Public water system record
Brookside MHP
Serves an area of Addison County, VT · 135 people served
Federal records show no health-based violations and 1 monitoring/reporting issue for Brookside MHP in the last ten years. At least one of these issues remains unresolved.
System profile
- Health-based violations, last 10 years
- 0
- Resolved
- 0
- Unresolved
- 0
- Any acute record
- No
- Monitoring issues, last 10 years
- 1
Key facts
- Brookside MHP draws water from 1 well.
- Most recent enforcement action: boil water order by Vermont, June 2009.
- Record on file since 1993, with 12 health-based violations before October 19, 2016.
- Lead pipe inventory: 0 lead and 0 unknown out of 52 service lines.
Check whether Brookside MHP serves your address
Health-based violations
Since October 2016Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.
None since October 2016.
Monitoring and reporting issues
Since October 2016Missed tests or reports, not contaminants found above a limit.
| Issue | Start date | Status |
|---|---|---|
|
E. coli
Monitoring and reporting
|
Dec 24, 2015 | Active |
Full record since 1993
EPA's records for Brookside MHP go back to 1993. Before October 19, 2016 they list 12 health-based violations (12 resolved) and 109 monitoring or reporting violations.
| Violations that began in | Health-based | Monitoring and reporting |
|---|---|---|
| 1990s | 1 | 65 |
| 2000s | 3 | 9 |
| 2010 to October 18, 2016 | 8 | 35 |
Most recent health-based violation before October 19, 2016: Combined Radium (-226 and -228), began July 2011, Resolved.
Show all 12 health-based violations before October 19, 2016
| Contaminant | Start date | Status |
|---|---|---|
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 10.2 pCi/L, federal limit 5 pCi/L (2 times the limit)
|
Jul 1, 2011 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 10.4 pCi/L, federal limit 5 pCi/L (2.1 times the limit)
|
Apr 1, 2011 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 6.5 pCi/L, federal limit 5 pCi/L (1.3 times the limit)
|
Jan 1, 2011 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 6.5 pCi/L, federal limit 5 pCi/L (1.3 times the limit)
|
Oct 1, 2010 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 6.8 pCi/L, federal limit 5 pCi/L (1.4 times the limit)
|
Jul 1, 2010 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 6.2 pCi/L, federal limit 5 pCi/L (1.2 times the limit)
|
Apr 1, 2010 | Resolved |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 16.5 pCi/L, federal limit 15 pCi/L (1.1 times the limit)
|
Jan 1, 2010 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 6.7 pCi/L, federal limit 5 pCi/L (1.3 times the limit)
|
Jan 1, 2010 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 6.2 pCi/L, federal limit 5 pCi/L (1.2 times the limit)
|
Oct 1, 2009 | Resolved |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 18 pCi/L, federal limit 15 pCi/L (1.2 times the limit)
|
Oct 1, 2009 | Resolved |
|
Total Coliform
Contaminant limit exceeded
|
Jun 1, 2009 | Resolved |
|
Total Coliform
Contaminant limit exceeded
|
Oct 1, 1993 | Resolved |
Enforcement actions
Vermont regulators took 1 formal enforcement action against Brookside MHP and issued 2 boil water orders between 1993 and 2009, filed as 7 records in EPA's data. The most recent was a boil water order in June 2009.
| Date | By | Action | Violations covered |
|---|---|---|---|
| Jun 15, 2009 | Vermont | Boil water order | 1 violation (1 health-based): Total Coliform |
| Aug 23, 2000 | Vermont | Compliance order with a penalty | 57 violations: CYANIDE, Gross Alpha, Excl. Radon and U, 1,2,4-Trichlorobenzene, Xylenes, Total, Styrene |
| Nov 1, 1993 | Vermont | Boil water order | 1 violation (1 health-based): Total Coliform |
Where the water comes from
Brookside MHP draws water from 1 well.
Annual water quality report
Brookside MHP must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.
Systems serving 500 or fewer people may meet the rule by telling customers the report is available on request, so you may need to ask Brookside MHP for a copy.
Find a posted report with EPA's Consumer Confidence Report search
Testing your own water
To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Vermont.
Certified drinking water labs by state EPA guidance for private wells