Public water system record
City of Cisco
Serves Cisco, Eastland County, TX · 4,076 people served
Federal records show 12 health-based violations and 20 monitoring/reporting issues for City of Cisco in the last ten years. The most serious issue in this window was a resolved Revised Total Coliform Rule violation.
System profile
- Health-based violations, last 10 years
- 12
- Resolved
- 12
- Unresolved
- 0
- Any acute record
- No
- Monitoring issues, last 10 years
- 20
Key facts
- City of Cisco draws water from 1 surface water intake.
- Highest measured level in the last 10 years: Total Trihalomethanes (TTHMs), 0.144 mg/L, federal limit 0.08 mg/L (1.8 times the limit), 2018.
- Most recent formal enforcement: compliance order with a penalty by Texas, April 2019.
- Record on file since 1992, with 39 health-based violations before October 19, 2016.
- Lead pipe inventory: 0 lead and 5 unknown out of 1,689 service lines.
Check whether City of Cisco serves your address
Health-based violations
Since October 2016Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.
| Contaminant | Rule family | Start date | Status | Acute |
|---|---|---|---|---|
|
Revised Total Coliform Rule
Treatment technique failure
|
110 | Dec 2, 2022 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.092 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
220 | Jul 1, 2022 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.1 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
|
220 | Apr 1, 2022 | Resolved | No |
|
Chlorite
Contaminant limit exceeded
Measured 1.3 mg/L, federal limit 1 mg/L (1.3 times the limit)
|
210 | Sep 1, 2021 | Resolved | No |
|
Chlorine dioxide
Disinfectant residual limit exceeded
Measured 0.9 mg/L, federal limit 0.8 mg/L (1.1 times the limit)
|
210 | Aug 1, 2019 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.082 mg/L, federal limit 0.08 mg/L (at or just above the limit)
|
220 | Oct 1, 2018 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.113 mg/L, federal limit 0.08 mg/L (1.4 times the limit)
|
220 | Jul 1, 2018 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.143 mg/L, federal limit 0.08 mg/L (1.8 times the limit)
|
220 | Apr 1, 2018 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.144 mg/L, federal limit 0.08 mg/L (1.8 times the limit)
|
220 | Apr 1, 2018 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.141 mg/L, federal limit 0.08 mg/L (1.8 times the limit)
|
220 | Jan 1, 2018 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.115 mg/L, federal limit 0.08 mg/L (1.4 times the limit)
|
220 | Oct 1, 2017 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.084 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
220 | Jul 1, 2017 | Resolved | No |
Monitoring and reporting issues
Since October 2016Missed tests or reports, not contaminants found above a limit.
| Issue | Start date | Status |
|---|---|---|
|
Public Notice
OTHER
|
Dec 8, 2022 | Resolved |
|
Chlorite
Monitoring and reporting
|
Sep 1, 2022 | Resolved |
|
Public Notice
OTHER
|
Aug 18, 2021 | Resolved |
|
Public Notice
OTHER
|
Aug 15, 2021 | Resolved |
|
Public Notice
OTHER
|
Jul 17, 2021 | Resolved |
|
Public Notice
OTHER
|
Jul 2, 2021 | Resolved |
|
Public Notice
OTHER
|
Jul 1, 2021 | Resolved |
|
Public Notice
OTHER
|
Jun 23, 2021 | Resolved |
|
Interim Enhanced Surface Water Treatment Rule
Monitoring and reporting
|
May 1, 2021 | Resolved |
|
Public Notice
OTHER
|
Nov 11, 2020 | Resolved |
|
Public Notice
OTHER
|
Nov 10, 2020 | Resolved |
|
Interim Enhanced Surface Water Treatment Rule
Monitoring and reporting
|
Aug 1, 2020 | Resolved |
|
Chlorite
Monitoring and reporting
|
Jan 1, 2020 | Resolved |
|
Chlorite
Monitoring and reporting
|
Dec 1, 2019 | Resolved |
|
Public Notice
OTHER
|
Nov 18, 2019 | Resolved |
|
Chlorite
Monitoring and reporting
|
Aug 1, 2019 | Resolved |
|
Interim Enhanced Surface Water Treatment Rule
Monitoring and reporting
|
Jun 1, 2019 | Resolved |
|
Long Term 2 Enhanced Surface Water Treatment Rule
Monitoring and reporting
|
Jun 1, 2019 | Resolved |
|
Interim Enhanced Surface Water Treatment Rule
Monitoring and reporting
|
Apr 1, 2019 | Resolved |
|
Interim Enhanced Surface Water Treatment Rule
Monitoring and reporting
|
Aug 1, 2017 | Resolved |
Full record since 1992
EPA's records for City of Cisco go back to 1992. Before October 19, 2016 they list 39 health-based violations (38 resolved, 1 archived by EPA without a recorded fix) and 15 monitoring or reporting violations.
| Violations that began in | Health-based | Monitoring and reporting |
|---|---|---|
| 1990s | 1 | 5 |
| 2000s | 28 | 0 |
| 2010 to October 18, 2016 | 10 | 10 |
| October 19, 2016 to 2019 | 8 | 7 |
| 2020s | 4 | 13 |
Most recent health-based violation before October 19, 2016: Total Trihalomethanes (TTHMs), began April 2016, Resolved.
