Public water system record

City of Center

Serves Center, Shelby County, TX · 5,450 people served

Federal records show no health-based violations and 1 monitoring/reporting issue for City of Center in the last ten years. At least one of these issues remains unresolved.

  • TX2100001
  • CENTER
  • TX
  • 5,450 served

System profile

Source water Surface water
ZIP 75935
EPA system ID TX2100001

Verify this system on EPA ECHO →

Health-based violations, last 10 years
0
Resolved
0
Unresolved
0
Any acute record
No
Monitoring issues, last 10 years
1

Key facts

  • City of Center draws water from 3 surface water intakes.
  • Most recent formal enforcement: compliance order with a penalty by Texas, August 2016.
  • Record on file since 1992, with 32 health-based violations before October 19, 2016.
  • Lead pipe inventory: 0 lead and 0 unknown out of 2,125 service lines.

Check whether City of Center serves your address

Address suggestions by Mapbox

Health-based violations

Since October 2016

Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.

None since October 2016.

Monitoring and reporting issues

Since October 2016

Missed tests or reports, not contaminants found above a limit.

Issue Start date Status
Consumer Confidence Rule
OTHER
Jul 1, 2025 Active

Full record since 1992

EPA's records for City of Center go back to 1992. Before October 19, 2016 they list 32 health-based violations (32 resolved) and 32 monitoring or reporting violations.

Violations that began in Health-based Monitoring and reporting
1990s 0 1
2000s 21 29
2010 to October 18, 2016 11 2
2020s 0 1

Most recent health-based violation before October 19, 2016: Haloacetic Acids (HAA5), began July 2016, Resolved.

Show all 32 health-based violations before October 19, 2016
Contaminant Start date Status
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.062 mg/L, federal limit 0.06 mg/L (at or just above the limit)
Jul 1, 2016 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.069 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
Apr 1, 2016 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.078 mg/L, federal limit 0.06 mg/L (1.3 times the limit)
Jan 1, 2016 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.105 mg/L, federal limit 0.06 mg/L (1.8 times the limit)
Jan 1, 2016 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.106 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
Jan 1, 2016 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.092 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
Oct 1, 2015 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.093 mg/L, federal limit 0.06 mg/L (1.6 times the limit)
Oct 1, 2015 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.083 mg/L, federal limit 0.08 mg/L (at or just above the limit)
Jul 1, 2015 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.079 mg/L, federal limit 0.06 mg/L (1.3 times the limit)
Jul 1, 2015 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.069 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
Apr 1, 2015 Resolved
Total Coliform
Contaminant limit exceeded
May 1, 2012 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.086 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
Jan 1, 2007 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.063 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
Jan 1, 2007 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.092 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
Oct 1, 2006 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.068 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
Oct 1, 2006 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.104 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
Jul 1, 2006 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.076 mg/L, federal limit 0.06 mg/L (1.3 times the limit)
Jul 1, 2006 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.14 mg/L, federal limit 0.08 mg/L (1.8 times the limit)
Apr 1, 2006 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.099 mg/L, federal limit 0.06 mg/L (1.7 times the limit)
Apr 1, 2006 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.161 mg/L, federal limit 0.08 mg/L (2 times the limit)
Jan 1, 2006 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.112 mg/L, federal limit 0.06 mg/L (1.9 times the limit)
Jan 1, 2006 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.126 mg/L, federal limit 0.06 mg/L (2.1 times the limit)
Oct 1, 2005 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.177 mg/L, federal limit 0.08 mg/L (2.2 times the limit)
Oct 1, 2005 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.131 mg/L, federal limit 0.06 mg/L (2.2 times the limit)
Jul 1, 2005 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.17 mg/L, federal limit 0.08 mg/L (2.1 times the limit)
Jul 1, 2005 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.108 mg/L, federal limit 0.06 mg/L (1.8 times the limit)
Apr 1, 2005 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.131 mg/L, federal limit 0.08 mg/L (1.6 times the limit)
Apr 1, 2005 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.091 mg/L, federal limit 0.06 mg/L (1.5 times the limit)
Jan 1, 2005 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.099 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
Jan 1, 2005 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.083 mg/L, federal limit 0.08 mg/L (at or just above the limit)
Oct 1, 2004 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.084 mg/L, federal limit 0.06 mg/L (1.4 times the limit)
Oct 1, 2004 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.061 mg/L, federal limit 0.06 mg/L (at or just above the limit)
Jul 1, 2004 Resolved

Enforcement actions

Texas regulators took 1 formal enforcement action against City of Center in 2016. The most recent was a compliance order with a penalty in August 2016.

Date By Action Violations covered
Aug 24, 2016 Texas Compliance order with a penalty 9 violations (9 health-based): Haloacetic Acids (HAA5), Total Trihalomethanes (TTHMs)

Where the water comes from

City of Center draws water from 3 surface water intakes. 1 other public water system has an emergency connection to City of Center.

Annual water quality report

City of Center must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.

Where the state allows it, systems serving fewer than 10,000 people may publish the report in a local newspaper or news site instead of mailing it, and must provide a copy on request.

Find a posted report with EPA's Consumer Confidence Report search

Testing your own water