Public water system record

South Desoto Water System

Serves an area of De Soto Parish, LA · 963 people served

Federal records show 39 health-based violations and 23 monitoring/reporting issues for South Desoto Water System in the last ten years. The most serious issue in this window was a Total Trihalomethanes (TTHMs) violation that EPA lists as archived, not resolved.

  • LA1031029
  • MANSFIELD
  • LA
  • 963 served

System profile

Source water Groundwater
ZIP 71052
EPA system ID LA1031029

Verify this system on EPA ECHO →

Health-based violations, last 10 years
39
Resolved
3
Unresolved
0
Archived by EPA
36
Any acute record
No
Monitoring issues, last 10 years
23

Key facts

  • South Desoto Water System draws water from 2 wells.
  • Highest measured level in the last 10 years: Total Trihalomethanes (TTHMs), 0.232 mg/L, federal limit 0.08 mg/L (2.9 times the limit), 2022.
  • Most recent formal enforcement: compliance order (no penalty) by Louisiana, April 2018.
  • Record on file since 1999, with 15 health-based violations before October 19, 2016.
  • Lead pipe inventory: 0 lead and 0 unknown out of 409 service lines.

Check whether South Desoto Water System serves your address

Address suggestions by Mapbox

Health-based violations

Since October 2016

Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.

Contaminant Rule family Start date Status Acute
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.126 mg/L, federal limit 0.08 mg/L (1.6 times the limit)
220 Oct 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.133 mg/L, federal limit 0.08 mg/L (1.7 times the limit)
220 Jul 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.143 mg/L, federal limit 0.08 mg/L (1.8 times the limit)
220 Apr 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.148 mg/L, federal limit 0.08 mg/L (1.9 times the limit)
220 Jan 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.154 mg/L, federal limit 0.08 mg/L (1.9 times the limit)
220 Oct 1, 2024 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.149 mg/L, federal limit 0.08 mg/L (1.9 times the limit)
220 Jul 1, 2024 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.162 mg/L, federal limit 0.08 mg/L (2 times the limit)
220 Apr 1, 2024 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.167 mg/L, federal limit 0.08 mg/L (2.1 times the limit)
220 Jan 1, 2024 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.161 mg/L, federal limit 0.08 mg/L (2 times the limit)
220 Oct 1, 2023 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.182 mg/L, federal limit 0.08 mg/L (2.3 times the limit)
220 Jul 1, 2023 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.193 mg/L, federal limit 0.08 mg/L (2.4 times the limit)
220 Apr 1, 2023 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.202 mg/L, federal limit 0.08 mg/L (2.5 times the limit)
220 Jan 1, 2023 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.221 mg/L, federal limit 0.08 mg/L (2.8 times the limit)
220 Oct 1, 2022 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.232 mg/L, federal limit 0.08 mg/L (2.9 times the limit)
220 Jul 1, 2022 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.19 mg/L, federal limit 0.08 mg/L (2.4 times the limit)
220 Apr 1, 2022 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.171 mg/L, federal limit 0.08 mg/L (2.1 times the limit)
220 Jan 1, 2022 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.125 mg/L, federal limit 0.08 mg/L (1.6 times the limit)
220 Oct 1, 2021 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.101 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
220 Jul 1, 2021 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.126 mg/L, federal limit 0.08 mg/L (1.6 times the limit)
220 Apr 1, 2021 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.144 mg/L, federal limit 0.08 mg/L (1.8 times the limit)
220 Jan 1, 2021 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.171 mg/L, federal limit 0.08 mg/L (2.1 times the limit)
220 Oct 1, 2020 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.17 mg/L, federal limit 0.08 mg/L (2.1 times the limit)
220 Jul 1, 2020 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.171 mg/L, federal limit 0.08 mg/L (2.1 times the limit)
220 Apr 1, 2020 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.166 mg/L, federal limit 0.08 mg/L (2.1 times the limit)
220 Jan 1, 2020 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.174 mg/L, federal limit 0.08 mg/L (2.2 times the limit)
220 Oct 1, 2019 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.169 mg/L, federal limit 0.08 mg/L (2.1 times the limit)
220 Jul 1, 2019 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.163 mg/L, federal limit 0.08 mg/L (2 times the limit)
220 Apr 1, 2019 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.159 mg/L, federal limit 0.08 mg/L (2 times the limit)
220 Jan 1, 2019 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Groundwater Rule
Treatment technique failure
140 Oct 2, 2018 Resolved No
Groundwater Rule
Treatment technique failure
140 Oct 2, 2018 Resolved No
Groundwater Rule
Treatment technique failure
140 Oct 2, 2018 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.149 mg/L, federal limit 0.08 mg/L (1.9 times the limit)
220 Oct 1, 2018 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 150 µg/L, federal limit 80 µg/L (1.9 times the limit)
220 Jul 1, 2018 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 147 µg/L, federal limit 80 µg/L (1.8 times the limit)
220 Apr 1, 2018 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 144 µg/L, federal limit 80 µg/L (1.8 times the limit)
220 Jan 1, 2018 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 146 µg/L, federal limit 80 µg/L (1.8 times the limit)
220 Oct 1, 2017 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 153 µg/L, federal limit 80 µg/L (1.9 times the limit)
220 Jul 1, 2017 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 124 µg/L, federal limit 80 µg/L (1.6 times the limit)
220 Apr 1, 2017 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 107 µg/L, federal limit 80 µg/L (1.3 times the limit)
220 Jan 1, 2017 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No

Monitoring and reporting issues

Since October 2016

Missed tests or reports, not contaminants found above a limit.

