Public water system record
City of Midland Water Purification Plant
Serves Midland, Midland County, TX · 157,000 people served
Federal records show 4 health-based violations and 1 monitoring/reporting issue for City of Midland Water Purification Plant in the last ten years. The most serious issue in this window was a resolved Interim Enhanced Surface Water Treatment Rule violation.
System profile
- Health-based violations, last 10 years
- 4
- Resolved
- 4
- Unresolved
- 0
- Any acute record
- Yes
- Monitoring issues, last 10 years
- 1
Key facts
- City of Midland Water Purification Plant draws water from 98 wells and 4 surface water intakes.
- Highest measured level in the last 10 years: Arsenic, 0.012 mg/L, federal limit 0.01 mg/L (1.2 times the limit), 2017.
- Most recent enforcement action: boil water order by Texas, January 2023.
- Record on file since 1991, with 72 health-based violations before October 20, 2016.
- Lead pipe inventory: 0 lead and 0 unknown out of 51,375 service lines.
Check whether City of Midland Water Purification Plant serves your address
Health-based violations
Since October 2016Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.
| Contaminant | Rule family | Start date | Status | Acute |
|---|---|---|---|---|
|
Interim Enhanced Surface Water Treatment Rule
Treatment technique failure
|
120 | Nov 1, 2024 | Resolved | Yes |
|
Arsenic
Contaminant limit exceeded
Measured 0.011 mg/L, federal limit 0.01 mg/L (1.1 times the limit)
|
330 | Oct 1, 2023 | Resolved | No |
|
Interim Enhanced Surface Water Treatment Rule
Treatment technique failure
|
120 | Jan 1, 2023 | Resolved | Yes |
|
Arsenic
Contaminant limit exceeded
Measured 0.012 mg/L, federal limit 0.01 mg/L (1.2 times the limit)
|
330 | Jan 1, 2017 | Resolved | No |
Monitoring and reporting issues
Since October 2016Missed tests or reports, not contaminants found above a limit.
| Issue | Start date | Status |
|---|---|---|
|
Public Notice
OTHER
|
Jul 7, 2017 | Resolved |
Full record since 1991
EPA's records for City of Midland Water Purification Plant go back to 1991. Before October 20, 2016 they list 72 health-based violations (72 resolved) and 13 monitoring or reporting violations.
| Violations that began in | Health-based | Monitoring and reporting |
|---|---|---|
| 1990s | 0 | 3 |
| 2000s | 9 | 0 |
| 2010 to October 19, 2016 | 63 | 10 |
| October 20, 2016 to 2019 | 1 | 1 |
| 2020s | 3 | 0 |
Most recent health-based violation before October 20, 2016: Interim Enhanced Surface Water Treatment Rule (acute), began July 2016, Resolved.
Show all 72 health-based violations before October 20, 2016
| Contaminant | Start date | Status |
|---|---|---|
|
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
|
Jul 1, 2016 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.085 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Apr 1, 2015 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.098 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
Jan 1, 2015 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.108 mg/L, federal limit 0.08 mg/L (1.4 times the limit)
|
Oct 1, 2014 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.116 mg/L, federal limit 0.08 mg/L (1.5 times the limit)
|
Jul 1, 2014 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.1 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
|
Apr 1, 2014 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.102 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
|
Apr 1, 2014 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.104 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
|
Apr 1, 2014 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.097 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
Apr 1, 2014 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.084 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Apr 1, 2014 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.096 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
Apr 1, 2014 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.102 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
|
Apr 1, 2014 | Resolved |
|
Fluoride
Contaminant limit exceeded
Measured 4.4 mg/L, federal limit 4 mg/L (1.1 times the limit)
|
Jan 1, 2014 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.087 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Jan 1, 2014 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.091 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Jan 1, 2014 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.093 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
Jan 1, 2014 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.023 mg/L, federal limit 0.01 mg/L (2.3 times the limit)
|
Jan 1, 2014 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.091 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Jan 1, 2014 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.094 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
Jan 1, 2014 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.088 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Jan 1, 2014 | Resolved |
|
Fluoride
Contaminant limit exceeded
Measured 4.4 mg/L, federal limit 4 mg/L (1.1 times the limit)
|
Oct 1, 2013 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.025 mg/L, federal limit 0.01 mg/L (2.5 times the limit)
|
Oct 1, 2013 | Resolved |
|
Selenium
Contaminant limit exceeded
Measured 0.06 mg/L, federal limit 0.05 mg/L (1.2 times the limit)
|
Oct 1, 2013 | Resolved |
|
Surface Water Treatment Rule
