Public water system record
City of Raymondville
Serves Raymondville, Willacy County, TX · 11,288 people served
Federal records show no health-based violations and 4 monitoring/reporting issues for City of Raymondville in the last ten years. At least one of these issues remains unresolved.
System profile
- Health-based violations, last 10 years
- 0
- Resolved
- 0
- Unresolved
- 0
- Any acute record
- No
- Monitoring issues, last 10 years
- 4
Key facts
- City of Raymondville draws water from 1 well and 1 surface water intake.
- Most recent formal enforcement: compliance order with a penalty by Texas, August 2016.
- Record on file since 1992, with 16 health-based violations before October 19, 2016.
- Lead pipe inventory: 0 lead and 0 unknown out of 3,504 service lines.
Check whether City of Raymondville serves your address
Health-based violations
Since October 2016Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.
None since October 2016.
Monitoring and reporting issues
Since October 2016Missed tests or reports, not contaminants found above a limit.
| Issue | Start date | Status |
|---|---|---|
|
Consumer Confidence Rule
OTHER
|
Jul 1, 2025 | Active |
|
Public Notice
OTHER
|
Aug 17, 2023 | Resolved |
|
Lead and Copper Rule
Monitoring and reporting
|
Jan 1, 2022 | Resolved |
|
Chlorite
Monitoring and reporting
|
Jan 1, 2021 | Resolved |
Full record since 1992
EPA's records for City of Raymondville go back to 1992. Before October 19, 2016 they list 16 health-based violations (9 resolved, 7 archived by EPA without a recorded fix) and 3 monitoring or reporting violations.
| Violations that began in | Health-based | Monitoring and reporting |
|---|---|---|
| 1990s | 3 | 3 |
| 2000s | 10 | 0 |
| 2010 to October 18, 2016 | 3 | 0 |
| 2020s | 0 | 4 |
Most recent health-based violation before October 19, 2016: Total Trihalomethanes (TTHMs), began October 2015, Archived.
Show all 16 health-based violations before October 19, 2016
| Contaminant | Start date | Status |
|---|---|---|
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.091 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Oct 1, 2015 | Archived |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.11 mg/L, federal limit 0.08 mg/L (1.4 times the limit)
|
Jul 1, 2015 | Archived |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.117 mg/L, federal limit 0.08 mg/L (1.5 times the limit)
|
Apr 1, 2015 | Archived |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.088 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Apr 1, 2005 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.157 mg/L, federal limit 0.08 mg/L (2 times the limit)
|
Jan 1, 2005 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.079 mg/L, federal limit 0.06 mg/L (1.3 times the limit)
|
Jan 1, 2005 | Resolved |
|
Surface Water Treatment Rule
Treatment technique failure
|
Nov 1, 2004 | Archived |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.193 mg/L, federal limit 0.08 mg/L (2.4 times the limit)
|
Oct 1, 2004 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.101 mg/L, federal limit 0.06 mg/L (1.7 times the limit)
|
Oct 1, 2004 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.174 mg/L, federal limit 0.08 mg/L (2.2 times the limit)
|
Jul 1, 2004 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.083 mg/L, federal limit 0.06 mg/L (1.4 times the limit)
|
Jul 1, 2004 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.076 mg/L, federal limit 0.06 mg/L (1.3 times the limit)
|
Apr 1, 2004 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.145 mg/L, federal limit 0.08 mg/L (1.8 times the limit)
|
Apr 1, 2004 | Resolved |
|
Surface Water Treatment Rule
Treatment technique failure
|
Sep 1, 1993 | Archived |
|
Surface Water Treatment Rule
Treatment technique failure
|
Aug 1, 1993 | Archived |
|
Surface Water Treatment Rule
Treatment technique failure
|
Jul 1, 1993 | Archived |
Enforcement actions
Texas regulators took 2 formal enforcement actions against City of Raymondville between 2005 and 2016. The most recent was a compliance order with a penalty in August 2016.
| Date | By | Action | Violations covered |
|---|---|---|---|
| Aug 24, 2016 | Texas | Compliance order with a penalty | 2 violations (2 health-based): Total Trihalomethanes (TTHMs) |
| Aug 20, 2005 | Texas | Compliance order with a penalty | 9 violations (9 health-based): Haloacetic Acids (HAA5), Total Trihalomethanes (TTHMs) |
Where the water comes from
City of Raymondville draws water from 1 well and 1 surface water intake. 2 other public water systems have emergency connections to City of Raymondville.
Annual water quality report
City of Raymondville must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.
Systems serving 10,000 or more people must mail or deliver the report to every customer, and from 2027 they must send it twice a year.
Find a posted report with EPA's Consumer Confidence Report search
Testing your own water
To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Texas.
Certified drinking water labs by state EPA guidance for private wells