Public water system record
Cadeville Water District
Serves an area of Ouachita Parish, LA · 6,219 people served
Federal records show 31 health-based violations and 22 monitoring/reporting issues for Cadeville Water District in the last ten years, including an unresolved Groundwater Rule violation.
System profile
- Health-based violations, last 10 years
- 31
- Resolved
- 29
- Unresolved
- 2
- Any acute record
- No
- Monitoring issues, last 10 years
- 22
Key facts
- Cadeville Water District draws water from 7 wells.
- Highest measured level in the last 10 years: Total Trihalomethanes (TTHMs), 168 µg/L, federal limit 80 µg/L (2.1 times the limit), 2017.
- Most recent formal enforcement: compliance order (no penalty) by Louisiana, September 2015.
- Record on file since 1994, with 25 health-based violations before October 19, 2016.
- Lead pipe inventory: 0 lead and 0 unknown out of 2,337 service lines.
Check whether Cadeville Water District serves your address
Health-based violations
Since October 2016Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.
| Contaminant | Rule family | Start date | Status | Acute |
|---|---|---|---|---|
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.081 mg/L, federal limit 0.08 mg/L (at or just above the limit)
|
220 | Jan 1, 2024 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.111 mg/L, federal limit 0.08 mg/L (1.4 times the limit)
|
220 | Jan 1, 2022 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.14 mg/L, federal limit 0.08 mg/L (1.8 times the limit)
|
220 | Oct 1, 2021 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.124 mg/L, federal limit 0.08 mg/L (1.6 times the limit)
|
220 | Jul 1, 2021 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.131 mg/L, federal limit 0.08 mg/L (1.6 times the limit)
|
220 | Apr 1, 2021 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.131 mg/L, federal limit 0.08 mg/L (1.6 times the limit)
|
220 | Jan 1, 2021 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.12 mg/L, federal limit 0.08 mg/L (1.5 times the limit)
|
220 | Oct 1, 2020 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.147 mg/L, federal limit 0.08 mg/L (1.8 times the limit)
|
220 | Jul 1, 2020 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.137 mg/L, federal limit 0.08 mg/L (1.7 times the limit)
|
220 | Apr 1, 2020 | Resolved | No |
|
Groundwater Rule
Treatment technique failure
|
140 | Jan 31, 2020 | Resolved | No |
|
Groundwater Rule
Treatment technique failure
|
140 | Jan 31, 2020 | Resolved | No |
|
Groundwater Rule
Treatment technique failure
|
140 | Jan 31, 2020 | Active | No |
|
Groundwater Rule
Treatment technique failure
|
140 | Jan 31, 2020 | Resolved | No |
|
Groundwater Rule
Treatment technique failure
|
140 | Jan 31, 2020 | Resolved | No |
|
Groundwater Rule
Treatment technique failure
|
140 | Jan 31, 2020 | Active | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.144 mg/L, federal limit 0.08 mg/L (1.8 times the limit)
|
220 | Jan 1, 2020 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.145 mg/L, federal limit 0.08 mg/L (1.8 times the limit)
|
220 | Oct 1, 2019 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.143 mg/L, federal limit 0.08 mg/L (1.8 times the limit)
|
220 | Jul 1, 2019 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.153 mg/L, federal limit 0.08 mg/L (1.9 times the limit)
|
220 | Apr 1, 2019 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.15 mg/L, federal limit 0.08 mg/L (1.9 times the limit)
|
220 | Jan 1, 2019 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.143 mg/L, federal limit 0.08 mg/L (1.8 times the limit)
|
220 | Oct 1, 2018 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 151 µg/L, federal limit 80 µg/L (1.9 times the limit)
|
220 | Jul 1, 2018 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 150 µg/L, federal limit 80 µg/L (1.9 times the limit)
|
220 | Apr 1, 2018 | Resolved | No |
|
Groundwater Rule
Treatment technique failure
|
140 | Feb 1, 2018 | Resolved | No |
|
Groundwater Rule
Treatment technique failure
|
140 | Feb 1, 2018 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 151 µg/L, federal limit 80 µg/L (1.9 times the limit)
|
220 | Jan 1, 2018 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 167 µg/L, federal limit 80 µg/L (2.1 times the limit)
|
220 | Oct 1, 2017 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 168 µg/L, federal limit 80 µg/L (2.1 times the limit)
|
220 | Jul 1, 2017 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 164 µg/L, federal limit 80 µg/L (2.1 times the limit)
|
220 | Apr 1, 2017 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 147 µg/L, federal limit 80 µg/L (1.8 times the limit)
|
220 | Jan 1, 2017 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 130 µg/L, federal limit 80 µg/L (1.6 times the limit)
|
220 | Oct 1, 2016 | Resolved | No |
Monitoring and reporting issues
Since October 2016Missed tests or reports, not contaminants found above a limit.
