Public water system record
G M WSC
Serves an area of Sabine County, TX that includes Milam · 11,220 people served
Federal records show 4 health-based violations and 9 monitoring/reporting issues for G M WSC in the last ten years. The most serious issue in this window was a resolved LEAD AND COPPER RULE REVISIONS violation.
System profile
- Health-based violations, last 10 years
- 4
- Resolved
- 4
- Unresolved
- 0
- Any acute record
- Yes
- Monitoring issues, last 10 years
- 9
Key facts
- G M WSC draws water from 3 wells and 1 surface water intake.
- Highest measured level in the last 10 years: Total Trihalomethanes (TTHMs), 0.084 mg/L, federal limit 0.08 mg/L (1.1 times the limit), 2021.
- Most recent formal enforcement: compliance order with a penalty by Texas, October 2016.
- Record on file since 1992, with 24 health-based violations before October 19, 2016.
- Lead pipe inventory: 0 lead and 0 unknown out of 3,685 service lines.
Check whether G M WSC serves your address
Health-based violations
Since October 2016Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.
| Contaminant | Rule family | Start date | Status | Acute |
|---|---|---|---|---|
|
LEAD AND COPPER RULE REVISIONS
Treatment technique failure
|
350 | Oct 17, 2024 | Resolved | No |
|
Revised Total Coliform Rule
Treatment technique failure
|
110 | Mar 9, 2024 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.084 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
220 | Oct 1, 2021 | Resolved | No |
|
Interim Enhanced Surface Water Treatment Rule
Treatment technique failure
|
120 | Jul 1, 2017 | Resolved | Yes |
Monitoring and reporting issues
Since October 2016Missed tests or reports, not contaminants found above a limit.
| Issue | Start date | Status |
|---|---|---|
|
Consumer Confidence Rule
OTHER
|
Jul 1, 2025 | Active |
|
LEAD AND COPPER RULE REVISIONS
RPT
|
Oct 17, 2024 | Resolved |
|
Public Notice
OTHER
|
Jan 15, 2022 | Resolved |
|
Public Notice
OTHER
|
Mar 11, 2021 | Active |
|
Lead and Copper Rule
Monitoring and reporting
|
Dec 30, 2020 | Resolved |
|
Lead and Copper Rule
Monitoring and reporting
|
Jul 1, 2019 | Resolved |
|
Lead and Copper Rule
Monitoring and reporting
|
Sep 29, 2017 | Resolved |
|
Public Notice
OTHER
|
Aug 31, 2017 | Resolved |
|
Public Notice
OTHER
|
Sep 1, 2016 | Resolved |
Full record since 1992
EPA's records for G M WSC go back to 1992. Before October 19, 2016 they list 24 health-based violations (24 resolved) and 8 monitoring or reporting violations.
| Violations that began in | Health-based | Monitoring and reporting |
|---|---|---|
| 1990s | 0 | 3 |
| 2000s | 13 | 1 |
| 2010 to October 18, 2016 | 11 | 4 |
| October 19, 2016 to 2019 | 1 | 3 |
| 2020s | 3 | 5 |
Most recent health-based violation before October 19, 2016: Interim Enhanced Surface Water Treatment Rule (acute), began September 2016, Resolved.
Show all 24 health-based violations before October 19, 2016
| Contaminant | Start date | Status |
|---|---|---|
|
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
|
Sep 1, 2016 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.065 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
|
Jan 1, 2016 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.081 mg/L, federal limit 0.08 mg/L (at or just above the limit)
|
Jan 1, 2016 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.09 mg/L, federal limit 0.06 mg/L (1.5 times the limit)
|
Jan 1, 2016 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.088 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Jan 1, 2016 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.096 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
Oct 1, 2015 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.092 mg/L, federal limit 0.06 mg/L (1.5 times the limit)
|
Oct 1, 2015 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.094 mg/L, federal limit 0.06 mg/L (1.6 times the limit)
|
Jul 1, 2015 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.099 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
Jul 1, 2015 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.07 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
|
Apr 1, 2015 | Resolved |
|
Total Coliform
Contaminant limit exceeded
|
May 1, 2012 | Resolved |
|
Total Coliform
Contaminant limit exceeded
|
Jan 1, 2008 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.086 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Oct 1, 2006 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.089 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Jul 1, 2006 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.087 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Apr 1, 2006 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.085 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Jul 1, 2005 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.071 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
|
Jul 1, 2005 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.097 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
Apr 1, 2005 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.078 mg/L, federal limit 0.06 mg/L (1.3 times the limit)
|
Apr 1, 2005 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.082 mg/L, federal limit 0.06 mg/L (1.4 times the limit)
|
Jan 1, 2005 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.111 mg/L, federal limit 0.08 mg/L (1.4 times the limit)
|
Jan 1, 2005 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.072 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
|
Oct 1, 2004 | Resolved |
|
Total Coliform
Contaminant limit exceeded
|
Aug 1, 2004 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.087 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Jul 1, 2004 | Resolved |
Enforcement actions
Texas regulators took 2 formal enforcement actions against G M WSC between 2005 and 2016. The most recent was a compliance order with a penalty in October 2016.
| Date | By | Action | Violations covered |
|---|---|---|---|
| Oct 11, 2016 | Texas | Compliance order with a penalty | 9 violations (9 health-based): Haloacetic Acids (HAA5), Total Trihalomethanes (TTHMs) |
| Aug 19, 2005 | Texas | Signed compliance agreement | 11 violations (11 health-based): Total Trihalomethanes (TTHMs), Haloacetic Acids (HAA5) |
What the violations mean
LEAD AND COPPER RULE REVISIONS
1 incidentThe system did not complete a treatment step or action that the LEAD AND COPPER RULE REVISIONS requires (a treatment technique violation).
The utility had to notify customers about this violation.
Revised Total Coliform Rule
1 incidentThe system did not meet a requirement of the Revised Total Coliform Rule
Coliform and E. coli rules protect against bacteria in the distribution system
Total Trihalomethanes (TTHMs)
1 incidentDisinfection byproduct levels exceeded the federal limit
Long-term TTHM exposure may increase bladder cancer risk
Interim Enhanced Surface Water Treatment Rule
1 incidentThe system did not meet a filtration or treatment requirement for surface water
Inadequate treatment of surface water can let pathogens such as Cryptosporidium and Giardia through
Where the water comes from
G M WSC draws water from 3 wells and 1 surface water intake. It also buys water from City of Hemphill. It also has an emergency connection to City of Pineland.
Buys water from
- City of Hemphill Hemphill, TX
Emergency or part-time connections to
- City of Pineland Pineland, TX
Annual water quality report
G M WSC must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.
Systems serving 10,000 or more people must mail or deliver the report to every customer, and from 2027 they must send it twice a year.
Find a posted report with EPA's Consumer Confidence Report search
Testing your own water
To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Texas.
Certified drinking water labs by state EPA guidance for private wells