Public water system record

Gulkana Village

Serves Gulkana, Copper River Census Area, AK · 54 people served

Federal records show 18 health-based violations and 43 monitoring/reporting issues for Gulkana Village in the last ten years. The most serious issue in this window was a resolved Total Trihalomethanes (TTHMs) violation.

  • AK2380214
  • GULKANA
  • AK
  • 54 served

System profile

Source water Surface water
ZIP 99586
EPA system ID AK2380214

Verify this system on EPA ECHO →

Health-based violations, last 10 years
18
Resolved
18
Unresolved
0
Any acute record
No
Monitoring issues, last 10 years
43

Key facts

  • Gulkana Village draws water from 1 infiltration gallery.
  • Highest measured level in the last 10 years: Total Trihalomethanes (TTHMs), 0.165 mg/L, federal limit 0.08 mg/L (2.1 times the limit), 2020.
  • Most recent enforcement action: boil water order by Alaska, October 2024.
  • Record on file since 1985, with 109 health-based violations before October 19, 2016.
  • Lead pipe inventory: 0 lead and 0 unknown out of 36 service lines.

Check whether Gulkana Village serves your address

Address suggestions by Mapbox

Health-based violations

Since October 2016

Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.

Contaminant Rule family Start date Status Acute
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.081 mg/L, federal limit 0.08 mg/L (at or just above the limit)
220 Jul 1, 2024 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.096 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
220 Apr 1, 2024 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.107 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
220 Jan 1, 2024 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.09 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
220 Oct 1, 2023 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.1 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
220 Jul 1, 2023 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.09 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
220 Apr 1, 2023 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.09 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
220 Jan 1, 2023 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.097 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
220 Oct 1, 2022 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.087 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
220 Oct 1, 2021 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.128 mg/L, federal limit 0.08 mg/L (1.6 times the limit)
220 Jul 1, 2021 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.135 mg/L, federal limit 0.08 mg/L (1.7 times the limit)
220 Apr 1, 2021 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.138 mg/L, federal limit 0.08 mg/L (1.7 times the limit)
220 Jan 1, 2021 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.165 mg/L, federal limit 0.08 mg/L (2.1 times the limit)
220 Oct 1, 2020 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.082 mg/L, federal limit 0.08 mg/L (at or just above the limit)
220 Oct 1, 2018 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.082 mg/L, federal limit 0.08 mg/L (at or just above the limit)
220 Apr 1, 2018 Resolved No
Surface Water Treatment Rule
Treatment technique failure
120 Aug 1, 2017 Resolved No
Surface Water Treatment Rule
Treatment technique failure
120 Jun 1, 2017 Resolved No
Surface Water Treatment Rule
Treatment technique failure
120 May 1, 2017 Resolved No

Monitoring and reporting issues

Since October 2016

Missed tests or reports, not contaminants found above a limit.

