Public water system record

Pecan Lake Subdivision WS

Serves an area of Ouachita Parish, LA · 57 people served

Federal records show 13 health-based violations and 4 monitoring/reporting issues for Pecan Lake Subdivision WS in the last ten years. The most serious issue in this window was a resolved Total Trihalomethanes (TTHMs) violation.

  • LA1073063
  • WEST MONROE
  • LA
  • 57 served

System profile

Source water Purchased groundwater
ZIP 71294
EPA system ID LA1073063

Verify this system on EPA ECHO →

Health-based violations, last 10 years
13
Resolved
13
Unresolved
0
Any acute record
No
Monitoring issues, last 10 years
4

Key facts

  • Pecan Lake Subdivision WS buys its water from Better Waterworks Water System.
  • Highest measured level in the last 10 years: Total Trihalomethanes (TTHMs), 393 µg/L, federal limit 80 µg/L (4.9 times the limit), 2018.
  • Most recent formal enforcement: compliance order (no penalty) by Louisiana, October 2017.
  • Record on file since 1999, with 5 health-based violations before October 19, 2016.
  • Lead pipe inventory: 0 lead and 0 unknown out of 21 service lines.

Check whether Pecan Lake Subdivision WS serves your address

Address suggestions by Mapbox

Health-based violations

Since October 2016

Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.

Contaminant Rule family Start date Status Acute
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.082 mg/L, federal limit 0.08 mg/L (at or just above the limit)
220 Apr 1, 2022 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.105 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
220 Jul 1, 2019 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.19 mg/L, federal limit 0.08 mg/L (2.4 times the limit)
220 Apr 1, 2019 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.281 mg/L, federal limit 0.08 mg/L (3.5 times the limit)
220 Jan 1, 2019 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.385 mg/L, federal limit 0.08 mg/L (4.8 times the limit)
220 Oct 1, 2018 Resolved No
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.069 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
220 Oct 1, 2018 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 378 µg/L, federal limit 80 µg/L (4.7 times the limit)
220 Jul 1, 2018 Resolved No
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 61 µg/L, federal limit 60 µg/L (at or just above the limit)
220 Jul 1, 2018 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 393 µg/L, federal limit 80 µg/L (4.9 times the limit)
220 Apr 1, 2018 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 353 µg/L, federal limit 80 µg/L (4.4 times the limit)
220 Jan 1, 2018 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 259 µg/L, federal limit 80 µg/L (3.2 times the limit)
220 Oct 1, 2017 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 189 µg/L, federal limit 80 µg/L (2.4 times the limit)
220 Jul 1, 2017 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 100 µg/L, federal limit 80 µg/L (1.3 times the limit)
220 Apr 1, 2017 Resolved No

Monitoring and reporting issues

Since October 2016

Missed tests or reports, not contaminants found above a limit.

Issue Start date Status
Consumer Confidence Rule
OTHER
Oct 1, 2017 Resolved
Consumer Confidence Rule
OTHER
Jul 1, 2017 Resolved
Total Trihalomethanes (TTHMs)
Monitoring and reporting
Jul 31, 2016 Resolved
Haloacetic Acids (HAA5)
Monitoring and reporting
Jul 31, 2016 Resolved

Full record since 1999

EPA's records for Pecan Lake Subdivision WS go back to 1999. Before October 19, 2016 they list 5 health-based violations (5 resolved) and 19 monitoring or reporting violations.

Violations that began in Health-based Monitoring and reporting
1990s 0 1
2010 to October 18, 2016 5 18
October 19, 2016 to 2019 12 2
2020s 1 0

Most recent health-based violation before October 19, 2016: Total Trihalomethanes (TTHMs), began July 2016, Resolved.

Show all 5 health-based violations before October 19, 2016
Contaminant Start date Status
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 106 µg/L, federal limit 80 µg/L (1.3 times the limit)
Jul 1, 2016 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 74 µg/L, federal limit 60 µg/L (1.2 times the limit)
Jul 1, 2016 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 136 µg/L, federal limit 80 µg/L (1.7 times the limit)
Apr 1, 2016 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 91 µg/L, federal limit 60 µg/L (1.5 times the limit)
Apr 1, 2016 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 82 µg/L, federal limit 80 µg/L (at or just above the limit)
Oct 1, 2015 Resolved

Enforcement actions

Louisiana regulators took 1 formal enforcement action against Pecan Lake Subdivision WS in 2017. The most recent was a compliance order (no penalty) in October 2017.

Date By Action Violations covered
Oct 3, 2017 Louisiana Compliance order (no penalty) 18 violations (18 health-based): Total Trihalomethanes (TTHMs), Haloacetic Acids (HAA5)

What the violations mean

Total Trihalomethanes (TTHMs)

11 incidents

Disinfection byproduct levels exceeded the federal limit

Long-term TTHM exposure may increase bladder cancer risk

Haloacetic Acids (HAA5)

2 incidents

Haloacetic acid byproducts exceeded the federal limit

Long-term exposure to HAAs may increase cancer risk

Where the water comes from

Pecan Lake Subdivision WS buys its water from Better Waterworks Water System. It lists no wells or intakes of its own.

Buys water from

Annual water quality report

Pecan Lake Subdivision WS must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.

Systems serving 500 or fewer people may meet the rule by telling customers the report is available on request, so you may need to ask Pecan Lake Subdivision WS for a copy.

Find a posted report with EPA's Consumer Confidence Report search

Testing your own water

To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Louisiana.