Public water system record

City of Santa Rosa

Serves an area of Cameron County, TX that includes Santa Rosa and Tierra Bonita · 2,883 people served

Federal records show 5 health-based violations and 34 monitoring/reporting issues for City of Santa Rosa in the last ten years, including an unresolved LEAD AND COPPER RULE REVISIONS violation.

  • TX0310009
  • SANTA ROSA
  • TX
  • 2,883 served

System profile

Source water Surface water
ZIP 78593
EPA system ID TX0310009

Verify this system on EPA ECHO →

Health-based violations, last 10 years
5
Resolved
1
Unresolved
1
Archived by EPA
3
Any acute record
No
Monitoring issues, last 10 years
34

Key facts

  • City of Santa Rosa draws water from 1 surface water intake.
  • Highest measured level in the last 10 years: Total Trihalomethanes (TTHMs), 0.109 mg/L, federal limit 0.08 mg/L (1.4 times the limit), 2025.
  • Most recent formal enforcement: compliance order with a penalty by Texas, September 2014.
  • Record on file since 1991, with 31 health-based violations before October 19, 2016.

Check whether City of Santa Rosa serves your address

Address suggestions by Mapbox

Health-based violations

Since October 2016

Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.

Contaminant Rule family Start date Status Acute
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.094 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
220 Oct 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.109 mg/L, federal limit 0.08 mg/L (1.4 times the limit)
220 Jul 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.092 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
220 Apr 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
LEAD AND COPPER RULE REVISIONS
Treatment technique failure
350 Oct 17, 2024 Active No
Chlorite
Contaminant limit exceeded
Measured 1.3 mg/L, federal limit 1 mg/L (1.3 times the limit)
210 Aug 1, 2019 Resolved No

Monitoring and reporting issues

Since October 2016

Missed tests or reports, not contaminants found above a limit.

Issue Start date Status
Public Notice
OTHER
Dec 24, 2025 Active
Total Trihalomethanes (TTHMs)
Monitoring and reporting
Dec 4, 2025 Active
Total Trihalomethanes (TTHMs)
Monitoring and reporting
Sep 2, 2025 Active
Public Notice
OTHER
Jul 12, 2025 Active
Consumer Confidence Rule
OTHER
Jul 1, 2025 Active
Total Trihalomethanes (TTHMs)
Monitoring and reporting
Jun 17, 2025 Active
Public Notice
OTHER
May 1, 2025 Active
Lead and Copper Rule
Monitoring and reporting
Dec 30, 2024 Resolved
LEAD AND COPPER RULE REVISIONS
RPT
Oct 17, 2024 Active
Consumer Confidence Rule
OTHER
Jul 1, 2022 Resolved
Public Notice
OTHER
Jan 30, 2022 Resolved
Public Notice
OTHER
Jan 30, 2022 Resolved
Public Notice
OTHER
Sep 18, 2021 Resolved
Public Notice
OTHER
Sep 18, 2021 Resolved
Haloacetic Acids (HAA5)
Monitoring and reporting
Jul 1, 2020 Resolved
Total Trihalomethanes (TTHMs)
Monitoring and reporting
Jul 1, 2020 Resolved
Total Trihalomethanes (TTHMs)
Monitoring and reporting
Apr 1, 2020 Resolved
Haloacetic Acids (HAA5)
Monitoring and reporting
Apr 1, 2020 Resolved
Public Notice
OTHER
Oct 21, 2019 Resolved
Consumer Confidence Rule
OTHER
Jul 1, 2019 Resolved
Chlorine dioxide
Monitoring and reporting
Sep 1, 2018 Resolved
Chlorite
Monitoring and reporting
Sep 1, 2018 Resolved
Consumer Confidence Rule
OTHER
Jul 1, 2018 Resolved
Lead and Copper Rule
Monitoring and reporting
Sep 29, 2017 Resolved
Interim Enhanced Surface Water Treatment Rule
Monitoring and reporting
Mar 1, 2017 Resolved
Chlorite
Monitoring and reporting
Mar 1, 2017 Resolved
Chlorine dioxide
Monitoring and reporting
Mar 1, 2017 Resolved
Public Notice
OTHER
Nov 12, 2016 Resolved
Lead and Copper Rule
Monitoring and reporting
Jul 1, 2016 Resolved
Lead and Copper Rule
Monitoring and reporting
Oct 1, 2015 Resolved
Lead and Copper Rule
Monitoring and reporting
Oct 1, 2014 Resolved
Lead and Copper Rule
Monitoring and reporting
Oct 1, 2013 Resolved
Lead and Copper Rule
Monitoring and reporting
Oct 1, 2010 Resolved
Public Notice
OTHER
May 27, 2010 Active

Full record since 1991

EPA's records for City of Santa Rosa go back to 1991. Before October 19, 2016 they list 31 health-based violations (30 resolved, 1 archived by EPA without a recorded fix) and 40 monitoring or reporting violations.