Show all 39 health-based violations before October 19, 2016
| Contaminant | Start date | Status |
|---|---|---|
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.083 mg/L, federal limit 0.08 mg/L (at or just above the limit)
|
Apr 1, 2016 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.095 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
Jan 1, 2016 | Resolved |
|
Long Term 2 Enhanced Surface Water Treatment Rule
Treatment technique failure
|
Dec 1, 2015 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.099 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
Oct 1, 2015 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.091 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Jul 1, 2015 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.117 mg/L, federal limit 0.08 mg/L (1.5 times the limit)
|
Apr 1, 2015 | Resolved |
|
Total Coliform
Contaminant limit exceeded
|
Apr 1, 2015 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.111 mg/L, federal limit 0.08 mg/L (1.4 times the limit)
|
Jan 1, 2015 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.104 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
|
Oct 1, 2014 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.096 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
Jul 1, 2014 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.083 mg/L, federal limit 0.08 mg/L (at or just above the limit)
|
Jan 1, 2009 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.082 mg/L, federal limit 0.08 mg/L (at or just above the limit)
|
Oct 1, 2008 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.083 mg/L, federal limit 0.08 mg/L (at or just above the limit)
|
Jul 1, 2008 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.095 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
Apr 1, 2008 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.087 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Jan 1, 2008 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.084 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Oct 1, 2007 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.09 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Oct 1, 2006 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.094 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
Jul 1, 2006 | Resolved |
|
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
|
May 1, 2006 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.091 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Apr 1, 2006 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.083 mg/L, federal limit 0.08 mg/L (at or just above the limit)
|
Jan 1, 2006 | Resolved |
|
Total Coliform
Contaminant limit exceeded
|
Aug 1, 2005 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.109 mg/L, federal limit 0.08 mg/L (1.4 times the limit)
|
Jul 1, 2005 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.113 mg/L, federal limit 0.08 mg/L (1.4 times the limit)
|
Apr 1, 2005 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.15 mg/L, federal limit 0.08 mg/L (1.9 times the limit)
|
Jan 1, 2005 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.088 mg/L, federal limit 0.06 mg/L (1.5 times the limit)
|
Jan 1, 2005 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.103 mg/L, federal limit 0.06 mg/L (1.7 times the limit)
|
Oct 1, 2004 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.13 mg/L, federal limit 0.08 mg/L (1.6 times the limit)
|
Oct 1, 2004 | Resolved |
|
Surface Water Treatment Rule
Treatment technique failure
|
Sep 1, 2004 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.088 mg/L, federal limit 0.06 mg/L (1.5 times the limit)
|
Jul 1, 2004 | Resolved |
|
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
|
Jul 1, 2004 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.061 mg/L, federal limit 0.06 mg/L (at or just above the limit)
|
Apr 1, 2004 | Resolved |
|
Surface Water Treatment Rule
Treatment technique failure
|
Nov 1, 2003 | Resolved |
|
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
|
Nov 1, 2003 | Resolved |
|
Surface Water Treatment Rule
Treatment technique failure
|
Mar 1, 2003 | Resolved |
|
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
|
Mar 1, 2003 | Resolved |
|
Surface Water Treatment Rule
Treatment technique failure
|
Dec 1, 2002 | Resolved |
|
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
|
Dec 1, 2002 | Resolved |
|
Total Coliform
Contaminant limit exceeded
|
Jul 1, 1992 | Archived |
Enforcement actions
Texas regulators took 4 formal enforcement actions against City of Cisco between 2005 and 2019, filed as 5 records in EPA's data. The most recent was a compliance order with a penalty in April 2019.
| Date | By | Action | Violations covered |
|---|---|---|---|
| Apr 26, 2019 | Texas | Compliance order with a penalty | 7 violations (7 health-based): Total Trihalomethanes (TTHMs) |
| Aug 10, 2015 | Texas | Compliance order with a penalty | 9 violations (8 health-based): Total Trihalomethanes (TTHMs), Lead and Copper Rule |
| Jul 20, 2009 | Texas | Compliance order with a penalty | 5 violations (5 health-based): Total Trihalomethanes (TTHMs) |
| Apr 25, 2005 | Texas | Compliance order with a penalty | 12 violations (12 health-based): Total Trihalomethanes (TTHMs), Haloacetic Acids (HAA5) |
What the violations mean
Total Trihalomethanes (TTHMs)
9 incidentsDisinfection byproduct levels exceeded the federal limit
Long-term TTHM exposure may increase bladder cancer risk
Revised Total Coliform Rule
1 incidentThe system did not meet a requirement of the Revised Total Coliform Rule
Coliform and E. coli rules protect against bacteria in the distribution system
Chlorite
1 incidentTest results for Chlorite were above the federal limit (a maximum contaminant level violation).
The utility had to notify customers about this violation.
Chlorine dioxide
1 incidentChlorine dioxide levels were above the federal maximum residual disinfectant level.
The utility had to notify customers about this violation.
Where the water comes from
City of Cisco draws water from 1 surface water intake. 1 other community water system buys water from City of Cisco.
Community systems that buy water from it
- Westbound WSC Cisco, TX
Annual water quality report
City of Cisco must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.
Where the state allows it, systems serving fewer than 10,000 people may publish the report in a local newspaper or news site instead of mailing it, and must provide a copy on request.
Find a posted report with EPA's Consumer Confidence Report search
Testing your own water
To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Texas.
Certified drinking water labs by state EPA guidance for private wells