Public water system record
East Cedar Creek FWSD Brookshire
Serves Gun Barrel City, Henderson County, TX · 14,823 people served
Federal records show 5 health-based violations and 10 monitoring/reporting issues for East Cedar Creek FWSD Brookshire in the last ten years. The most serious issue in this window was a resolved Haloacetic Acids (HAA5) violation.
System profile
- Health-based violations, last 10 years
- 5
- Resolved
- 5
- Unresolved
- 0
- Any acute record
- Yes
- Monitoring issues, last 10 years
- 10
Key facts
- East Cedar Creek FWSD Brookshire draws water from 1 surface water intake.
- Highest measured level in the last 10 years: Total Trihalomethanes (TTHMs), 0.082 mg/L, federal limit 0.08 mg/L (at or just above the limit), 2025.
- Most recent formal enforcement: compliance order with a penalty by Texas, March 2006.
- Record on file since 1991, with 25 health-based violations before October 19, 2016.
- Lead pipe inventory: 0 lead and 0 unknown out of 131 service lines.
Check whether East Cedar Creek FWSD Brookshire serves your address
Health-based violations
Since October 2016Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.
| Contaminant | Rule family | Start date | Status | Acute |
|---|---|---|---|---|
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.061 mg/L, federal limit 0.06 mg/L (at or just above the limit)
|
220 | Apr 1, 2025 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.082 mg/L, federal limit 0.08 mg/L (at or just above the limit)
|
220 | Apr 1, 2025 | Resolved | No |
|
Interim Enhanced Surface Water Treatment Rule
Treatment technique failure
|
120 | Jan 1, 2024 | Resolved | Yes |
|
Interim Enhanced Surface Water Treatment Rule
Treatment technique failure
|
120 | Feb 1, 2021 | Resolved | Yes |
|
Interim Enhanced Surface Water Treatment Rule
Treatment technique failure
|
120 | Feb 1, 2021 | Resolved | Yes |
Monitoring and reporting issues
Since October 2016Missed tests or reports, not contaminants found above a limit.
| Issue | Start date | Status |
|---|---|---|
|
Consumer Confidence Rule
OTHER
|
Jul 1, 2025 | Active |
|
Public Notice
OTHER
|
Feb 4, 2024 | Resolved |
|
Lead and Copper Rule
Monitoring and reporting
|
Oct 1, 2022 | Resolved |
|
Public Notice
OTHER
|
Mar 31, 2021 | Resolved |
|
Public Notice
OTHER
|
Mar 20, 2021 | Resolved |
|
Public Notice
OTHER
|
Mar 19, 2021 | Resolved |
|
Public Notice
OTHER
|
Mar 19, 2021 | Resolved |
|
Interim Enhanced Surface Water Treatment Rule
Monitoring and reporting
|
Feb 1, 2021 | Resolved |
|
Interim Enhanced Surface Water Treatment Rule
Monitoring and reporting
|
Feb 1, 2021 | Resolved |
|
Lead and Copper Rule
Monitoring and reporting
|
Dec 30, 2019 | Resolved |
Full record since 1991
EPA's records for East Cedar Creek FWSD Brookshire go back to 1991. Before October 19, 2016 they list 25 health-based violations (25 resolved) and 3 monitoring or reporting violations.
| Violations that began in | Health-based | Monitoring and reporting |
|---|---|---|
| 1990s | 0 | 2 |
| 2000s | 22 | 1 |
| 2010 to October 18, 2016 | 3 | 0 |
| October 19, 2016 to 2019 | 0 | 1 |
| 2020s | 5 | 9 |
Most recent health-based violation before October 19, 2016: Interim Enhanced Surface Water Treatment Rule (acute), began December 2010, Resolved.
Show all 25 health-based violations before October 19, 2016
| Contaminant | Start date | Status |
|---|---|---|
|
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
|
Dec 1, 2010 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.069 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
|
Apr 1, 2010 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.071 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
|
Jan 1, 2010 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.071 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
|
Oct 1, 2009 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.066 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
|
Jul 1, 2009 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.062 mg/L, federal limit 0.06 mg/L (at or just above the limit)
|
Apr 1, 2009 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.064 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
|
Jan 1, 2009 | Resolved |
|
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
|
Dec 1, 2008 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.066 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
|
Oct 1, 2008 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.09 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Jul 1, 2008 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.071 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
|
Jul 1, 2008 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.101 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
|
Apr 1, 2008 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.072 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
|
Apr 1, 2008 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.11 mg/L, federal limit 0.08 mg/L (1.4 times the limit)
|
Jan 1, 2008 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.071 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
|
Jan 1, 2008 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.106 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
|
Oct 1, 2007 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.065 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
|
Oct 1, 2007 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.1 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
|
Jul 1, 2007 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.096 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
Apr 1, 2007 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.088 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Jan 1, 2007 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.085 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Oct 1, 2006 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.085 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Jan 1, 2005 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.063 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
|
Oct 1, 2004 | Resolved |
|
Surface Water Treatment Rule
Treatment technique failure
|
Aug 1, 2004 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.082 mg/L, federal limit 0.08 mg/L (at or just above the limit)
|
Jul 1, 2004 | Resolved |
Enforcement actions
Texas regulators took 1 formal enforcement action against East Cedar Creek FWSD Brookshire in 2006. The most recent was a compliance order with a penalty in March 2006.
| Date | By | Action | Violations covered |
|---|---|---|---|
| Mar 6, 2006 | Texas | Compliance order with a penalty | 18 violations (18 health-based): Haloacetic Acids (HAA5), Total Trihalomethanes (TTHMs) |
What the violations mean
Interim Enhanced Surface Water Treatment Rule
3 incidentsThe system did not meet a filtration or treatment requirement for surface water
Inadequate treatment of surface water can let pathogens such as Cryptosporidium and Giardia through
Haloacetic Acids (HAA5)
1 incidentHaloacetic acid byproducts exceeded the federal limit
Long-term exposure to HAAs may increase cancer risk
Total Trihalomethanes (TTHMs)
1 incidentDisinfection byproduct levels exceeded the federal limit
Long-term TTHM exposure may increase bladder cancer risk
Where the water comes from
East Cedar Creek FWSD Brookshire draws water from 1 surface water intake.
Annual water quality report
East Cedar Creek FWSD Brookshire must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.
Systems serving 10,000 or more people must mail or deliver the report to every customer, and from 2027 they must send it twice a year.
Find a posted report with EPA's Consumer Confidence Report search
Testing your own water
To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Texas.
Certified drinking water labs by state EPA guidance for private wells