Public water system record

Harris Farms South 101-144

Serves an area of Fresno County, CA · 182 people served

Federal records show 2 health-based violations and no monitoring/reporting issues for Harris Farms South 101-144 in the last ten years. The most serious issue in this window was a resolved Haloacetic Acids (HAA5) violation.

  • CA1009028
  • COALINGA
  • CA
  • 182 served

System profile

Source water Surface water
ZIP 93210
EPA system ID CA1009028

Verify this system on EPA ECHO →

Health-based violations, last 10 years
2
Resolved
2
Unresolved
0
Any acute record
No
Monitoring issues, last 10 years
0

Key facts

  • Harris Farms South 101-144 draws water from 1 surface water intake.
  • Highest measured level in the last 10 years: Haloacetic Acids (HAA5), 0.1008 mg/L, federal limit 0.06 mg/L (1.7 times the limit), 2016.
  • Most recent formal enforcement: compliance order (no penalty) by California, November 2015.
  • Record on file since 1980, with 38 health-based violations before October 19, 2016.
  • Lead pipe inventory: 0 lead and 0 unknown out of 25 service lines.

Check whether Harris Farms South 101-144 serves your address

Address suggestions by Mapbox

Health-based violations

Since October 2016

Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.

Contaminant Rule family Start date Status Acute
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.098 mg/L, federal limit 0.06 mg/L (1.6 times the limit)
220 Jan 1, 2017 Resolved No
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.1008 mg/L, federal limit 0.06 mg/L (1.7 times the limit)
220 Oct 1, 2016 Resolved No

Full record since 1980

EPA's records for Harris Farms South 101-144 go back to 1980. Before October 19, 2016 they list 38 health-based violations (38 resolved) and 28 monitoring or reporting violations.

Violations that began in Health-based Monitoring and reporting
1980s 0 26
2000s 8 0
2010 to October 18, 2016 30 2
October 19, 2016 to 2019 1 0

Most recent health-based violation before October 19, 2016: Haloacetic Acids (HAA5), began October 2016, Resolved.

Show all 38 health-based violations before October 19, 2016
Contaminant Start date Status
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.1008 mg/L, federal limit 0.06 mg/L (1.7 times the limit)
Oct 1, 2016 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.1073 mg/L, federal limit 0.06 mg/L (1.8 times the limit)
Jul 1, 2016 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.114 mg/L, federal limit 0.06 mg/L (1.9 times the limit)
Apr 1, 2016 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.0714 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
Jan 1, 2016 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.07 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
Oct 1, 2015 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.084 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
Oct 1, 2015 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.072 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
Jul 1, 2015 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.109 mg/L, federal limit 0.08 mg/L (1.4 times the limit)
Jul 1, 2015 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.136 mg/L, federal limit 0.08 mg/L (1.7 times the limit)
Apr 1, 2015 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.067 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
Apr 1, 2015 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.157 mg/L, federal limit 0.08 mg/L (2 times the limit)
Jan 1, 2015 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.128 mg/L, federal limit 0.08 mg/L (1.6 times the limit)
Oct 1, 2014 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.118 mg/L, federal limit 0.08 mg/L (1.5 times the limit)
Jul 1, 2014 Resolved
Surface Water Treatment Rule
Treatment technique failure
Dec 1, 2013 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.104 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
Oct 1, 2013 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.104 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
Jul 1, 2013 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.124 mg/L, federal limit 0.08 mg/L (1.6 times the limit)
Apr 1, 2013 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.122 mg/L, federal limit 0.08 mg/L (1.5 times the limit)
Jan 1, 2013 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.106 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
Oct 1, 2012 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.087 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
Jul 1, 2012 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.083 mg/L, federal limit 0.08 mg/L (at or just above the limit)
Apr 1, 2012 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.0913 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
Jul 1, 2011 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.119 mg/L, federal limit 0.08 mg/L (1.5 times the limit)
Apr 1, 2011 Resolved
Surface Water Treatment Rule
Treatment technique failure
Feb 1, 2011 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.131 mg/L, federal limit 0.08 mg/L (1.6 times the limit)
Jan 1, 2011 Resolved
Surface Water Treatment Rule
Treatment technique failure
Jan 1, 2011 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.131 mg/L, federal limit 0.08 mg/L (1.6 times the limit)
Oct 1, 2010 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.119 mg/L, federal limit 0.08 mg/L (1.5 times the limit)
Jul 1, 2010 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.126 mg/L, federal limit 0.08 mg/L (1.6 times the limit)
Apr 1, 2010 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.126 mg/L, federal limit 0.08 mg/L (1.6 times the limit)
Jan 1, 2010 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.128 mg/L, federal limit 0.08 mg/L (1.6 times the limit)
Oct 1, 2009 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.139 mg/L, federal limit 0.08 mg/L (1.7 times the limit)
Jul 1, 2009 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.107 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
Apr 1, 2009 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.102 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
Jan 1, 2009 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.103 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
Oct 1, 2008 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.0969 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
Jul 1, 2008 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.102 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
Apr 1, 2008 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.115 mg/L, federal limit 0.08 mg/L (1.4 times the limit)
Jan 1, 2008 Resolved

Enforcement actions

California regulators took 7 formal enforcement actions against Harris Farms South 101-144 between 2008 and 2015. The most recent was a compliance order (no penalty) in November 2015.

Date By Action Violations covered
Nov 10, 2015 California Compliance order (no penalty) 8 violations (8 health-based): Haloacetic Acids (HAA5)
Jun 22, 2015 California Compliance order (no penalty) 28 violations (27 health-based): Total Trihalomethanes (TTHMs), Miscellaneous Other Rules
Oct 8, 2014 California Compliance order (no penalty) 2 violations (2 health-based): Total Trihalomethanes (TTHMs)
May 5, 2014 California Compliance order (no penalty) 1 violation (1 health-based): Surface Water Treatment Rule
Mar 22, 2011 California Compliance order (no penalty) 1 violation (1 health-based): Surface Water Treatment Rule
Feb 25, 2011 California Compliance order (no penalty) 1 violation (1 health-based): Surface Water Treatment Rule
Apr 29, 2008 California Compliance order (no penalty) 22 violations (22 health-based): Total Trihalomethanes (TTHMs)

What the violations mean

Haloacetic Acids (HAA5)

2 incidents

Haloacetic acid byproducts exceeded the federal limit

Long-term exposure to HAAs may increase cancer risk

Where the water comes from

Harris Farms South 101-144 draws water from 1 surface water intake.

Annual water quality report

Harris Farms South 101-144 must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.

Systems serving 500 or fewer people may meet the rule by telling customers the report is available on request, so you may need to ask Harris Farms South 101-144 for a copy.

Find a posted report with EPA's Consumer Confidence Report search

Testing your own water

To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by California.