Public water system record
Town of Clayton Water System
Serves Clayton, Concordia Parish, LA · 723 people served
Federal records show 50 health-based violations and 11 monitoring/reporting issues for Town of Clayton Water System in the last ten years, including an unresolved Groundwater Rule violation.
System profile
- Health-based violations, last 10 years
- 50
- Resolved
- 9
- Unresolved
- 5
- Archived by EPA
- 36
- Any acute record
- No
- Monitoring issues, last 10 years
- 11
Key facts
- Town of Clayton Water System draws water from 2 wells.
- Highest measured level in the last 10 years: Total Trihalomethanes (TTHMs), 0.142 mg/L, federal limit 0.08 mg/L (1.8 times the limit), 2024.
- Most recent formal enforcement: compliance order (no penalty) by Louisiana, March 2021.
- Record on file since 1992, with 11 health-based violations before October 19, 2016.
- Lead pipe inventory: 0 lead and 5 unknown out of 231 service lines.
Check whether Town of Clayton Water System serves your address
Health-based violations
Since October 2016Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.
| Contaminant | Rule family | Start date | Status | Acute |
|---|---|---|---|---|
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.108 mg/L, federal limit 0.08 mg/L (1.4 times the limit)
|
220 | Oct 1, 2025 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.107 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
|
220 | Jul 1, 2025 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.109 mg/L, federal limit 0.08 mg/L (1.4 times the limit)
|
220 | Apr 1, 2025 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Groundwater Rule
Treatment technique failure
|
140 | Feb 6, 2025 | Active | No |
|
Groundwater Rule
Treatment technique failure
|
140 | Feb 6, 2025 | Active | No |
|
Groundwater Rule
Treatment technique failure
|
140 | Feb 6, 2025 | Resolved | No |
|
Groundwater Rule
Treatment technique failure
|
140 | Feb 6, 2025 | Resolved | No |
|
Groundwater Rule
Treatment technique failure
|
140 | Feb 6, 2025 | Resolved | No |
|
Groundwater Rule
Treatment technique failure
|
140 | Feb 6, 2025 | Active | No |
|
Groundwater Rule
Treatment technique failure
|
140 | Feb 6, 2025 | Active | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.107 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
|
220 | Jan 1, 2025 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.118 mg/L, federal limit 0.08 mg/L (1.5 times the limit)
|
220 | Oct 1, 2024 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.123 mg/L, federal limit 0.08 mg/L (1.5 times the limit)
|
220 | Jul 1, 2024 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.129 mg/L, federal limit 0.08 mg/L (1.6 times the limit)
|
220 | Apr 1, 2024 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.142 mg/L, federal limit 0.08 mg/L (1.8 times the limit)
|
220 | Jan 1, 2024 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.138 mg/L, federal limit 0.08 mg/L (1.7 times the limit)
|
220 | Oct 1, 2023 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.139 mg/L, federal limit 0.08 mg/L (1.7 times the limit)
|
220 | Jul 1, 2023 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.137 mg/L, federal limit 0.08 mg/L (1.7 times the limit)
|
220 | Apr 1, 2023 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.127 mg/L, federal limit 0.08 mg/L (1.6 times the limit)
|
220 | Jan 1, 2023 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.124 mg/L, federal limit 0.08 mg/L (1.6 times the limit)
|
220 | Oct 1, 2022 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.124 mg/L, federal limit 0.08 mg/L (1.6 times the limit)
|
220 | Jul 1, 2022 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.12 mg/L, federal limit 0.08 mg/L (1.5 times the limit)
|
220 | Apr 1, 2022 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.127 mg/L, federal limit 0.08 mg/L (1.6 times the limit)
|
220 | Jan 1, 2022 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.137 mg/L, federal limit 0.08 mg/L (1.7 times the limit)
|
220 | Oct 1, 2021 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.139 mg/L, federal limit 0.08 mg/L (1.7 times the limit)
|
220 | Jul 1, 2021 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.142 mg/L, federal limit 0.08 mg/L (1.8 times the limit)
