Public water system record
Chatham Water System
Serves an area of Jackson Parish, LA that includes Chatham · 1,557 people served
Federal records show 37 health-based violations and 2 monitoring/reporting issues for Chatham Water System in the last ten years. The most serious issue in this window was a Total Trihalomethanes (TTHMs) violation that EPA lists as archived, not resolved.
System profile
- Health-based violations, last 10 years
- 37
- Resolved
- 36
- Unresolved
- 0
- Archived by EPA
- 1
- Any acute record
- No
- Monitoring issues, last 10 years
- 2
Key facts
- Chatham Water System draws water from 3 wells.
- Highest measured level in the last 10 years: Total Trihalomethanes (TTHMs), 0.261 mg/L, federal limit 0.08 mg/L (3.3 times the limit), 2019.
- Most recent formal enforcement: compliance order (no penalty) by Louisiana, June 2016.
- Record on file since 1993, with 23 health-based violations before October 19, 2016.
- Lead pipe inventory: 0 lead and 0 unknown out of 545 service lines.
Check whether Chatham Water System serves your address
Health-based violations
Since October 2016Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.
| Contaminant | Rule family | Start date | Status | Acute |
|---|---|---|---|---|
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.088 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
220 | Oct 1, 2025 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Groundwater Rule
Treatment technique failure
|
140 | Feb 4, 2024 | Resolved | No |
|
Groundwater Rule
Treatment technique failure
|
140 | Feb 4, 2024 | Resolved | No |
|
Groundwater Rule
Treatment technique failure
|
140 | Feb 4, 2024 | Resolved | No |
|
Groundwater Rule
Treatment technique failure
|
140 | Feb 4, 2024 | Resolved | No |
|
Groundwater Rule
Treatment technique failure
|
140 | Feb 4, 2024 | Resolved | No |
|
Groundwater Rule
Treatment technique failure
|
140 | Feb 4, 2024 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.086 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
220 | Oct 1, 2021 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.136 mg/L, federal limit 0.08 mg/L (1.7 times the limit)
|
220 | Jul 1, 2021 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.171 mg/L, federal limit 0.08 mg/L (2.1 times the limit)
|
220 | Apr 1, 2021 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.065 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
|
220 | Apr 1, 2021 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.23 mg/L, federal limit 0.08 mg/L (2.9 times the limit)
|
220 | Jan 1, 2021 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.078 mg/L, federal limit 0.06 mg/L (1.3 times the limit)
|
220 | Jan 1, 2021 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.209 mg/L, federal limit 0.08 mg/L (2.6 times the limit)
|
220 | Oct 1, 2020 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.076 mg/L, federal limit 0.06 mg/L (1.3 times the limit)
|
220 | Oct 1, 2020 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.208 mg/L, federal limit 0.08 mg/L (2.6 times the limit)
|
220 | Jul 1, 2020 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.24 mg/L, federal limit 0.08 mg/L (3 times the limit)
|
220 | Apr 1, 2020 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.24 mg/L, federal limit 0.08 mg/L (3 times the limit)
|
220 | Jan 1, 2020 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.064 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
|
220 | Jan 1, 2020 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.256 mg/L, federal limit 0.08 mg/L (3.2 times the limit)
|
220 | Oct 1, 2019 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.064 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
|
220 | Oct 1, 2019 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.256 mg/L, federal limit 0.08 mg/L (3.2 times the limit)
|
220 | Jul 1, 2019 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.071 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
|
220 | Jul 1, 2019 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.074 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
|
220 | Apr 1, 2019 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.261 mg/L, federal limit 0.08 mg/L (3.3 times the limit)
|
220 | Apr 1, 2019 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.249 mg/L, federal limit 0.08 mg/L (3.1 times the limit)
|
220 | Jan 1, 2019 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.068 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
|
220 | Jan 1, 2019 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 260 µg/L, federal limit 80 µg/L (3.3 times the limit)
|
220 | Oct 1, 2018 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 66 µg/L, federal limit 60 µg/L (1.1 times the limit)
|
220 | Oct 1, 2018 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 222 µg/L, federal limit 80 µg/L (2.8 times the limit)
|
220 | Jul 1, 2018 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 203 µg/L, federal limit 80 µg/L (2.5 times the limit)
|
220 | Apr 1, 2018 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 190 µg/L, federal limit 80 µg/L (2.4 times the limit)
|
220 | Jan 1, 2018 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 161 µg/L, federal limit 80 µg/L (2 times the limit)
|
220 | Oct 1, 2017 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 189 µg/L, federal limit 80 µg/L (2.4 times the limit)
|
220 | Jul 1, 2017 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 170 µg/L, federal limit 80 µg/L (2.1 times the limit)
|
220 | Apr 1, 2017 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 117 µg/L, federal limit 80 µg/L (1.5 times the limit)
|
220 | Jan 1, 2017 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 105 µg/L, federal limit 80 µg/L (1.3 times the limit)
|
220 | Oct 1, 2016 | Resolved | No |
Monitoring and reporting issues
Since October 2016Missed tests or reports, not contaminants found above a limit.