Issue Start date Status
Public Notice
OTHER
May 23, 2024 Resolved
Public Notice
OTHER
Feb 24, 2024 Resolved
Public Notice
OTHER
Oct 31, 2023 Resolved
Public Notice
OTHER
Sep 2, 2023 Resolved
Total Trihalomethanes (TTHMs)
Monitoring and reporting
May 1, 2023 Active
Enforcement action in place
Public Notice
OTHER
Apr 25, 2022 Resolved
Consumer Confidence Rule
OTHER
Jul 1, 2021 Resolved
Public Notice
OTHER
Feb 24, 2021 Resolved
Public Notice
OTHER
Aug 21, 2019 Resolved
Public Notice
OTHER
May 23, 2019 Resolved
Public Notice
OTHER
Mar 2, 2019 Resolved
Public Notice
OTHER
Feb 9, 2019 Resolved
Total Trihalomethanes (TTHMs)
Monitoring and reporting
Oct 31, 2017 Resolved
Total Trihalomethanes (TTHMs)
Monitoring and reporting
Jul 31, 2017 Resolved
Public Notice
OTHER
May 25, 2017 Resolved
Total Trihalomethanes (TTHMs)
Monitoring and reporting
May 1, 2017 Resolved
Public Notice
OTHER
Nov 14, 2016 Resolved
Haloacetic Acids (HAA5)
Monitoring and reporting
Oct 1, 2016 Resolved
Total Trihalomethanes (TTHMs)
Monitoring and reporting
Oct 1, 2016 Resolved
Lead and Copper Rule
Monitoring and reporting
Apr 21, 2016 Resolved
Public Notice
OTHER
Feb 29, 2016 Resolved
Total Trihalomethanes (TTHMs)
Monitoring and reporting
Oct 31, 2014 Resolved
Public Notice
OTHER
Apr 28, 2012 Resolved

Full record since 1999

EPA's records for South Desoto Water System go back to 1999. Before October 19, 2016 they list 15 health-based violations (1 resolved, 14 archived by EPA without a recorded fix) and 44 monitoring or reporting violations.

Violations that began in Health-based Monitoring and reporting
1990s 0 1
2000s 12 13
2010 to October 18, 2016 3 30
October 19, 2016 to 2019 15 9
2020s 24 8

Most recent health-based violation before October 19, 2016: Total Trihalomethanes (TTHMs), began April 2015, Resolved.

Show all 15 health-based violations before October 19, 2016
Contaminant Start date Status
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 92 µg/L, federal limit 80 µg/L (1.2 times the limit)
Apr 1, 2015 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 87 µg/L, federal limit 80 µg/L (1.1 times the limit)
Oct 1, 2011 Archived
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 99 µg/L, federal limit 80 µg/L (1.2 times the limit)
Jul 1, 2011 Archived
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 102 µg/L, federal limit 80 µg/L (1.3 times the limit)
Jan 1, 2009 Archived
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 111 µg/L, federal limit 80 µg/L (1.4 times the limit)
Oct 1, 2008 Archived
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 99 µg/L, federal limit 80 µg/L (1.2 times the limit)
Jul 1, 2008 Archived
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 83 µg/L, federal limit 80 µg/L (at or just above the limit)
Apr 1, 2007 Archived
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 96 µg/L, federal limit 80 µg/L (1.2 times the limit)
Jan 1, 2007 Archived
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 113 µg/L, federal limit 80 µg/L (1.4 times the limit)
Oct 1, 2006 Archived
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 118 µg/L, federal limit 80 µg/L (1.5 times the limit)
Jul 1, 2006 Archived
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 111 µg/L, federal limit 80 µg/L (1.4 times the limit)
Apr 1, 2006 Archived
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 95 µg/L, federal limit 80 µg/L (1.2 times the limit)
Jan 1, 2006 Archived
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 84 µg/L, federal limit 80 µg/L (1.1 times the limit)
Oct 1, 2005 Archived
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 104 µg/L, federal limit 80 µg/L (1.3 times the limit)
Apr 1, 2005 Archived
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 81 µg/L, federal limit 80 µg/L (at or just above the limit)
Jan 1, 2005 Archived

Enforcement actions

Louisiana regulators took 2 formal enforcement actions against South Desoto Water System between 2006 and 2018. The most recent was a compliance order (no penalty) in April 2018.

Date By Action Violations covered
Apr 24, 2018 Louisiana Compliance order (no penalty) 58 violations (37 health-based): Total Trihalomethanes (TTHMs), Lead and Copper Rule, Public Notice
Mar 13, 2006 Louisiana Compliance order (no penalty) 36 violations (14 health-based): Total Trihalomethanes (TTHMs), Haloacetic Acids (HAA5)

What the violations mean

Total Trihalomethanes (TTHMs)

36 incidents

Disinfection byproduct levels exceeded the federal limit

Long-term TTHM exposure may increase bladder cancer risk

Groundwater Rule

3 incidents

The system did not complete a treatment step or action that the Groundwater Rule requires (a treatment technique violation).

The utility had to notify customers about each of these violations.

Where the water comes from

South Desoto Water System draws water from 2 wells.

Annual water quality report

South Desoto Water System must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.

Where the state allows it, systems serving fewer than 10,000 people may publish the report in a local newspaper or news site instead of mailing it, and must provide a copy on request.

Find a posted report with EPA's Consumer Confidence Report search

Testing your own water

To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Louisiana.