2024 Resolved
Consumer Confidence Rule
OTHER
Jul 1, 2017 Resolved

Full record since 1992

EPA's records for St John Water District 1 go back to 1992. Before October 19, 2016 they list 54 health-based violations (45 resolved, 9 archived by EPA without a recorded fix) and 11 monitoring or reporting violations.

Violations that began in Health-based Monitoring and reporting
1990s 3 0
2000s 42 7
2010 to October 18, 2016 9 4
October 19, 2016 to 2019 1 1
2020s 0 1

Most recent health-based violation before October 19, 2016: Interim Enhanced Surface Water Treatment Rule (acute), began November 2015, Resolved.

Show all 54 health-based violations before October 19, 2016
Contaminant Start date Status
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
Nov 1, 2015 Resolved
Long Term 2 Enhanced Surface Water Treatment Rule
Treatment technique failure
Oct 1, 2015 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 107 µg/L, federal limit 80 µg/L (1.3 times the limit)
Apr 1, 2015 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 116 µg/L, federal limit 80 µg/L (1.5 times the limit)
Jan 1, 2015 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 95 µg/L, federal limit 80 µg/L (1.2 times the limit)
Oct 1, 2014 Resolved
CARBON, TOTAL
Treatment technique failure
Apr 1, 2014 Resolved
CARBON, TOTAL
Treatment technique failure
Jan 1, 2014 Resolved
CARBON, TOTAL
Treatment technique failure
Oct 1, 2013 Resolved
Total Coliform
Contaminant limit exceeded
Jun 1, 2013 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Oct 1, 2009 Resolved
Total Coliform
Contaminant limit exceeded
Aug 1, 2009 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Jul 1, 2009 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 90 µg/L, federal limit 80 µg/L (1.1 times the limit)
Jan 1, 2009 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 94 µg/L, federal limit 80 µg/L (1.2 times the limit)
Jul 1, 2008 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 88 µg/L, federal limit 80 µg/L (1.1 times the limit)
Apr 1, 2008 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 91 µg/L, federal limit 80 µg/L (1.1 times the limit)
Jan 1, 2008 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 84 µg/L, federal limit 80 µg/L (1.1 times the limit)
Oct 1, 2007 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 65 µg/L, federal limit 60 µg/L (1.1 times the limit)
Jul 1, 2007 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 91 µg/L, federal limit 80 µg/L (1.1 times the limit)
Jul 1, 2007 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 68 µg/L, federal limit 60 µg/L (1.1 times the limit)
Apr 1, 2007 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 93 µg/L, federal limit 80 µg/L (1.2 times the limit)
Apr 1, 2007 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 65 µg/L, federal limit 60 µg/L (1.1 times the limit)
Jan 1, 2007 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 89 µg/L, federal limit 80 µg/L (1.1 times the limit)
Jan 1, 2007 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 82 µg/L, federal limit 80 µg/L (at or just above the limit)
Oct 1, 2006 Resolved
CARBON, TOTAL
Treatment technique failure
Jul 1, 2006 Archived
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 84 µg/L, federal limit 80 µg/L (1.1 times the limit)
Jul 1, 2006 Resolved
CARBON, TOTAL
Treatment technique failure
Apr 1, 2006 Archived
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 91 µg/L, federal limit 80 µg/L (1.1 times the limit)
Apr 1, 2006 Resolved
CARBON, TOTAL
Treatment technique failure
Jan 1, 2006 Archived
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 90 µg/L, federal limit 80 µg/L (1.1 times the limit)
Jan 1, 2006 Resolved
CARBON, TOTAL
Treatment technique failure
Oct 1, 2005 Archived
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 99 µg/L, federal limit 80 µg/L (1.2 times the limit)
Oct 1, 2005 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Jul 1, 2005 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Jul 1, 2005 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Apr 1, 2005 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Apr 1, 2005 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Jan 1, 2005 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Jan 1, 2005 Resolved
Total Coliform
Contaminant limit exceeded
Dec 1, 2004 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Jul 1, 2004 Archived
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Jan 1, 2004 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Oct 1, 2003 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Jul 1, 2003 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Jul 1, 2003 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Apr 1, 2003 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Apr 1, 2003 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Jan 1, 2003 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Jan 1, 2003 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Oct 1, 2002 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Jul 1, 2002 Resolved

4 older violations are not listed here. EPA ECHO has the complete list.

Enforcement actions

Louisiana regulators took 6 formal enforcement actions against St John Water District 1 between 2003 and 2009. The most recent was a compliance order (no penalty) in August 2009.

Date By Action Violations covered
Aug 17, 2009 Louisiana Compliance order (no penalty) 10 violations (9 health-based): Total Trihalomethanes (TTHMs), Total Coliform, Haloacetic Acids (HAA5)
May 21, 2007 Louisiana Compliance order (no penalty) 29 violations (29 health-based): Total Trihalomethanes (TTHMs), Haloacetic Acids (HAA5), CARBON, TOTAL
Jan 27, 2006 Louisiana Compliance order (no penalty) 10 violations (10 health-based): Total Trihalomethanes (TTHMs), Haloacetic Acids (HAA5)
May 5, 2005 Louisiana Administrative penalty 4 violations (4 health-based): Total Trihalomethanes (TTHMs)
Oct 19, 2004 Louisiana Compliance order (no penalty) 4 violations (4 health-based): Total Trihalomethanes (TTHMs)
Dec 8, 2003 Louisiana Compliance order (no penalty) 4 violations (4 health-based): Total Trihalomethanes (TTHMs)

What the violations mean

Interim Enhanced Surface Water Treatment Rule

1 incident

The system did not meet a filtration or treatment requirement for surface water

Inadequate treatment of surface water can let pathogens such as Cryptosporidium and Giardia through

Where the water comes from

St John Water District 1 draws water from 1 surface water intake. It also has an emergency connection to St John Water District 3. 2 other public water systems have emergency, seasonal or other part-time connections to St John Water District 1.

Emergency or part-time connections to

Annual water quality report

St John Water District 1 must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.

Systems serving 10,000 or more people must mail or deliver the report to every customer, and from 2027 they must send it twice a year.

Find a posted report with EPA's Consumer Confidence Report search

Testing your own water

To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Louisiana.