| Issue | Start date | Status |
|---|---|---|
|
Public Notice
OTHER
|
Jul 9, 2020 | Resolved |
|
Total Trihalomethanes (TTHMs)
Monitoring and reporting
|
Jul 31, 2016 | Resolved |
Full record since 1993
EPA's records for Chatham Water System go back to 1993. Before October 19, 2016 they list 23 health-based violations (21 resolved, 2 archived by EPA without a recorded fix) and 21 monitoring or reporting violations.
| Violations that began in | Health-based | Monitoring and reporting |
|---|---|---|
| 1990s | 1 | 1 |
| 2000s | 12 | 2 |
| 2010 to October 18, 2016 | 10 | 18 |
| October 19, 2016 to 2019 | 17 | 0 |
| 2020s | 19 | 1 |
Most recent health-based violation before October 19, 2016: Total Trihalomethanes (TTHMs), began October 2016, Resolved.
Show all 23 health-based violations before October 19, 2016
| Contaminant | Start date | Status |
|---|---|---|
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 105 µg/L, federal limit 80 µg/L (1.3 times the limit)
|
Oct 1, 2016 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 118 µg/L, federal limit 80 µg/L (1.5 times the limit)
|
Jul 1, 2016 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 126 µg/L, federal limit 80 µg/L (1.6 times the limit)
|
Apr 1, 2016 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 162 µg/L, federal limit 80 µg/L (2 times the limit)
|
Jan 1, 2016 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 180 µg/L, federal limit 80 µg/L (2.3 times the limit)
|
Oct 1, 2015 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 193 µg/L, federal limit 80 µg/L (2.4 times the limit)
|
Jul 1, 2015 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 149 µg/L, federal limit 80 µg/L (1.9 times the limit)
|
Apr 1, 2015 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 104 µg/L, federal limit 80 µg/L (1.3 times the limit)
|
Jan 1, 2015 | Resolved |
|
Total Coliform
Contaminant limit exceeded
|
Oct 1, 2012 | Resolved |
|
Total Coliform
Contaminant limit exceeded
|
Aug 1, 2011 | Archived |
|
Total Coliform
Contaminant limit exceeded
|
Sep 1, 2008 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 88 µg/L, federal limit 80 µg/L (1.1 times the limit)
|
Apr 1, 2008 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 62 µg/L, federal limit 60 µg/L (at or just above the limit)
|
Jan 1, 2008 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 117 µg/L, federal limit 80 µg/L (1.5 times the limit)
|
Jan 1, 2008 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 110 µg/L, federal limit 80 µg/L (1.4 times the limit)
|
Oct 1, 2007 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 65 µg/L, federal limit 60 µg/L (1.1 times the limit)
|
Jul 1, 2007 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 110 µg/L, federal limit 80 µg/L (1.4 times the limit)
|
Jul 1, 2007 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 138 µg/L, federal limit 80 µg/L (1.7 times the limit)
|
Jan 1, 2007 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 155 µg/L, federal limit 80 µg/L (1.9 times the limit)
|
Oct 1, 2006 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 127 µg/L, federal limit 80 µg/L (1.6 times the limit)
|
Jul 1, 2006 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 140 µg/L, federal limit 80 µg/L (1.8 times the limit)
|
Apr 1, 2006 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 116 µg/L, federal limit 80 µg/L (1.5 times the limit)
|
Jan 1, 2006 | Resolved |
|
Total Coliform
Contaminant limit exceeded
|
Jul 15, 1993 | Archived |
Enforcement actions
Louisiana regulators took 2 formal enforcement actions against Chatham Water System between 2007 and 2016. The most recent was a compliance order (no penalty) in June 2016.
| Date | By | Action | Violations covered |
|---|---|---|---|
| Jun 21, 2016 | Louisiana | Compliance order (no penalty) | 42 violations (37 health-based): Total Trihalomethanes (TTHMs), Haloacetic Acids (HAA5), Total Coliform, Chlorine, Revised Total Coliform Rule |
| Sep 4, 2007 | Louisiana | Compliance order (no penalty) | 17 violations (11 health-based): Total Trihalomethanes (TTHMs), Haloacetic Acids (HAA5) |
What the violations mean
Total Trihalomethanes (TTHMs)
22 incidentsDisinfection byproduct levels exceeded the federal limit
Long-term TTHM exposure may increase bladder cancer risk
Haloacetic Acids (HAA5)
9 incidentsHaloacetic acid byproducts exceeded the federal limit
Long-term exposure to HAAs may increase cancer risk
Groundwater Rule
6 incidentsThe system did not complete a treatment step or action that the Groundwater Rule requires (a treatment technique violation).
The utility had to notify customers about each of these violations.
Where the water comes from
Chatham Water System draws water from 3 wells.
Annual water quality report
Chatham Water System must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.
Where the state allows it, systems serving fewer than 10,000 people may publish the report in a local newspaper or news site instead of mailing it, and must provide a copy on request.
Find a posted report with EPA's Consumer Confidence Report search
Testing your own water
To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Louisiana.
Certified drinking water labs by state EPA guidance for private wells