Public water system record
North Ridge Water & Light Co.
Serves Valdosta and Bemiss, Lowndes County, GA · 354 people served
Federal records show 14 health-based violations and 1 monitoring/reporting issue for North Ridge Water & Light Co. in the last ten years. The most serious issue in this window was a Total Trihalomethanes (TTHMs) violation that EPA lists as archived, not resolved.
System profile
- Health-based violations, last 10 years
- 14
- Resolved
- 10
- Unresolved
- 0
- Archived by EPA
- 4
- Any acute record
- No
- Monitoring issues, last 10 years
- 1
Key facts
- North Ridge Water & Light Co. draws water from 2 wells.
- Highest measured level in the last 10 years: Haloacetic Acids (HAA5), 0.126 mg/L, federal limit 0.06 mg/L (2.1 times the limit), 2022.
- Most recent formal enforcement: compliance order (no penalty) by Georgia, July 2022.
- Record on file since 1993, with 0 health-based violations before October 19, 2016.
- Lead pipe inventory: 0 lead and 135 unknown out of 135 service lines.
Check whether North Ridge Water & Light Co. serves your address
Health-based violations
Since October 2016Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.
| Contaminant | Rule family | Start date | Status | Acute |
|---|---|---|---|---|
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.09 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
220 | Jul 1, 2025 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.08 mg/L, federal limit 0.06 mg/L (1.3 times the limit)
|
220 | Jul 1, 2025 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.086 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
220 | Apr 1, 2025 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.069 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
|
220 | Apr 1, 2025 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.067 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
|
220 | Oct 1, 2022 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.09 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
220 | Jul 1, 2022 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.098 mg/L, federal limit 0.06 mg/L (1.6 times the limit)
|
220 | Jul 1, 2022 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.104 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
|
220 | Apr 1, 2022 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.113 mg/L, federal limit 0.06 mg/L (1.9 times the limit)
|
220 | Apr 1, 2022 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.12 mg/L, federal limit 0.08 mg/L (1.5 times the limit)
|
220 | Jan 1, 2022 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.126 mg/L, federal limit 0.06 mg/L (2.1 times the limit)
|
220 | Jan 1, 2022 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.097 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
220 | Oct 1, 2021 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.099 mg/L, federal limit 0.06 mg/L (1.7 times the limit)
|
220 | Oct 1, 2021 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.072 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
|
220 | Jul 1, 2021 | Resolved | No |
Monitoring and reporting issues
Since October 2016Missed tests or reports, not contaminants found above a limit.
| Issue | Start date | Status |
|---|---|---|
|
Public Notice
OTHER
|
Apr 1, 2023 | Active |
Full record since 1993
EPA's records for North Ridge Water & Light Co. go back to 1993. Before October 19, 2016 they list no health-based violations and 10 monitoring or reporting violations.
| Violations that began in | Health-based | Monitoring and reporting |
|---|---|---|
| 1990s | 0 | 1 |
| 2000s | 0 | 5 |
| 2010 to October 18, 2016 | 0 | 4 |
| 2020s | 14 | 1 |
Enforcement actions
Georgia regulators took 1 formal enforcement action against North Ridge Water & Light Co. in 2022. The most recent was a compliance order (no penalty) in July 2022.
| Date | By | Action | Violations covered |
|---|---|---|---|
| Jul 29, 2022 | Georgia | Compliance order (no penalty) | 10 violations (10 health-based): Haloacetic Acids (HAA5), Total Trihalomethanes (TTHMs) |
What the violations mean
Haloacetic Acids (HAA5)
8 incidentsHaloacetic acid byproducts exceeded the federal limit
Long-term exposure to HAAs may increase cancer risk
Total Trihalomethanes (TTHMs)
6 incidentsDisinfection byproduct levels exceeded the federal limit
Long-term TTHM exposure may increase bladder cancer risk
Where the water comes from
North Ridge Water & Light Co. draws water from 2 wells.
Annual water quality report
North Ridge Water & Light Co. must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.
Systems serving 500 or fewer people may meet the rule by telling customers the report is available on request, so you may need to ask North Ridge Water & Light Co. for a copy.
Find a posted report with EPA's Consumer Confidence Report search
Testing your own water
To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Georgia.
Certified drinking water labs by state EPA guidance for private wells