|
220 | Apr 1, 2021 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.132 mg/L, federal limit 0.08 mg/L (1.7 times the limit)
|
220 | Jan 1, 2021 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.121 mg/L, federal limit 0.08 mg/L (1.5 times the limit)
|
220 | Oct 1, 2020 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.121 mg/L, federal limit 0.08 mg/L (1.5 times the limit)
|
220 | Jul 1, 2020 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.113 mg/L, federal limit 0.08 mg/L (1.4 times the limit)
|
220 | Apr 1, 2020 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Groundwater Rule
Treatment technique failure
|
140 | Jan 6, 2020 | Resolved | No |
|
Groundwater Rule
Treatment technique failure
|
140 | Jan 6, 2020 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.124 mg/L, federal limit 0.08 mg/L (1.6 times the limit)
|
220 | Jan 1, 2020 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.131 mg/L, federal limit 0.08 mg/L (1.6 times the limit)
|
220 | Oct 1, 2019 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.127 mg/L, federal limit 0.08 mg/L (1.6 times the limit)
|
220 | Jul 1, 2019 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.134 mg/L, federal limit 0.08 mg/L (1.7 times the limit)
|
220 | Apr 1, 2019 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.104 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
|
220 | Jan 1, 2019 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Groundwater Rule
Treatment technique failure
|
140 | Dec 25, 2018 |
Active
Enforcement action in place
|
No |
|
Groundwater Rule
Treatment technique failure
|
140 | Dec 25, 2018 | Resolved | No |
|
Groundwater Rule
Treatment technique failure
|
140 | Dec 25, 2018 | Resolved | No |
|
Groundwater Rule
Treatment technique failure
|
140 | Dec 25, 2018 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.095 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
220 | Oct 1, 2018 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 91 µg/L, federal limit 80 µg/L (1.1 times the limit)
|
220 | Jul 1, 2018 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 83 µg/L, federal limit 80 µg/L (at or just above the limit)
|
220 | Apr 1, 2018 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Revised Total Coliform Rule
Treatment technique failure
|
110 | Jan 3, 2018 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 102 µg/L, federal limit 80 µg/L (1.3 times the limit)
|
220 | Jan 1, 2018 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 113 µg/L, federal limit 80 µg/L (1.4 times the limit)
|
220 | Oct 1, 2017 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 118 µg/L, federal limit 80 µg/L (1.5 times the limit)
|
220 | Jul 1, 2017 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 124 µg/L, federal limit 80 µg/L (1.6 times the limit)
|
220 | Apr 1, 2017 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 110 µg/L, federal limit 80 µg/L (1.4 times the limit)
|
220 | Jan 1, 2017 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
Monitoring and reporting issues
Since October 2016Missed tests or reports, not contaminants found above a limit.
| Issue | Start date | Status |
|---|---|---|
|
Public Notice
OTHER
|
May 13, 2025 | Resolved |
|
Total Trihalomethanes (TTHMs)
Monitoring and reporting
|
May 1, 2023 |
Active
Enforcement action in place
|
|
Public Notice
OTHER
|
Jun 16, 2018 | Resolved |
|
Consumer Confidence Rule
OTHER
|
Oct 1, 2017 | Resolved |
|
Public Notice
OTHER
|
Feb 22, 2017 | Resolved |
|
Public Notice
OTHER
|
Feb 11, 2017 | Resolved |
|
Haloacetic Acids (HAA5)
Monitoring and reporting
|
Oct 1, 2016 | Resolved |
|
Total Trihalomethanes (TTHMs)
Monitoring and reporting
|
Oct 1, 2016 | Resolved |
|
Total Trihalomethanes (TTHMs)
Monitoring and reporting
|
Jul 31, 2014 | Resolved |
|
Total Trihalomethanes (TTHMs)
Monitoring and reporting
|
May 1, 2014 | Resolved |
|
Haloacetic Acids (HAA5)
Monitoring and reporting
|
May 1, 2014 | Resolved |
Full record since 1992
EPA's records for Town of Clayton Water System go back to 1992. Before October 19, 2016 they list 11 health-based violations (3 resolved, 8 archived by EPA without a recorded fix) and 33 monitoring or reporting violations.