| Issue | Start date | Status |
|---|---|---|
|
Public Notice
OTHER
|
Mar 15, 2020 | Resolved |
|
Public Notice
OTHER
|
Feb 9, 2020 | Resolved |
|
Lead and Copper Rule
Monitoring and reporting
|
Oct 1, 2019 | Resolved |
|
Public Notice
OTHER
|
Jul 30, 2019 | Resolved |
|
Public Notice
OTHER
|
Apr 6, 2019 | Resolved |
|
Public Notice
OTHER
|
Mar 12, 2018 | Resolved |
|
Total Trihalomethanes (TTHMs)
Monitoring and reporting
|
Oct 31, 2017 | Resolved |
|
Total Trihalomethanes (TTHMs)
Monitoring and reporting
|
Jul 31, 2017 | Resolved |
|
Consumer Confidence Rule
OTHER
|
Jul 1, 2017 | Resolved |
|
Total Trihalomethanes (TTHMs)
Monitoring and reporting
|
May 1, 2017 | Resolved |
|
Total Trihalomethanes (TTHMs)
Monitoring and reporting
|
Oct 31, 2016 | Resolved |
|
Haloacetic Acids (HAA5)
Monitoring and reporting
|
Sep 1, 2016 | Resolved |
|
Total Trihalomethanes (TTHMs)
Monitoring and reporting
|
Sep 1, 2016 | Resolved |
|
Public Notice
OTHER
|
Aug 21, 2016 | Resolved |
|
Total Trihalomethanes (TTHMs)
Monitoring and reporting
|
Jul 31, 2016 | Resolved |
|
Public Notice
OTHER
|
Jun 5, 2015 | Resolved |
|
Public Notice
OTHER
|
May 21, 2015 | Resolved |
|
Public Notice
OTHER
|
May 1, 2015 | Resolved |
|
Total Trihalomethanes (TTHMs)
Monitoring and reporting
|
May 1, 2015 | Resolved |
|
Total Trihalomethanes (TTHMs)
Monitoring and reporting
|
Jul 31, 2014 | Resolved |
|
Haloacetic Acids (HAA5)
Monitoring and reporting
|
Jul 31, 2014 | Resolved |
|
Total Trihalomethanes (TTHMs)
Monitoring and reporting
|
May 1, 2014 | Resolved |
Full record since 1994
EPA's records for Cadeville Water District go back to 1994. Before October 19, 2016 they list 25 health-based violations (14 resolved, 11 archived by EPA without a recorded fix) and 20 monitoring or reporting violations.
| Violations that began in | Health-based | Monitoring and reporting |
|---|---|---|
| 1990s | 1 | 1 |
| 2000s | 10 | 0 |
| 2010 to October 18, 2016 | 14 | 19 |
| October 19, 2016 to 2019 | 14 | 9 |
| 2020s | 16 | 2 |
Most recent health-based violation before October 19, 2016: Total Trihalomethanes (TTHMs), began October 2016, Resolved.