Issue Start date Status
Surface Water Treatment Rule
Monitoring and reporting
Sep 1, 2025 Resolved
Surface Water Treatment Rule
Monitoring and reporting
Jun 1, 2025 Resolved
Revised Total Coliform Rule
Monitoring violation
Nov 1, 2024 Resolved
Chlorine
Monitoring and reporting
Nov 1, 2024 Resolved
Surface Water Treatment Rule
Monitoring and reporting
Nov 1, 2024 Resolved
Surface Water Treatment Rule
Monitoring and reporting
Jul 1, 2024 Resolved
Haloacetic Acids (HAA5)
Monitoring and reporting
Apr 1, 2024 Resolved
Total Trihalomethanes (TTHMs)
Monitoring and reporting
Apr 1, 2024 Resolved
Surface Water Treatment Rule
Monitoring and reporting
Sep 1, 2023 Resolved
Chlorine
Monitoring and reporting
Jul 1, 2023 Resolved
Revised Total Coliform Rule
Monitoring violation
Jul 1, 2023 Resolved
Public Notice
OTHER
May 20, 2023 Resolved
Surface Water Treatment Rule
Monitoring and reporting
May 1, 2023 Resolved
Revised Total Coliform Rule
Monitoring violation
May 1, 2023 Resolved
Chlorine
Monitoring and reporting
Apr 1, 2023 Resolved
Total Trihalomethanes (TTHMs)
Monitoring and reporting
Jan 9, 2023 Resolved
Total Trihalomethanes (TTHMs)
Monitoring and reporting
Oct 1, 2022 Resolved
Revised Total Coliform Rule
Monitoring violation
Oct 1, 2022 Resolved
Interim Enhanced Surface Water Treatment Rule
Monitoring and reporting
Aug 1, 2022 Resolved
Revised Total Coliform Rule
Monitoring violation
Aug 1, 2022 Resolved
Revised Total Coliform Rule
Monitoring violation
Jul 1, 2022 Resolved
Revised Total Coliform Rule
Monitoring violation
May 1, 2022 Resolved
Lead and Copper Rule
Monitoring and reporting
Jul 1, 2021 Resolved
Surface Water Treatment Rule
Monitoring and reporting
Nov 1, 2017 Resolved
Revised Total Coliform Rule
Monitoring violation
Nov 1, 2017 Resolved
Chlorine
Monitoring and reporting
Oct 1, 2017 Resolved
Surface Water Treatment Rule
Monitoring and reporting
Aug 1, 2017 Resolved
Surface Water Treatment Rule
Monitoring and reporting
Jul 1, 2017 Resolved
Chlorine
Monitoring and reporting
Jul 1, 2017 Resolved
Surface Water Treatment Rule
Monitoring and reporting
Jun 1, 2017 Resolved
Surface Water Treatment Rule
Monitoring and reporting
May 1, 2017 Resolved
Chlorine
Monitoring and reporting
Apr 1, 2017 Resolved
Surface Water Treatment Rule
Monitoring and reporting
Apr 1, 2017 Resolved
Interim Enhanced Surface Water Treatment Rule
Monitoring and reporting
Apr 1, 2017 Resolved
Surface Water Treatment Rule
Monitoring and reporting
Mar 1, 2017 Resolved
Surface Water Treatment Rule
Monitoring and reporting
Feb 1, 2017 Resolved
Revised Total Coliform Rule
Monitoring violation
Feb 1, 2017 Resolved
Chlorine
Monitoring and reporting
Jan 1, 2017 Resolved
Surface Water Treatment Rule
Monitoring and reporting
Jan 1, 2017 Resolved
Surface Water Treatment Rule
Monitoring and reporting
Dec 1, 2016 Resolved
Surface Water Treatment Rule
Monitoring and reporting
Nov 1, 2016 Resolved
Revised Total Coliform Rule
Monitoring violation
Nov 1, 2016 Resolved
Chlorine
Monitoring and reporting
Oct 1, 2016 Resolved

Full record since 1985

EPA's records for Gulkana Village go back to 1985. Before October 19, 2016 they list 109 health-based violations (80 resolved, 29 archived by EPA without a recorded fix) and 468 monitoring or reporting violations.

Violations that began in Health-based Monitoring and reporting
1980s 0 1
1990s 13 241
2000s 58 81
2010 to October 18, 2016 38 145
October 19, 2016 to 2019 5 19
2020s 13 23

Most recent health-based violation before October 19, 2016: Surface Water Treatment Rule, began June 2014, Resolved.

