Public water system record

Ramsey Water System

On record as serving Ouachita Parish, LA · Serves 84 people

Federal records show 21 health-based violations and 5 monitoring/reporting issues for Ramsey Water System in the last ten years. The most serious issue in this window was a resolved Total Trihalomethanes (TTHMs) violation.

  • LA1073025
  • WEST MONROE
  • LA
  • 84 served

System profile

Source water Purchased groundwater
ZIP 71294
EPA system ID LA1073025

Verify this system on EPA ECHO →

Health-based violations, last 10 years
21
Resolved
21
Unresolved
0
Any acute record
No
Monitoring issues, last 10 years
5

Key facts

  • Ramsey Water System buys its water from Better Waterworks Water System.
  • Highest measured level in the last 10 years: Total Trihalomethanes (TTHMs), 403 µg/L, federal limit 80 µg/L (5 times the limit), 2018.
  • Most recent formal enforcement: compliance order (no penalty) by Louisiana, April 2018.
  • Record on file since 2005, with 3 health-based violations before October 19, 2016.
  • Lead pipe inventory: 0 lead and 0 unknown out of 35 service lines.

Check whether Ramsey Water System serves your address

Address suggestions by Mapbox

Health-based violations

Since October 2016

Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.

Contaminant Rule family Start date Status Acute
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.091 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
220 Apr 1, 2022 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.087 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
220 Jan 1, 2022 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.09 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
220 Oct 1, 2021 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.082 mg/L, federal limit 0.08 mg/L (at or just above the limit)
220 Jul 1, 2021 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.096 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
220 Jul 1, 2019 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.196 mg/L, federal limit 0.08 mg/L (2.5 times the limit)
220 Apr 1, 2019 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.286 mg/L, federal limit 0.08 mg/L (3.6 times the limit)
220 Jan 1, 2019 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 390 µg/L, federal limit 80 µg/L (4.9 times the limit)
220 Oct 1, 2018 Resolved No
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 66 µg/L, federal limit 60 µg/L (1.1 times the limit)
220 Oct 1, 2018 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 403 µg/L, federal limit 80 µg/L (5 times the limit)
220 Jul 1, 2018 Resolved No
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 73 µg/L, federal limit 60 µg/L (1.2 times the limit)
220 Jul 1, 2018 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 402 µg/L, federal limit 80 µg/L (5 times the limit)
220 Apr 1, 2018 Resolved No
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 66 µg/L, federal limit 60 µg/L (1.1 times the limit)
220 Apr 1, 2018 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 400 µg/L, federal limit 80 µg/L (5 times the limit)
220 Jan 1, 2018 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 384 µg/L, federal limit 80 µg/L (4.8 times the limit)
220 Oct 1, 2017 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 399 µg/L, federal limit 80 µg/L (5 times the limit)
220 Jul 1, 2017 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 364 µg/L, federal limit 80 µg/L (4.6 times the limit)
220 Apr 1, 2017 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 118 µg/L, federal limit 80 µg/L (1.5 times the limit)
220 Jan 1, 2017 Resolved No
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 73 µg/L, federal limit 60 µg/L (1.2 times the limit)
220 Jan 1, 2017 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 92 µg/L, federal limit 80 µg/L (1.2 times the limit)
220 Oct 1, 2016 Resolved No
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 78 µg/L, federal limit 60 µg/L (1.3 times the limit)
220 Oct 1, 2016 Resolved No

Monitoring and reporting issues

Since October 2016

Missed tests or reports, not contaminants found above a limit.

Issue Start date Status
Consumer Confidence Rule
OTHER
Oct 1, 2017 Resolved
Consumer Confidence Rule
OTHER
Jul 1, 2017 Resolved
Haloacetic Acids (HAA5)
Monitoring and reporting
Oct 31, 2016 Resolved
Total Trihalomethanes (TTHMs)
Monitoring and reporting
Oct 31, 2016 Resolved
Lead and Copper Rule
Monitoring and reporting
Oct 1, 2016 Resolved

Full record since 2005

EPA's records for Ramsey Water System go back to 2005. Before October 19, 2016 they list 3 health-based violations (3 resolved) and 12 monitoring or reporting violations.

Violations that began in Health-based Monitoring and reporting
2000s 1 2
2010 to October 18, 2016 2 10
October 19, 2016 to 2019 15 4
2020s 4 0

Most recent health-based violation before October 19, 2016: Total Trihalomethanes (TTHMs), began October 2016, Resolved.

Show all 3 health-based violations before October 19, 2016
Contaminant Start date Status
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 92 µg/L, federal limit 80 µg/L (1.2 times the limit)
Oct 1, 2016 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 78 µg/L, federal limit 60 µg/L (1.3 times the limit)
Oct 1, 2016 Resolved
Total Coliform
Contaminant limit exceeded
Jul 1, 2005 Resolved

Enforcement actions

Louisiana regulators took 1 formal enforcement action against Ramsey Water System in 2018. The most recent was a compliance order (no penalty) in April 2018.

Date By Action Violations covered
Apr 19, 2018 Louisiana Compliance order (no penalty) 21 violations (21 health-based): Haloacetic Acids (HAA5), Total Trihalomethanes (TTHMs)

What the violations mean

Total Trihalomethanes (TTHMs)

16 incidents

Disinfection byproduct levels exceeded the federal limit

Long-term TTHM exposure may increase bladder cancer risk

Haloacetic Acids (HAA5)

5 incidents

Haloacetic acid byproducts exceeded the federal limit

Long-term exposure to HAAs may increase cancer risk

Where the water comes from

Ramsey Water System buys its water from Better Waterworks Water System. It lists no wells or intakes of its own. It also has an emergency connection to Gowc East Water System.

Buys water from

Emergency or part-time connections to

Annual water quality report

Ramsey Water System must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.

Systems serving 500 or fewer people may meet the rule by telling customers the report is available on request, so you may need to ask Ramsey Water System for a copy.

Find a posted report with EPA's Consumer Confidence Report search

Testing your own water

To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Louisiana.