Show all 25 health-based violations before October 19, 2016
| Contaminant | Start date | Status |
|---|---|---|
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 130 µg/L, federal limit 80 µg/L (1.6 times the limit)
|
Oct 1, 2016 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 140 µg/L, federal limit 80 µg/L (1.8 times the limit)
|
Jul 1, 2016 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 142 µg/L, federal limit 80 µg/L (1.8 times the limit)
|
Apr 1, 2016 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 131 µg/L, federal limit 80 µg/L (1.6 times the limit)
|
Oct 1, 2015 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 116 µg/L, federal limit 80 µg/L (1.5 times the limit)
|
Jul 1, 2015 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 106 µg/L, federal limit 80 µg/L (1.3 times the limit)
|
Apr 1, 2015 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 111 µg/L, federal limit 80 µg/L (1.4 times the limit)
|
Jan 1, 2015 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 121 µg/L, federal limit 80 µg/L (1.5 times the limit)
|
Oct 1, 2014 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 133 µg/L, federal limit 80 µg/L (1.7 times the limit)
|
Jul 1, 2014 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 129 µg/L, federal limit 80 µg/L (1.6 times the limit)
|
Apr 1, 2014 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 95 µg/L, federal limit 80 µg/L (1.2 times the limit)
|
Jan 1, 2014 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 97 µg/L, federal limit 80 µg/L (1.2 times the limit)
|
Oct 1, 2013 | Archived |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 84 µg/L, federal limit 80 µg/L (1.1 times the limit)
|
Jul 1, 2013 | Resolved |
|
Groundwater Rule
Treatment technique failure
|
Jan 5, 2012 | Resolved |
|
Total Coliform
Contaminant limit exceeded
|
Sep 1, 2007 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 91 µg/L, federal limit 80 µg/L (1.1 times the limit)
|
Jan 1, 2006 | Archived |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 97 µg/L, federal limit 80 µg/L (1.2 times the limit)
|
Oct 1, 2005 | Archived |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
|
Jul 1, 2005 | Archived |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
|
Apr 1, 2005 | Archived |
|
Total Coliform
Contaminant limit exceeded
|
Aug 1, 2004 | Archived |
|
Total Coliform
Contaminant limit exceeded
|
May 1, 2004 | Archived |
|
Total Coliform
Contaminant limit exceeded
|
Nov 1, 2003 | Archived |
|
Total Coliform
Contaminant limit exceeded
|
Jul 15, 2003 | Archived |
|
Total Coliform
Contaminant limit exceeded
|
Jul 15, 2000 | Archived |
|
Total Coliform
Contaminant limit exceeded
|
Nov 15, 1997 | Archived |
Enforcement actions
Louisiana regulators and EPA took 2 formal enforcement actions against Cadeville Water District between 2006 and 2015. The most recent was a compliance order (no penalty) in September 2015.
| Date | By | Action | Violations covered |
|---|---|---|---|
| Sep 29, 2015 | Louisiana | Compliance order (no penalty) | 57 violations (38 health-based): Total Trihalomethanes (TTHMs), Haloacetic Acids (HAA5), Chlorine, Consumer Confidence Rule, Total Coliform |
| Aug 30, 2006 | EPA | Compliance order (no penalty) | 4 violations (4 health-based): Total Trihalomethanes (TTHMs) |
What the violations mean
Total Trihalomethanes (TTHMs)
23 incidentsDisinfection byproduct levels exceeded the federal limit
Long-term TTHM exposure may increase bladder cancer risk
Groundwater Rule
8 incidentsThe system did not complete a treatment step or action that the Groundwater Rule requires (a treatment technique violation).
The utility had to notify customers about each of these violations.
Where the water comes from
Cadeville Water District draws water from 7 wells. It also has an emergency connection to Southwest Ouachita Waterworks, Inc. 2 other public water systems have emergency connections to Cadeville Water District.
Emergency or part-time connections to
- Southwest Ouachita Waterworks, Inc West Monroe, LA
Annual water quality report
Cadeville Water District must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.
Where the state allows it, systems serving fewer than 10,000 people may publish the report in a local newspaper or news site instead of mailing it, and must provide a copy on request.
Find a posted report with EPA's Consumer Confidence Report search
Testing your own water
To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Louisiana.
Certified drinking water labs by state EPA guidance for private wells