| Violations that began in | Health-based | Monitoring and reporting |
|---|---|---|
| 1990s | 6 | 1 |
| 2000s | 1 | 7 |
| 2010 to October 18, 2016 | 4 | 25 |
| October 19, 2016 to 2019 | 17 | 4 |
| 2020s | 33 | 2 |
Most recent health-based violation before October 19, 2016: Total Trihalomethanes (TTHMs), began April 2014, Archived.
Show all 11 health-based violations before October 19, 2016
| Contaminant | Start date | Status |
|---|---|---|
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 98 µg/L, federal limit 80 µg/L (1.2 times the limit)
|
Apr 1, 2014 | Archived |
|
Total Coliform
Contaminant limit exceeded
|
Apr 1, 2012 | Resolved |
|
Groundwater Rule
Treatment technique failure
|
Jan 31, 2012 | Resolved |
|
Total Coliform
Contaminant limit exceeded
|
Jan 1, 2010 | Resolved |
|
Total Coliform
Contaminant limit exceeded
|
Aug 1, 2001 | Archived |
|
Total Coliform
Contaminant limit exceeded
|
Jun 1, 1999 | Archived |
|
Total Coliform
Contaminant limit exceeded
|
Dec 1, 1998 | Archived |
|
Total Coliform
Contaminant limit exceeded
|
Feb 1, 1996 | Archived |
|
Total Coliform
Contaminant limit exceeded
|
Dec 1, 1995 | Archived |
|
Total Coliform (acute)
Contaminant limit exceeded
|
Aug 1, 1993 | Archived |
|
Total Coliform
Contaminant limit exceeded
|
Aug 1, 1992 | Archived |
Enforcement actions
Louisiana regulators and EPA took 4 formal enforcement actions against Town of Clayton Water System between 2005 and 2021. The most recent was a compliance order (no penalty) in March 2021.
| Date | By | Action | Violations covered |
|---|---|---|---|
| Mar 19, 2021 | Louisiana | Compliance order (no penalty) | 5 violations (5 health-based): Groundwater Rule |
| Jul 29, 2015 | EPA | Compliance order (no penalty) | 1 violation (1 health-based): Groundwater Rule |
| Jul 1, 2015 | Louisiana | Compliance order (no penalty) | 65 violations (38 health-based): E. coli, Total Coliform, Total Trihalomethanes (TTHMs), Haloacetic Acids (HAA5), Chlorine |
| Aug 5, 2005 | Louisiana | Compliance order (no penalty) | 2 violations: Total Trihalomethanes (TTHMs), Haloacetic Acids (HAA5) |
What the violations mean
Total Trihalomethanes (TTHMs)
36 incidentsDisinfection byproduct levels exceeded the federal limit
Long-term TTHM exposure may increase bladder cancer risk
Groundwater Rule
13 incidentsThe system did not complete a treatment step or action that the Groundwater Rule requires (a treatment technique violation).
The utility had to notify customers about each of these violations.
Revised Total Coliform Rule
1 incidentThe system did not meet a requirement of the Revised Total Coliform Rule
Coliform and E. coli rules protect against bacteria in the distribution system
Where the water comes from
Town of Clayton Water System draws water from 2 wells.
Annual water quality report
Town of Clayton Water System must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.
Where the state allows it, systems serving fewer than 10,000 people may publish the report in a local newspaper or news site instead of mailing it, and must provide a copy on request.
Find a posted report with EPA's Consumer Confidence Report search
Testing your own water
To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Louisiana.
Certified drinking water labs by state EPA guidance for private wells