Violations that began in Health-based Monitoring and reporting
1990s 1 1
2000s 28 1
2010 to October 18, 2016 2 38
October 19, 2016 to 2019 1 10
2020s 4 18

Most recent health-based violation before October 19, 2016: Total Trihalomethanes (TTHMs), began April 2010, Resolved.

Show all 31 health-based violations before October 19, 2016
Contaminant Start date Status
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.096 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
Apr 1, 2010 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.11 mg/L, federal limit 0.08 mg/L (1.4 times the limit)
Jan 1, 2010 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.09 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
Oct 1, 2009 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.096 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
Jul 1, 2009 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.084 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
Apr 1, 2009 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.081 mg/L, federal limit 0.08 mg/L (at or just above the limit)
Oct 1, 2008 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.089 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
Apr 1, 2008 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.092 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
Jan 1, 2008 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.081 mg/L, federal limit 0.08 mg/L (at or just above the limit)
Oct 1, 2007 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.082 mg/L, federal limit 0.08 mg/L (at or just above the limit)
Oct 1, 2006 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.062 mg/L, federal limit 0.06 mg/L (at or just above the limit)
Jul 1, 2006 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.115 mg/L, federal limit 0.08 mg/L (1.4 times the limit)
Jul 1, 2006 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.103 mg/L, federal limit 0.06 mg/L (1.7 times the limit)
Apr 1, 2006 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.185 mg/L, federal limit 0.08 mg/L (2.3 times the limit)
Apr 1, 2006 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.219 mg/L, federal limit 0.08 mg/L (2.7 times the limit)
Jan 1, 2006 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.114 mg/L, federal limit 0.06 mg/L (1.9 times the limit)
Jan 1, 2006 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.224 mg/L, federal limit 0.08 mg/L (2.8 times the limit)
Oct 1, 2005 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.133 mg/L, federal limit 0.06 mg/L (2.2 times the limit)
Oct 1, 2005 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.15 mg/L, federal limit 0.06 mg/L (2.5 times the limit)
Jul 1, 2005 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.251 mg/L, federal limit 0.08 mg/L (3.1 times the limit)
Jul 1, 2005 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.15 mg/L, federal limit 0.06 mg/L (2.5 times the limit)
Apr 1, 2005 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.259 mg/L, federal limit 0.08 mg/L (3.2 times the limit)
Apr 1, 2005 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.17 mg/L, federal limit 0.06 mg/L (2.8 times the limit)
Jan 1, 2005 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.297 mg/L, federal limit 0.08 mg/L (3.7 times the limit)
Jan 1, 2005 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.316 mg/L, federal limit 0.08 mg/L (4 times the limit)
Oct 1, 2004 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.149 mg/L, federal limit 0.06 mg/L (2.5 times the limit)
Oct 1, 2004 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.237 mg/L, federal limit 0.08 mg/L (3 times the limit)
Jul 1, 2004 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.112 mg/L, federal limit 0.06 mg/L (1.9 times the limit)
Jul 1, 2004 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.153 mg/L, federal limit 0.08 mg/L (1.9 times the limit)
Apr 1, 2004 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.07 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
Apr 1, 2004 Resolved
Total Coliform (acute)
Contaminant limit exceeded
Aug 1, 1991 Archived

Enforcement actions

Texas regulators took 2 formal enforcement actions against City of Santa Rosa between 2010 and 2014, filed as 3 records in EPA's data. The most recent was a compliance order with a penalty in September 2014.

Date By Action Violations covered
Sep 22, 2014 Texas Compliance order with a penalty 21 violations: Lead and Copper Rule, Interim Enhanced Surface Water Treatment Rule
Mar 8, 2010 Texas Compliance order with a penalty 16 violations (16 health-based): Total Trihalomethanes (TTHMs)

What the violations mean

Total Trihalomethanes (TTHMs)

3 incidents

Disinfection byproduct levels exceeded the federal limit

Long-term TTHM exposure may increase bladder cancer risk

LEAD AND COPPER RULE REVISIONS

1 incident

The system did not complete a treatment step or action that the LEAD AND COPPER RULE REVISIONS requires (a treatment technique violation).

The utility had to notify customers about this violation.

Chlorite

1 incident

Test results for Chlorite were above the federal limit (a maximum contaminant level violation).

The utility had to notify customers about this violation.

Where the water comes from

City of Santa Rosa draws water from 1 surface water intake.

Annual water quality report

City of Santa Rosa must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.

Where the state allows it, systems serving fewer than 10,000 people may publish the report in a local newspaper or news site instead of mailing it, and must provide a copy on request.

Find a posted report with EPA's Consumer Confidence Report search

Testing your own water

To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Texas.