Public water system record
Freer WCID
Serves Freer, Duval County, TX · 2,923 people served
Federal records show 14 health-based violations and 5 monitoring/reporting issues for Freer WCID in the last ten years. The most serious issue in this window was a Arsenic violation that EPA lists as archived, not resolved.
System profile
- Health-based violations, last 10 years
- 14
- Resolved
- 2
- Unresolved
- 0
- Archived by EPA
- 12
- Any acute record
- No
- Monitoring issues, last 10 years
- 5
Key facts
- Freer WCID draws water from 6 wells.
- Highest measured level in the last 10 years: Arsenic, 0.038 mg/L, federal limit 0.01 mg/L (3.8 times the limit), 2024.
- Most recent formal enforcement: compliance order (no penalty) by Texas, June 2025.
- Record on file since 2006, with 37 health-based violations before October 19, 2016.
- Lead pipe inventory: 0 lead and 2 unknown out of 1,404 service lines.
Check whether Freer WCID serves your address
Health-based violations
Since October 2016Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.
| Contaminant | Rule family | Start date | Status | Acute |
|---|---|---|---|---|
|
Arsenic
Contaminant limit exceeded
Measured 0.018 mg/L, federal limit 0.01 mg/L (1.8 times the limit)
|
330 | Oct 1, 2025 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.034 mg/L, federal limit 0.01 mg/L (3.4 times the limit)
|
330 | Apr 1, 2025 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.035 mg/L, federal limit 0.01 mg/L (3.5 times the limit)
|
330 | Jan 1, 2025 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.035 mg/L, federal limit 0.01 mg/L (3.5 times the limit)
|
330 | Oct 1, 2024 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.036 mg/L, federal limit 0.01 mg/L (3.6 times the limit)
|
330 | Jul 1, 2024 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.038 mg/L, federal limit 0.01 mg/L (3.8 times the limit)
|
330 | Apr 1, 2024 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.038 mg/L, federal limit 0.01 mg/L (3.8 times the limit)
|
330 | Jan 1, 2024 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.031 mg/L, federal limit 0.01 mg/L (3.1 times the limit)
|
330 | Oct 1, 2023 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.023 mg/L, federal limit 0.01 mg/L (2.3 times the limit)
|
330 | Jul 1, 2023 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.019 mg/L, federal limit 0.01 mg/L (1.9 times the limit)
|
330 | Jan 1, 2023 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.018 mg/L, federal limit 0.01 mg/L (1.8 times the limit)
|
330 | Oct 1, 2022 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.016 mg/L, federal limit 0.01 mg/L (1.6 times the limit)
|
330 | Jul 1, 2022 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.014 mg/L, federal limit 0.01 mg/L (1.4 times the limit)
|
330 | Jan 1, 2017 | Resolved | No |
|
Arsenic
Contaminant limit exceeded
Measured 0.015 mg/L, federal limit 0.01 mg/L (1.5 times the limit)
|
330 | Oct 1, 2016 | Resolved | No |
Monitoring and reporting issues
Since October 2016Missed tests or reports, not contaminants found above a limit.
| Issue | Start date | Status |
|---|---|---|
|
Public Notice
OTHER
|
Dec 1, 2024 | Resolved |
|
Arsenic
Monitoring and reporting
|
Apr 1, 2023 | Resolved |
|
Nitrate
Monitoring and reporting
|
Apr 1, 2023 | Resolved |
|
Public Notice
OTHER
|
Mar 16, 2023 | Resolved |
|
E. coli
Monitoring and reporting
|
Mar 28, 2012 | Resolved |
Full record since 2006
EPA's records for Freer WCID go back to 2006. Before October 19, 2016 they list 37 health-based violations (37 resolved) and 6 monitoring or reporting violations.
| Violations that began in | Health-based | Monitoring and reporting |
|---|---|---|
| 2000s | 14 | 1 |
| 2010 to October 18, 2016 | 23 | 5 |
| October 19, 2016 to 2019 | 1 | 0 |
| 2020s | 12 | 4 |
Most recent health-based violation before October 19, 2016: Arsenic, began October 2016, Resolved.