Show all 109 health-based violations before October 19, 2016
Contaminant Start date Status
Surface Water Treatment Rule
Treatment technique failure
Jun 1, 2014 Resolved
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
Apr 1, 2014 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.068 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
Jul 1, 2013 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.135 mg/L, federal limit 0.08 mg/L (1.7 times the limit)
Jul 1, 2013 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.121 mg/L, federal limit 0.06 mg/L (2 times the limit)
Apr 1, 2013 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.17 mg/L, federal limit 0.08 mg/L (2.1 times the limit)
Apr 1, 2013 Resolved
Surface Water Treatment Rule
Treatment technique failure
Feb 1, 2013 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.157 mg/L, federal limit 0.06 mg/L (2.6 times the limit)
Jan 1, 2013 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.199 mg/L, federal limit 0.08 mg/L (2.5 times the limit)
Jan 1, 2013 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.205 mg/L, federal limit 0.08 mg/L (2.6 times the limit)
Oct 1, 2012 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.183 mg/L, federal limit 0.06 mg/L (3.1 times the limit)
Oct 1, 2012 Resolved
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
Sep 1, 2012 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.204 mg/L, federal limit 0.08 mg/L (2.6 times the limit)
Jul 1, 2012 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.191 mg/L, federal limit 0.06 mg/L (3.2 times the limit)
Jul 1, 2012 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.136 mg/L, federal limit 0.06 mg/L (2.3 times the limit)
Apr 1, 2012 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.179 mg/L, federal limit 0.08 mg/L (2.2 times the limit)
Apr 1, 2012 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.117 mg/L, federal limit 0.06 mg/L (2 times the limit)
Jan 1, 2012 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.166 mg/L, federal limit 0.08 mg/L (2.1 times the limit)
Jan 1, 2012 Resolved
Surface Water Treatment Rule
Treatment technique failure
Dec 1, 2011 Resolved
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
Nov 1, 2011 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.103 mg/L, federal limit 0.06 mg/L (1.7 times the limit)
Oct 1, 2011 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.162 mg/L, federal limit 0.08 mg/L (2 times the limit)
Oct 1, 2011 Resolved
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
Sep 1, 2011 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.121 mg/L, federal limit 0.08 mg/L (1.5 times the limit)
Jul 1, 2011 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.062 mg/L, federal limit 0.06 mg/L (at or just above the limit)
Jul 1, 2011 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.135 mg/L, federal limit 0.08 mg/L (1.7 times the limit)
Apr 1, 2011 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.1 mg/L, federal limit 0.06 mg/L (1.7 times the limit)
Apr 1, 2011 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.156 mg/L, federal limit 0.08 mg/L (2 times the limit)
Jan 1, 2011 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.152 mg/L, federal limit 0.06 mg/L (2.5 times the limit)
Jan 1, 2011 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.155 mg/L, federal limit 0.08 mg/L (1.9 times the limit)
Oct 1, 2010 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.179 mg/L, federal limit 0.06 mg/L (3 times the limit)
Oct 1, 2010 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.156 mg/L, federal limit 0.08 mg/L (2 times the limit)
Jul 1, 2010 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.192 mg/L, federal limit 0.06 mg/L (3.2 times the limit)
Jul 1, 2010 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.148 mg/L, federal limit 0.08 mg/L (1.9 times the limit)
Apr 1, 2010 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.189 mg/L, federal limit 0.06 mg/L (3.2 times the limit)
Apr 1, 2010 Resolved
Surface Water Treatment Rule
Treatment technique failure
Apr 1, 2010 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.141 mg/L, federal limit 0.08 mg/L (1.8 times the limit)
Jan 1, 2010 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.168 mg/L, federal limit 0.06 mg/L (2.8 times the limit)
Jan 1, 2010 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.173 mg/L, federal limit 0.06 mg/L (2.9 times the limit)
Oct 1, 2009 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.151 mg/L, federal limit 0.08 mg/L (1.9 times the limit)
Oct 1, 2009 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.187 mg/L, federal limit 0.08 mg/L (2.3 times the limit)
Jul 1, 2009 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.287 mg/L, federal limit 0.06 mg/L (4.8 times the limit)
Jul 1, 2009 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.26 mg/L, federal limit 0.06 mg/L (4.3 times the limit)
Apr 1, 2009 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.178 mg/L, federal limit 0.08 mg/L (2.2 times the limit)
Apr 1, 2009 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.285 mg/L, federal limit 0.06 mg/L (4.8 times the limit)
Jan 1, 2009 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.178 mg/L, federal limit 0.08 mg/L (2.2 times the limit)
Jan 1, 2009 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.186 mg/L, federal limit 0.08 mg/L (2.3 times the limit)
Oct 1, 2008 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.266 mg/L, federal limit 0.06 mg/L (4.4 times the limit)
Oct 1, 2008 Resolved
Surface Water Treatment Rule
Treatment technique failure
Jun 1, 2008 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.208 mg/L, federal limit 0.08 mg/L (2.6 times the limit)
Apr 1, 2008 Resolved

59 older violations are not listed here. EPA ECHO has the complete list.

Enforcement actions

Alaska regulators took 1 formal enforcement action against Gulkana Village and issued 5 boil water orders between 1994 and 2024. The most recent was a boil water order in October 2024.

Date By Action Violations covered
Oct 10, 2024 Alaska Boil water order 1 violation
May 31, 2024 Alaska Boil water order 1 violation
Sep 25, 2018 Alaska Boil water order 1 violation
Dec 11, 2017 Alaska Boil water order 1 violation
Jun 26, 2017 Alaska Boil water order 1 violation
Sep 1, 1994 Alaska Signed compliance agreement 6 violations: Total Coliform

What the violations mean

Total Trihalomethanes (TTHMs)

15 incidents

Disinfection byproduct levels exceeded the federal limit

Long-term TTHM exposure may increase bladder cancer risk

Surface Water Treatment Rule

3 incidents

The system did not complete a treatment step or action that the Surface Water Treatment Rule requires (a treatment technique violation).

The utility had to notify customers about each of these violations.

Where the water comes from

Gulkana Village draws water from 1 infiltration gallery.

Annual water quality report

Gulkana Village must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.

Systems serving 500 or fewer people may meet the rule by telling customers the report is available on request, so you may need to ask Gulkana Village for a copy.

Find a posted report with EPA's Consumer Confidence Report search

Testing your own water

To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Alaska.