Public water system record
Walnut Creek SUD
Serves an area of Parker County and Wise County, TX that includes Carter and Sanctuary · 30,364 people served
Federal records show 16 health-based violations and 6 monitoring/reporting issues for Walnut Creek SUD in the last ten years. The most serious issue in this window was a resolved LEAD AND COPPER RULE REVISIONS violation.
System profile
- Health-based violations, last 10 years
- 16
- Resolved
- 16
- Unresolved
- 0
- Any acute record
- No
- Monitoring issues, last 10 years
- 6
Key facts
- Walnut Creek SUD draws water from 1 surface water intake.
- Highest measured level in the last 10 years: Total Trihalomethanes (TTHMs), 0.148 mg/L, federal limit 0.08 mg/L (1.9 times the limit), 2016.
- Most recent formal enforcement: compliance order with a penalty by Texas, August 2021.
- Record on file since 1991, with 37 health-based violations before October 19, 2016.
- Lead pipe inventory: 0 lead and 0 unknown out of 11,907 service lines.
Check whether Walnut Creek SUD serves your address
Health-based violations
Since October 2016Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.
| Contaminant | Rule family | Start date | Status | Acute |
|---|---|---|---|---|
|
LEAD AND COPPER RULE REVISIONS
Treatment technique failure
|
350 | Oct 17, 2024 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.081 mg/L, federal limit 0.08 mg/L (at or just above the limit)
|
220 | Jul 1, 2020 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.084 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
220 | Apr 1, 2020 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.085 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
220 | Jan 1, 2020 | Resolved | No |
|
Chlorite
Contaminant limit exceeded
Measured 1.1 mg/L, federal limit 1 mg/L (1.1 times the limit)
|
210 | Sep 1, 2019 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.083 mg/L, federal limit 0.08 mg/L (at or just above the limit)
|
220 | Oct 1, 2017 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.082 mg/L, federal limit 0.08 mg/L (at or just above the limit)
|
220 | Oct 1, 2017 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.083 mg/L, federal limit 0.08 mg/L (at or just above the limit)
|
220 | Oct 1, 2017 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.062 mg/L, federal limit 0.06 mg/L (at or just above the limit)
|
220 | Jul 1, 2017 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.097 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
220 | Jul 1, 2017 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.122 mg/L, federal limit 0.08 mg/L (1.5 times the limit)
|
220 | Apr 1, 2017 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.088 mg/L, federal limit 0.06 mg/L (1.5 times the limit)
|
220 | Apr 1, 2017 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.1 mg/L, federal limit 0.06 mg/L (1.7 times the limit)
|
220 | Jan 1, 2017 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.14 mg/L, federal limit 0.08 mg/L (1.8 times the limit)
|
220 | Jan 1, 2017 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.109 mg/L, federal limit 0.06 mg/L (1.8 times the limit)
|
220 | Oct 1, 2016 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.148 mg/L, federal limit 0.08 mg/L (1.9 times the limit)
|
220 | Oct 1, 2016 | Resolved | No |
Monitoring and reporting issues
Since October 2016Missed tests or reports, not contaminants found above a limit.
| Issue | Start date | Status |
|---|---|---|
|
Public Notice
OTHER
|
May 1, 2025 | Active |
|
Lead and Copper Rule
Monitoring and reporting
|
Dec 30, 2024 | Active |
|
LEAD AND COPPER RULE REVISIONS
RPT
|
Oct 17, 2024 | Resolved |
|
Public Notice
OTHER
|
Feb 3, 2017 | Resolved |
|
Lead and Copper Rule
Monitoring and reporting
|
Dec 30, 2016 | Resolved |
|
Lead and Copper Rule
Monitoring and reporting
|
Oct 1, 2016 | Resolved |
Full record since 1991
EPA's records for Walnut Creek SUD go back to 1991. Before October 19, 2016 they list 37 health-based violations (26 resolved, 11 archived by EPA without a recorded fix) and 6 monitoring or reporting violations.
| Violations that began in | Health-based | Monitoring and reporting |
|---|---|---|
| 1990s | 2 | 2 |
| 2000s | 7 | 0 |
| 2010 to October 18, 2016 | 28 | 4 |
| October 19, 2016 to 2019 | 10 | 2 |
| 2020s | 4 | 3 |
Most recent health-based violation before October 19, 2016: Haloacetic Acids (HAA5), began October 2016, Resolved.