Show all 37 health-based violations before October 19, 2016
| Contaminant | Start date | Status |
|---|---|---|
|
Arsenic
Contaminant limit exceeded
Measured 0.015 mg/L, federal limit 0.01 mg/L (1.5 times the limit)
|
Oct 1, 2016 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.018 mg/L, federal limit 0.01 mg/L (1.8 times the limit)
|
Jul 1, 2016 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.016 mg/L, federal limit 0.01 mg/L (1.6 times the limit)
|
Apr 1, 2016 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.016 mg/L, federal limit 0.01 mg/L (1.6 times the limit)
|
Jan 1, 2016 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.016 mg/L, federal limit 0.01 mg/L (1.6 times the limit)
|
Oct 1, 2015 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.014 mg/L, federal limit 0.01 mg/L (1.4 times the limit)
|
Jul 1, 2015 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.012 mg/L, federal limit 0.01 mg/L (1.2 times the limit)
|
Apr 1, 2015 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.014 mg/L, federal limit 0.01 mg/L (1.4 times the limit)
|
Oct 1, 2013 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.022 mg/L, federal limit 0.01 mg/L (2.2 times the limit)
|
Jul 1, 2013 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.03 mg/L, federal limit 0.01 mg/L (3 times the limit)
|
Apr 1, 2013 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.038 mg/L, federal limit 0.01 mg/L (3.8 times the limit)
|
Jan 1, 2013 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.039 mg/L, federal limit 0.01 mg/L (3.9 times the limit)
|
Oct 1, 2012 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.039 mg/L, federal limit 0.01 mg/L (3.9 times the limit)
|
Jul 1, 2012 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.041 mg/L, federal limit 0.01 mg/L (4.1 times the limit)
|
Apr 1, 2012 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.042 mg/L, federal limit 0.01 mg/L (4.2 times the limit)
|
Jan 1, 2012 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.041 mg/L, federal limit 0.01 mg/L (4.1 times the limit)
|
Oct 1, 2011 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.043 mg/L, federal limit 0.01 mg/L (4.3 times the limit)
|
Jul 1, 2011 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.045 mg/L, federal limit 0.01 mg/L (4.5 times the limit)
|
Apr 1, 2011 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.047 mg/L, federal limit 0.01 mg/L (4.7 times the limit)
|
Jan 1, 2011 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.045425 mg/L, federal limit 0.01 mg/L (4.5 times the limit)
|
Oct 1, 2010 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.0447 mg/L, federal limit 0.01 mg/L (4.5 times the limit)
|
Jul 1, 2010 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.043175 mg/L, federal limit 0.01 mg/L (4.3 times the limit)
|
Apr 1, 2010 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.0429 mg/L, federal limit 0.01 mg/L (4.3 times the limit)
|
Jan 1, 2010 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.042575 mg/L, federal limit 0.01 mg/L (4.3 times the limit)
|
Oct 1, 2009 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.043275 mg/L, federal limit 0.01 mg/L (4.3 times the limit)
|
Jul 1, 2009 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.04275 mg/L, federal limit 0.01 mg/L (4.3 times the limit)
|
Apr 1, 2009 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.043275 mg/L, federal limit 0.01 mg/L (4.3 times the limit)
|
Jan 1, 2009 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.0439 mg/L, federal limit 0.01 mg/L (4.4 times the limit)
|
Oct 1, 2008 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.044225 mg/L, federal limit 0.01 mg/L (4.4 times the limit)
|
Jul 1, 2008 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.044975 mg/L, federal limit 0.01 mg/L (4.5 times the limit)
|
Apr 1, 2008 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.045 mg/L, federal limit 0.01 mg/L (4.5 times the limit)
|
Jan 1, 2008 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.044425 mg/L, federal limit 0.01 mg/L (4.4 times the limit)
|
Oct 1, 2007 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.042325 mg/L, federal limit 0.01 mg/L (4.2 times the limit)
|
Jul 1, 2007 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.04185 mg/L, federal limit 0.01 mg/L (4.2 times the limit)
|
Apr 1, 2007 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.040425 mg/L, federal limit 0.01 mg/L (4 times the limit)
|
Jan 1, 2007 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.039 mg/L, federal limit 0.01 mg/L (3.9 times the limit)
|
Oct 1, 2006 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.01885 mg/L, federal limit 0.01 mg/L (1.9 times the limit)
|
Apr 1, 2006 | Resolved |
Enforcement actions
Texas regulators and EPA took 5 formal enforcement actions against Freer WCID between 2007 and 2025. The most recent was a compliance order (no penalty) in June 2025.
| Date | By | Action | Violations covered |
|---|---|---|---|
| Jun 24, 2025 | Texas | Compliance order (no penalty) | 11 violations (11 health-based): Arsenic |
| Jun 8, 2016 | EPA | Compliance order (no penalty) | 39 violations (38 health-based): Arsenic, Public Notice |
| Jul 19, 2011 | EPA | Compliance order (no penalty) | 33 violations (32 health-based): Arsenic, Public Notice |
| Mar 28, 2011 | Texas | Signed compliance agreement | 20 violations (20 health-based): Arsenic |
| Oct 10, 2007 | Texas | Signed compliance agreement | 17 violations (17 health-based): Arsenic |
What the violations mean
Arsenic
14 incidentsArsenic exceeded the federal limit
Long-term arsenic exposure is linked to cancer and cardiovascular effects
Where the water comes from
Freer WCID draws water from 6 wells.
Annual water quality report
Freer WCID must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.
Where the state allows it, systems serving fewer than 10,000 people may publish the report in a local newspaper or news site instead of mailing it, and must provide a copy on request.
Find a posted report with EPA's Consumer Confidence Report search
Testing your own water
To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Texas.
Certified drinking water labs by state EPA guidance for private wells