Public water system record

City of Flatonia

Serves an area of Fayette County, TX that includes Flatonia · 1,969 people served

Federal records show 8 health-based violations and 8 monitoring/reporting issues for City of Flatonia in the last ten years, including an unresolved LEAD AND COPPER RULE REVISIONS violation.

  • TX0750002
  • FLATONIA
  • TX
  • 1,969 served

System profile

Source water Groundwater
ZIP 78941
EPA system ID TX0750002

Verify this system on EPA ECHO →

Health-based violations, last 10 years
8
Resolved
7
Unresolved
1
Any acute record
No
Monitoring issues, last 10 years
8

Key facts

  • City of Flatonia draws water from 3 wells.
  • Highest measured level in the last 10 years: Arsenic, 0.012 mg/L, federal limit 0.01 mg/L (1.2 times the limit), 2018.
  • Most recent formal enforcement: compliance order (no penalty) by EPA, December 2017.
  • Record on file since 2006, with 26 health-based violations before October 19, 2016.

Check whether City of Flatonia serves your address

Address suggestions by Mapbox

Health-based violations

Since October 2016

Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.

Contaminant Rule family Start date Status Acute
LEAD AND COPPER RULE REVISIONS
Treatment technique failure
350 Oct 17, 2024 Active No
Arsenic
Contaminant limit exceeded
Measured 0.011 mg/L, federal limit 0.01 mg/L (1.1 times the limit)
330 Jul 1, 2018 Resolved No
Arsenic
Contaminant limit exceeded
Measured 0.012 mg/L, federal limit 0.01 mg/L (1.2 times the limit)
330 Apr 1, 2018 Resolved No
Arsenic
Contaminant limit exceeded
Measured 0.012 mg/L, federal limit 0.01 mg/L (1.2 times the limit)
330 Jan 1, 2018 Resolved No
Arsenic
Contaminant limit exceeded
Measured 0.012 mg/L, federal limit 0.01 mg/L (1.2 times the limit)
330 Oct 1, 2017 Resolved No
Arsenic
Contaminant limit exceeded
Measured 0.012 mg/L, federal limit 0.01 mg/L (1.2 times the limit)
330 Jul 1, 2017 Resolved No
Arsenic
Contaminant limit exceeded
Measured 0.011 mg/L, federal limit 0.01 mg/L (1.1 times the limit)
330 Apr 1, 2017 Resolved No
Arsenic
Contaminant limit exceeded
Measured 0.011 mg/L, federal limit 0.01 mg/L (1.1 times the limit)
330 Jan 1, 2017 Resolved No

Monitoring and reporting issues

Since October 2016

Missed tests or reports, not contaminants found above a limit.

Issue Start date Status
Chlorine
Monitoring and reporting
Jul 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
Consumer Confidence Rule
OTHER
Jul 1, 2025 Active
Public Notice
OTHER
Jun 30, 2025 Active
LEAD AND COPPER RULE REVISIONS
RPT
Oct 17, 2024 Active
Public Notice
OTHER
Sep 1, 2023 Resolved
Revised Total Coliform Rule
Monitoring violation
Aug 1, 2022 Resolved
Public Notice
OTHER
May 19, 2017 Resolved
Lead and Copper Rule
Monitoring and reporting
Dec 30, 2016 Resolved

Full record since 2006

EPA's records for City of Flatonia go back to 2006. Before October 19, 2016 they list 26 health-based violations (26 resolved) and 8 monitoring or reporting violations.

Violations that began in Health-based Monitoring and reporting
2000s 15 0
2010 to October 18, 2016 11 8
October 19, 2016 to 2019 7 2
2020s 1 6

Most recent health-based violation before October 19, 2016: Arsenic, began July 2012, Resolved.