Show all 37 health-based violations before October 19, 2016
| Contaminant | Start date | Status |
|---|---|---|
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.109 mg/L, federal limit 0.06 mg/L (1.8 times the limit)
|
Oct 1, 2016 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.148 mg/L, federal limit 0.08 mg/L (1.9 times the limit)
|
Oct 1, 2016 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.119 mg/L, federal limit 0.06 mg/L (2 times the limit)
|
Jul 1, 2016 | Archived |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.153 mg/L, federal limit 0.08 mg/L (1.9 times the limit)
|
Jul 1, 2016 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.154 mg/L, federal limit 0.08 mg/L (1.9 times the limit)
|
Apr 1, 2016 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.121 mg/L, federal limit 0.06 mg/L (2 times the limit)
|
Apr 1, 2016 | Archived |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.116 mg/L, federal limit 0.08 mg/L (1.5 times the limit)
|
Jan 1, 2016 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.126 mg/L, federal limit 0.08 mg/L (1.6 times the limit)
|
Jan 1, 2016 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.103 mg/L, federal limit 0.06 mg/L (1.7 times the limit)
|
Jan 1, 2016 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.105 mg/L, federal limit 0.06 mg/L (1.8 times the limit)
|
Jan 1, 2016 | Archived |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.113 mg/L, federal limit 0.06 mg/L (1.9 times the limit)
|
Jan 1, 2016 | Archived |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.132 mg/L, federal limit 0.08 mg/L (1.7 times the limit)
|
Jan 1, 2016 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.138 mg/L, federal limit 0.08 mg/L (1.7 times the limit)
|
Jan 1, 2016 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.115 mg/L, federal limit 0.06 mg/L (1.9 times the limit)
|
Jan 1, 2016 | Archived |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.092 mg/L, federal limit 0.06 mg/L (1.5 times the limit)
|
Oct 1, 2015 | Archived |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.092 mg/L, federal limit 0.06 mg/L (1.5 times the limit)
|
Oct 1, 2015 | Archived |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.094 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
Oct 1, 2015 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.114 mg/L, federal limit 0.08 mg/L (1.4 times the limit)
|
Oct 1, 2015 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.119 mg/L, federal limit 0.08 mg/L (1.5 times the limit)
|
Oct 1, 2015 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.119 mg/L, federal limit 0.08 mg/L (1.5 times the limit)
|
Oct 1, 2015 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.083 mg/L, federal limit 0.06 mg/L (1.4 times the limit)
|
Oct 1, 2015 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.085 mg/L, federal limit 0.06 mg/L (1.4 times the limit)
|
Oct 1, 2015 | Archived |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.101 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
|
Jul 1, 2015 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.068 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
|
Jul 1, 2015 | Archived |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.082 mg/L, federal limit 0.08 mg/L (at or just above the limit)
|
Apr 1, 2011 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.091 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Jan 1, 2011 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.089 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Oct 1, 2010 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.095 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
Jul 1, 2010 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.081 mg/L, federal limit 0.08 mg/L (at or just above the limit)
|
Jul 1, 2008 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.083 mg/L, federal limit 0.08 mg/L (at or just above the limit)
|
Apr 1, 2008 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.085 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Jan 1, 2008 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.089 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Jan 1, 2003 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.105 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
|
Oct 1, 2002 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.13 mg/L, federal limit 0.08 mg/L (1.6 times the limit)
|
Jul 1, 2002 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.11 mg/L, federal limit 0.08 mg/L (1.4 times the limit)
|
Apr 1, 2002 | Resolved |
|
Total Coliform
Contaminant limit exceeded
|
Feb 1, 1992 | Archived |
|
Total Coliform
Contaminant limit exceeded
|
Jun 1, 1991 | Archived |
Enforcement actions
Texas regulators took 3 formal enforcement actions against Walnut Creek SUD between 2006 and 2021. The most recent was a compliance order with a penalty in August 2021.
| Date | By | Action | Violations covered |
|---|---|---|---|
| Aug 19, 2021 | Texas | Compliance order with a penalty | 3 violations (3 health-based): Total Trihalomethanes (TTHMs) |
| Dec 9, 2016 | Texas | Compliance order with a penalty | 30 violations (30 health-based): Haloacetic Acids (HAA5), Total Trihalomethanes (TTHMs) |
| Mar 23, 2006 | Texas | Compliance order with a penalty | 3 violations (3 health-based): Total Trihalomethanes (TTHMs) |
What the violations mean
Total Trihalomethanes (TTHMs)
10 incidentsDisinfection byproduct levels exceeded the federal limit
Long-term TTHM exposure may increase bladder cancer risk
Haloacetic Acids (HAA5)
4 incidentsHaloacetic acid byproducts exceeded the federal limit
Long-term exposure to HAAs may increase cancer risk
LEAD AND COPPER RULE REVISIONS
1 incidentThe system did not complete a treatment step or action that the LEAD AND COPPER RULE REVISIONS requires (a treatment technique violation).
The utility had to notify customers about this violation.
Chlorite
1 incidentTest results for Chlorite were above the federal limit (a maximum contaminant level violation).
The utility had to notify customers about this violation.
Where the water comes from
Walnut Creek SUD draws water from 1 surface water intake. It also has an emergency connection to City of Springtown. 5 other community water systems buy water from Walnut Creek SUD. 4 other public water systems have emergency connections to Walnut Creek SUD.
Emergency or part-time connections to
- City of Springtown Springtown, TX
Community systems that buy water from it
- City of Boyd Boyd, TX
- City of Paradise Paradise, TX
- City of Reno Azle, TX
- City of Rhome Rhome, TX
- West Wise SUD Bridgeport, TX
Annual water quality report
Walnut Creek SUD must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.
Systems serving 10,000 or more people must mail or deliver the report to every customer, and from 2027 they must send it twice a year.
Find a posted report with EPA's Consumer Confidence Report search
Testing your own water