Public water system record

St Marys Water System

Serves an area of Bossier Parish, LA · 294 people served

Federal records show 16 health-based violations and 10 monitoring/reporting issues for St Marys Water System in the last ten years, including an unresolved LEAD AND COPPER RULE REVISIONS violation.

  • LA1015023
  • PLAIN DEALING
  • LA
  • 294 served

System profile

Source water Groundwater
ZIP 71064
EPA system ID LA1015023

Verify this system on EPA ECHO →

Health-based violations, last 10 years
16
Resolved
8
Unresolved
8
Any acute record
No
Monitoring issues, last 10 years
10

Key facts

  • St Marys Water System draws water from 2 wells.
  • Highest measured level in the last 10 years: Total Trihalomethanes (TTHMs), 0.093 mg/L, federal limit 0.08 mg/L (1.2 times the limit), 2019.
  • Most recent formal enforcement: compliance order (no penalty) by Louisiana, October 2025.
  • Record on file since 1999, with 6 health-based violations before October 19, 2016.

Check whether St Marys Water System serves your address

Address suggestions by Mapbox

Health-based violations

Since October 2016

Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.

Contaminant Rule family Start date Status Acute
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.081 mg/L, federal limit 0.08 mg/L (at or just above the limit)
220 Jan 1, 2025 Resolved No
LEAD AND COPPER RULE REVISIONS
Treatment technique failure
350 Oct 17, 2024 Active No
Groundwater Rule
Treatment technique failure
140 Mar 23, 2023 Active No
Groundwater Rule
Treatment technique failure
140 Mar 23, 2023 Active No
Groundwater Rule
Treatment technique failure
140 Mar 23, 2023 Active No
Groundwater Rule
Treatment technique failure
140 Mar 23, 2023 Active
Enforcement action in place
No
Groundwater Rule
Treatment technique failure
140 Mar 23, 2023 Active
Enforcement action in place
No
Groundwater Rule
Treatment technique failure
140 Mar 23, 2023 Active
Enforcement action in place
No
Revised Total Coliform Rule
Treatment technique failure
110 Mar 14, 2023 Active
Enforcement action in place
No
Groundwater Rule
Treatment technique failure
140 Mar 1, 2021 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.082 mg/L, federal limit 0.08 mg/L (at or just above the limit)
220 Oct 1, 2019 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.086 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
220 Jul 1, 2019 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.093 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
220 Apr 1, 2019 Resolved No
Groundwater Rule
Treatment technique failure
140 Jan 2, 2019 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.082 mg/L, federal limit 0.08 mg/L (at or just above the limit)
220 Jan 1, 2019 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 82 µg/L, federal limit 80 µg/L (at or just above the limit)
220 Jul 1, 2018 Resolved No

Monitoring and reporting issues

Since October 2016

Missed tests or reports, not contaminants found above a limit.

Issue Start date Status
Public Notice
OTHER
Apr 29, 2025 Resolved
Lead and Copper Rule
Monitoring and reporting
Dec 20, 2024 Resolved
LEAD AND COPPER RULE REVISIONS
RPT
Oct 17, 2024 Active
Public Notice
OTHER
May 4, 2023 Resolved
Public Notice
OTHER
Apr 21, 2023 Active
Enforcement action in place
Lead and Copper Rule
Monitoring and reporting
Apr 5, 2022 Resolved
Public Notice
OTHER
Oct 16, 2018 Resolved
Total Trihalomethanes (TTHMs)
Monitoring and reporting
May 1, 2017 Resolved
Total Trihalomethanes (TTHMs)
Monitoring and reporting
Jan 31, 2015 Resolved
Haloacetic Acids (HAA5)
Monitoring and reporting
May 1, 2014 Resolved

Full record since 1999

EPA's records for St Marys Water System go back to 1999. Before October 19, 2016 they list 6 health-based violations (6 resolved) and 18 monitoring or reporting violations.

Violations that began in Health-based Monitoring and reporting
1990s 0 1
2000s 1 1
2010 to October 18, 2016 5 16
October 19, 2016 to 2019 6 2
2020s 10 6

Most recent health-based violation before October 19, 2016: Total Trihalomethanes (TTHMs), began January 2016, Resolved.

Show all 6 health-based violations before October 19, 2016
Contaminant Start date Status
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 90 µg/L, federal limit 80 µg/L (1.1 times the limit)
Jan 1, 2016 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 94 µg/L, federal limit 80 µg/L (1.2 times the limit)
Oct 1, 2015 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 92 µg/L, federal limit 80 µg/L (1.2 times the limit)
Jul 1, 2015 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 91 µg/L, federal limit 80 µg/L (1.1 times the limit)
Apr 1, 2015 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 82 µg/L, federal limit 80 µg/L (at or just above the limit)
Jul 1, 2014 Resolved
Total Coliform
Contaminant limit exceeded
Oct 1, 2009 Resolved

Enforcement actions

Louisiana regulators and EPA took 5 formal enforcement actions against St Marys Water System between 2000 and 2025. The most recent was a compliance order (no penalty) in October 2025.

Date By Action Violations covered
Oct 3, 2025 Louisiana Compliance order (no penalty) 8 violations (4 health-based): Lead and Copper Rule, Groundwater Rule, Public Notice, Revised Total Coliform Rule
Aug 11, 2020 Louisiana Compliance order (no penalty) 10 violations (10 health-based): Total Trihalomethanes (TTHMs)
May 19, 2016 Louisiana Compliance order (no penalty) 12 violations (10 health-based): Haloacetic Acids (HAA5), Total Trihalomethanes (TTHMs)
Nov 12, 2002 EPA Compliance order (no penalty) 1 violation: Consumer Confidence Rule
May 16, 2000 EPA Compliance order (no penalty) 1 violation: Consumer Confidence Rule

What the violations mean

Groundwater Rule

8 incidents

The system did not complete a treatment step or action that the Groundwater Rule requires (a treatment technique violation).

The utility had to notify customers about each of these violations.

Total Trihalomethanes (TTHMs)

6 incidents

Disinfection byproduct levels exceeded the federal limit

Long-term TTHM exposure may increase bladder cancer risk

LEAD AND COPPER RULE REVISIONS

1 incident

The system did not complete a treatment step or action that the LEAD AND COPPER RULE REVISIONS requires (a treatment technique violation).

The utility had to notify customers about this violation.

Revised Total Coliform Rule

1 incident

The system did not meet a requirement of the Revised Total Coliform Rule

Coliform and E. coli rules protect against bacteria in the distribution system

Where the water comes from

St Marys Water System draws water from 2 wells.

Annual water quality report

St Marys Water System must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.

Systems serving 500 or fewer people may meet the rule by telling customers the report is available on request, so you may need to ask St Marys Water System for a copy.

Find a posted report with EPA's Consumer Confidence Report search

Testing your own water

To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Louisiana.