Show all 26 health-based violations before October 19, 2016
Contaminant Start date Status
Arsenic
Contaminant limit exceeded
Measured 0.014 mg/L, federal limit 0.01 mg/L (1.4 times the limit)
Jul 1, 2012 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.02 mg/L, federal limit 0.01 mg/L (2 times the limit)
Apr 1, 2012 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.022 mg/L, federal limit 0.01 mg/L (2.2 times the limit)
Jan 1, 2012 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.026 mg/L, federal limit 0.01 mg/L (2.6 times the limit)
Oct 1, 2011 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.025 mg/L, federal limit 0.01 mg/L (2.5 times the limit)
Jul 1, 2011 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.025 mg/L, federal limit 0.01 mg/L (2.5 times the limit)
Apr 1, 2011 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.027 mg/L, federal limit 0.01 mg/L (2.7 times the limit)
Jan 1, 2011 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.027025 mg/L, federal limit 0.01 mg/L (2.7 times the limit)
Oct 1, 2010 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.027125 mg/L, federal limit 0.01 mg/L (2.7 times the limit)
Jul 1, 2010 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.0238 mg/L, federal limit 0.01 mg/L (2.4 times the limit)
Apr 1, 2010 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.0235 mg/L, federal limit 0.01 mg/L (2.4 times the limit)
Jan 1, 2010 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.024425 mg/L, federal limit 0.01 mg/L (2.4 times the limit)
Oct 1, 2009 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.02295 mg/L, federal limit 0.01 mg/L (2.3 times the limit)
Jul 1, 2009 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.024775 mg/L, federal limit 0.01 mg/L (2.5 times the limit)
Apr 1, 2009 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.02435 mg/L, federal limit 0.01 mg/L (2.4 times the limit)
Jan 1, 2009 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.022863 mg/L, federal limit 0.01 mg/L (2.3 times the limit)
Oct 1, 2008 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.022913 mg/L, federal limit 0.01 mg/L (2.3 times the limit)
Jul 1, 2008 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.023638 mg/L, federal limit 0.01 mg/L (2.4 times the limit)
Apr 1, 2008 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.023738 mg/L, federal limit 0.01 mg/L (2.4 times the limit)
Jan 1, 2008 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.023725 mg/L, federal limit 0.01 mg/L (2.4 times the limit)
Oct 1, 2007 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.023275 mg/L, federal limit 0.01 mg/L (2.3 times the limit)
Jul 1, 2007 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.023225 mg/L, federal limit 0.01 mg/L (2.3 times the limit)
Apr 1, 2007 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.022675 mg/L, federal limit 0.01 mg/L (2.3 times the limit)
Jan 1, 2007 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.02355 mg/L, federal limit 0.01 mg/L (2.4 times the limit)
Oct 1, 2006 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.0186 mg/L, federal limit 0.01 mg/L (1.9 times the limit)
Jul 1, 2006 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.012325 mg/L, federal limit 0.01 mg/L (1.2 times the limit)
Apr 1, 2006 Resolved

Enforcement actions

Texas regulators and EPA took 4 formal enforcement actions against City of Flatonia between 2007 and 2017. The most recent was a compliance order (no penalty) in December 2017.

Date By Action Violations covered
Dec 12, 2017 EPA Compliance order (no penalty) 39 violations (33 health-based): Public Notice, Arsenic
Jul 19, 2011 EPA Compliance order (no penalty) 26 violations (26 health-based): Arsenic
Apr 12, 2011 Texas Signed compliance agreement 21 violations (21 health-based): Arsenic
Aug 14, 2007 Texas Signed compliance agreement 17 violations (17 health-based): Arsenic

What the violations mean

Arsenic

7 incidents

Arsenic exceeded the federal limit

Long-term arsenic exposure is linked to cancer and cardiovascular effects

LEAD AND COPPER RULE REVISIONS

1 incident

The system did not complete a treatment step or action that the LEAD AND COPPER RULE REVISIONS requires (a treatment technique violation).

The utility had to notify customers about this violation.

Where the water comes from

City of Flatonia draws water from 3 wells.

Annual water quality report

City of Flatonia must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.

Where the state allows it, systems serving fewer than 10,000 people may publish the report in a local newspaper or news site instead of mailing it, and must provide a copy on request.

Find a posted report with EPA's Consumer Confidence Report search

Testing your own water