Treatment technique failure
|
Aug 1, 2013 | Resolved |
|
Fluoride
Contaminant limit exceeded
Measured 4.3 mg/L, federal limit 4 mg/L (1.1 times the limit)
|
Jul 1, 2013 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.025 mg/L, federal limit 0.01 mg/L (2.5 times the limit)
|
Jul 1, 2013 | Resolved |
|
Selenium
Contaminant limit exceeded
Measured 0.06 mg/L, federal limit 0.05 mg/L (1.2 times the limit)
|
Jul 1, 2013 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.135 mg/L, federal limit 0.08 mg/L (1.7 times the limit)
|
Apr 1, 2013 | Resolved |
|
Fluoride
Contaminant limit exceeded
Measured 4.3 mg/L, federal limit 4 mg/L (1.1 times the limit)
|
Apr 1, 2013 | Resolved |
|
Selenium
Contaminant limit exceeded
Measured 0.07 mg/L, federal limit 0.05 mg/L (1.4 times the limit)
|
Apr 1, 2013 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.027 mg/L, federal limit 0.01 mg/L (2.7 times the limit)
|
Apr 1, 2013 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.133 mg/L, federal limit 0.08 mg/L (1.7 times the limit)
|
Jan 1, 2013 | Resolved |
|
Selenium
Contaminant limit exceeded
Measured 0.07 mg/L, federal limit 0.05 mg/L (1.4 times the limit)
|
Jan 1, 2013 | Resolved |
|
Fluoride
Contaminant limit exceeded
Measured 4.3 mg/L, federal limit 4 mg/L (1.1 times the limit)
|
Jan 1, 2013 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.027 mg/L, federal limit 0.01 mg/L (2.7 times the limit)
|
Jan 1, 2013 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.121 mg/L, federal limit 0.08 mg/L (1.5 times the limit)
|
Oct 1, 2012 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.031 mg/L, federal limit 0.01 mg/L (3.1 times the limit)
|
Oct 1, 2012 | Resolved |
|
Selenium
Contaminant limit exceeded
Measured 0.09 mg/L, federal limit 0.05 mg/L (1.8 times the limit)
|
Oct 1, 2012 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.011 mg/L, federal limit 0.01 mg/L (1.1 times the limit)
|
Oct 1, 2012 | Resolved |
|
Fluoride
Contaminant limit exceeded
Measured 4.4 mg/L, federal limit 4 mg/L (1.1 times the limit)
|
Oct 1, 2012 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.109 mg/L, federal limit 0.08 mg/L (1.4 times the limit)
|
Jul 1, 2012 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.012 mg/L, federal limit 0.01 mg/L (1.2 times the limit)
|
Jul 1, 2012 | Resolved |
|
Selenium
Contaminant limit exceeded
Measured 0.1 mg/L, federal limit 0.05 mg/L (2 times the limit)
|
Jul 1, 2012 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.034 mg/L, federal limit 0.01 mg/L (3.4 times the limit)
|
Jul 1, 2012 | Resolved |
|
Fluoride
Contaminant limit exceeded
Measured 4.4 mg/L, federal limit 4 mg/L (1.1 times the limit)
|
Jul 1, 2012 | Resolved |
|
Selenium
Contaminant limit exceeded
Measured 0.09 mg/L, federal limit 0.05 mg/L (1.8 times the limit)
|
Apr 1, 2012 | Resolved |
|
Fluoride
Contaminant limit exceeded
Measured 4.5 mg/L, federal limit 4 mg/L (1.1 times the limit)
|
Apr 1, 2012 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.041 mg/L, federal limit 0.01 mg/L (4.1 times the limit)
|
Apr 1, 2012 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.082 mg/L, federal limit 0.08 mg/L (at or just above the limit)
|
Jan 1, 2012 | Resolved |
|
Selenium
Contaminant limit exceeded
Measured 0.09 mg/L, federal limit 0.05 mg/L (1.8 times the limit)
|
Jan 1, 2012 | Resolved |
22 older violations are not listed here. EPA ECHO has the complete list.
Enforcement actions
Texas regulators and EPA took 4 formal enforcement actions against City of Midland Water Purification Plant and issued 1 boil water order between 2009 and 2023. The most recent was a boil water order in January 2023.
| Date | By | Action | Violations covered |
|---|---|---|---|
| Jan 5, 2023 | Texas | Boil water order | 1 violation (1 health-based): Interim Enhanced Surface Water Treatment Rule |
| Mar 15, 2015 | Texas | Compliance order with a penalty | 16 violations (16 health-based): Total Trihalomethanes (TTHMs) |
| Apr 2, 2013 | EPA | Compliance order (no penalty) | 9 violations (9 health-based): Selenium |
| Mar 29, 2013 | EPA | Compliance order (no penalty) | 39 violations (39 health-based): Fluoride, Arsenic |
| Dec 18, 2009 | Texas | Signed compliance agreement | 7 violations (7 health-based): Fluoride |
What the violations mean
Interim Enhanced Surface Water Treatment Rule
2 incidentsThe system did not meet a filtration or treatment requirement for surface water
Inadequate treatment of surface water can let pathogens such as Cryptosporidium and Giardia through
Arsenic
2 incidentsArsenic exceeded the federal limit
Long-term arsenic exposure is linked to cancer and cardiovascular effects
Where the water comes from
City of Midland Water Purification Plant draws water from 98 wells and 4 surface water intakes. It also buys water from System TX1140038, Colorado River Municipal Water District and Midland County FWSD 1.
Buys water from
- System TX1140038
- Colorado River Municipal Water District Big Spring, TX
- Midland County FWSD 1 Midland, TX
Annual water quality report
City of Midland Water Purification Plant must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.
Systems serving 10,000 or more people must mail or deliver the report to every customer, and from 2027 they must send it twice a year.
Find a posted report with EPA's Consumer Confidence Report search
Testing your own water
To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Texas.
Certified drinking water labs by state EPA guidance for private wells