Public water system record
Ramsey Water System
On record as serving Ouachita Parish, LA · Serves 84 people
Federal records show 21 health-based violations and 5 monitoring/reporting issues for Ramsey Water System in the last ten years. The most serious issue in this window was a resolved Total Trihalomethanes (TTHMs) violation.
System profile
- Health-based violations, last 10 years
- 21
- Resolved
- 21
- Unresolved
- 0
- Any acute record
- No
- Monitoring issues, last 10 years
- 5
Key facts
- Ramsey Water System buys its water from Better Waterworks Water System.
- Highest measured level in the last 10 years: Total Trihalomethanes (TTHMs), 403 µg/L, federal limit 80 µg/L (5 times the limit), 2018.
- Most recent formal enforcement: compliance order (no penalty) by Louisiana, April 2018.
- Record on file since 2005, with 3 health-based violations before October 19, 2016.
- Lead pipe inventory: 0 lead and 0 unknown out of 35 service lines.
Check whether Ramsey Water System serves your address
Health-based violations
Since October 2016Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.
| Contaminant | Rule family | Start date | Status | Acute |
|---|---|---|---|---|
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.091 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
220 | Apr 1, 2022 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.087 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
220 | Jan 1, 2022 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.09 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
220 | Oct 1, 2021 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.082 mg/L, federal limit 0.08 mg/L (at or just above the limit)
|
220 | Jul 1, 2021 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.096 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
220 | Jul 1, 2019 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.196 mg/L, federal limit 0.08 mg/L (2.5 times the limit)
|
220 | Apr 1, 2019 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.286 mg/L, federal limit 0.08 mg/L (3.6 times the limit)
|
220 | Jan 1, 2019 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 390 µg/L, federal limit 80 µg/L (4.9 times the limit)
|
220 | Oct 1, 2018 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 66 µg/L, federal limit 60 µg/L (1.1 times the limit)
|
220 | Oct 1, 2018 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 403 µg/L, federal limit 80 µg/L (5 times the limit)
|
220 | Jul 1, 2018 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 73 µg/L, federal limit 60 µg/L (1.2 times the limit)
|
220 | Jul 1, 2018 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 402 µg/L, federal limit 80 µg/L (5 times the limit)
|
220 | Apr 1, 2018 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 66 µg/L, federal limit 60 µg/L (1.1 times the limit)
|
220 | Apr 1, 2018 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 400 µg/L, federal limit 80 µg/L (5 times the limit)
|
220 | Jan 1, 2018 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 384 µg/L, federal limit 80 µg/L (4.8 times the limit)
|
220 | Oct 1, 2017 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 399 µg/L, federal limit 80 µg/L (5 times the limit)
|
220 | Jul 1, 2017 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 364 µg/L, federal limit 80 µg/L (4.6 times the limit)
|
220 | Apr 1, 2017 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 118 µg/L, federal limit 80 µg/L (1.5 times the limit)
|
220 | Jan 1, 2017 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 73 µg/L, federal limit 60 µg/L (1.2 times the limit)
|
220 | Jan 1, 2017 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 92 µg/L, federal limit 80 µg/L (1.2 times the limit)
|
220 | Oct 1, 2016 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 78 µg/L, federal limit 60 µg/L (1.3 times the limit)
|
220 | Oct 1, 2016 | Resolved | No |
Monitoring and reporting issues
Since October 2016Missed tests or reports, not contaminants found above a limit.
| Issue | Start date | Status |
|---|---|---|
|
Consumer Confidence Rule
OTHER
|
Oct 1, 2017 | Resolved |
|
Consumer Confidence Rule
OTHER
|
Jul 1, 2017 | Resolved |
|
Haloacetic Acids (HAA5)
Monitoring and reporting
|
Oct 31, 2016 | Resolved |
|
Total Trihalomethanes (TTHMs)
Monitoring and reporting
|
Oct 31, 2016 | Resolved |
|
Lead and Copper Rule
Monitoring and reporting
|
Oct 1, 2016 | Resolved |
Full record since 2005
EPA's records for Ramsey Water System go back to 2005. Before October 19, 2016 they list 3 health-based violations (3 resolved) and 12 monitoring or reporting violations.
| Violations that began in | Health-based | Monitoring and reporting |
|---|---|---|
| 2000s | 1 | 2 |
| 2010 to October 18, 2016 | 2 | 10 |
| October 19, 2016 to 2019 | 15 | 4 |
| 2020s | 4 | 0 |
Most recent health-based violation before October 19, 2016: Total Trihalomethanes (TTHMs), began October 2016, Resolved.
Show all 3 health-based violations before October 19, 2016
| Contaminant | Start date | Status |
|---|---|---|
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 92 µg/L, federal limit 80 µg/L (1.2 times the limit)
|
Oct 1, 2016 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 78 µg/L, federal limit 60 µg/L (1.3 times the limit)
|
Oct 1, 2016 | Resolved |
|
Total Coliform
Contaminant limit exceeded
|
Jul 1, 2005 | Resolved |
Enforcement actions
Louisiana regulators took 1 formal enforcement action against Ramsey Water System in 2018. The most recent was a compliance order (no penalty) in April 2018.
| Date | By | Action | Violations covered |
|---|---|---|---|
| Apr 19, 2018 | Louisiana | Compliance order (no penalty) | 21 violations (21 health-based): Haloacetic Acids (HAA5), Total Trihalomethanes (TTHMs) |
What the violations mean
Total Trihalomethanes (TTHMs)
16 incidentsDisinfection byproduct levels exceeded the federal limit
Long-term TTHM exposure may increase bladder cancer risk
Haloacetic Acids (HAA5)
5 incidentsHaloacetic acid byproducts exceeded the federal limit
Long-term exposure to HAAs may increase cancer risk
Where the water comes from
Ramsey Water System buys its water from Better Waterworks Water System. It lists no wells or intakes of its own. It also has an emergency connection to Gowc East Water System.
Buys water from
- Better Waterworks Water System West Monroe, LA
Emergency or part-time connections to
- Gowc East Water System West Monroe, LA
Annual water quality report
Ramsey Water System must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.
Systems serving 500 or fewer people may meet the rule by telling customers the report is available on request, so you may need to ask Ramsey Water System for a copy.
Find a posted report with EPA's Consumer Confidence Report search
Testing your own water
To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Louisiana.