Public water system record

Quantico Marine Base-Mainside

Serves Quantico Base, Prince William County, VA · 19,000 people served

Federal records show 14 health-based violations and 13 monitoring/reporting issues for Quantico Marine Base-Mainside in the last ten years. The most serious issue in this window was a Total Trihalomethanes (TTHMs) violation that EPA lists as archived, not resolved.

  • VA6153675
  • MCINCR, MCB QUANTICO
  • VA
  • 19,000 served

System profile

Source water Surface water
ZIP 22134
EPA system ID VA6153675

Verify this system on EPA ECHO →

Health-based violations, last 10 years
14
Resolved
11
Unresolved
0
Archived by EPA
3
Any acute record
No
Monitoring issues, last 10 years
13

Key facts

  • Quantico Marine Base-Mainside draws water from 2 surface water intakes (1 of them for emergency, seasonal or other part-time use).
  • Highest measured level in the last 10 years: Total Trihalomethanes (TTHMs), 0.11 mg/L, federal limit 0.08 mg/L (1.4 times the limit), 2017.
  • Most recent formal enforcement: compliance order (no penalty) by Virginia, May 2019.
  • Record on file since 1984, with 12 health-based violations before October 19, 2016.
  • Lead pipe inventory: 0 lead and 95 unknown out of 1,315 service lines.

Check whether Quantico Marine Base-Mainside serves your address

Address suggestions by Mapbox

Health-based violations

Since October 2016

Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.

Contaminant Rule family Start date Status Acute
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.092 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
220 Oct 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.093 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
220 Jul 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 88 µg/L, federal limit 80 µg/L (1.1 times the limit)
220 Apr 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.082 mg/L, federal limit 0.08 mg/L (at or just above the limit)
220 Apr 1, 2019 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.083 mg/L, federal limit 0.08 mg/L (at or just above the limit)
220 Jan 1, 2019 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.083 mg/L, federal limit 0.08 mg/L (at or just above the limit)
220 Oct 1, 2018 Resolved No
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.062 mg/L, federal limit 0.06 mg/L (at or just above the limit)
220 Oct 1, 2018 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.088 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
220 Jul 1, 2018 Resolved No
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.067 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
220 Jul 1, 2018 Resolved No
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.064 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
220 Apr 1, 2018 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.1 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
220 Jan 1, 2018 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.11 mg/L, federal limit 0.08 mg/L (1.4 times the limit)
220 Oct 1, 2017 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.098 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
220 Jul 1, 2017 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.086 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
220 Apr 1, 2017 Resolved No

Monitoring and reporting issues

Since October 2016

Missed tests or reports, not contaminants found above a limit.

Issue Start date Status
CARBON, TOTAL
Monitoring and reporting
Oct 1, 2019 Resolved
Selenium
Monitoring and reporting
Jan 1, 2019 Resolved
Thallium, Total
Monitoring and reporting
Jan 1, 2019 Resolved
Beryllium, Total
Monitoring and reporting
Jan 1, 2019 Resolved
Antimony, Total
Monitoring and reporting
Jan 1, 2019 Resolved
Nickel
Monitoring and reporting
Jan 1, 2019 Resolved
Mercury
Monitoring and reporting
Jan 1, 2019 Resolved
Chromium (total)
Monitoring and reporting
Jan 1, 2019 Resolved
Cadmium
Monitoring and reporting
Jan 1, 2019 Resolved
Barium
Monitoring and reporting
Jan 1, 2019 Resolved
Arsenic
Monitoring and reporting
Jan 1, 2019 Resolved
Lead and Copper Rule
Monitoring and reporting
Oct 1, 2018 Resolved
CARBON, TOTAL
Monitoring and reporting
Oct 1, 2017 Resolved

Full record since 1984

EPA's records for Quantico Marine Base-Mainside go back to 1984. Before October 19, 2016 they list 12 health-based violations (12 resolved) and 20 monitoring or reporting violations.

Violations that began in Health-based Monitoring and reporting
1980s 0 8
1990s 5 0
2000s 3 0
2010 to October 18, 2016 4 12
October 19, 2016 to 2019 11 13
2020s 3 0

Most recent health-based violation before October 19, 2016: Haloacetic Acids (HAA5), began October 2015, Resolved.

Show all 12 health-based violations before October 19, 2016
Contaminant Start date Status
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.067 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
Oct 1, 2015 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.062 mg/L, federal limit 0.06 mg/L (at or just above the limit)
Jul 1, 2015 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.065 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
Apr 1, 2015 Resolved
Total Coliform
Contaminant limit exceeded
Mar 1, 2015 Resolved
Total Coliform
Contaminant limit exceeded
Jun 1, 2004 Resolved
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
Feb 1, 2004 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Oct 1, 2003 Resolved
Total Coliform (acute)
Contaminant limit exceeded
Jun 1, 1999 Resolved
Total Coliform
Contaminant limit exceeded
May 1, 1999 Resolved
Total Coliform
Contaminant limit exceeded
Dec 1, 1998 Resolved
Total Coliform
Contaminant limit exceeded
Jul 1, 1996 Resolved
Total Coliform (acute)
Contaminant limit exceeded
Mar 1, 1996 Resolved

Enforcement actions

Virginia regulators took 1 formal enforcement action against Quantico Marine Base-Mainside and issued 1 boil water order between 2004 and 2019. The most recent was a compliance order (no penalty) in May 2019.

Date By Action Violations covered
May 15, 2019 Virginia Compliance order (no penalty) 11 violations (11 health-based): Total Trihalomethanes (TTHMs), Haloacetic Acids (HAA5)
Feb 17, 2004 Virginia Boil water order 1 violation (1 health-based): Interim Enhanced Surface Water Treatment Rule

What the violations mean

Total Trihalomethanes (TTHMs)

11 incidents

Disinfection byproduct levels exceeded the federal limit

Long-term TTHM exposure may increase bladder cancer risk

Haloacetic Acids (HAA5)

3 incidents

Haloacetic acid byproducts exceeded the federal limit

Long-term exposure to HAAs may increase cancer risk

Where the water comes from

Quantico Marine Base-Mainside draws water from 2 surface water intakes (1 of them for emergency, seasonal or other part-time use). 1 other community water system buys water from Quantico Marine Base-Mainside.

Community systems that buy water from it

Annual water quality report

Quantico Marine Base-Mainside must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.

Systems serving 10,000 or more people must mail or deliver the report to every customer, and from 2027 they must send it twice a year.

Find a posted report with EPA's Consumer Confidence Report search

Testing your own water

To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Virginia.