Federal records show 70 health-based violations and 38 monitoring/reporting issues for Council Creek Village in the last ten years. The most serious issue in this window was a Gross Alpha, Excl. Radon and U violation that EPA lists as archived, not resolved.
System profile
- Health-based violations, last 10 years
- 70
- Resolved
- 0
- Unresolved
- 0
- Archived by EPA
- 70
- Any acute record
- No
- Monitoring issues, last 10 years
- 38
Key facts
- Council Creek Village draws water from 4 wells (2 of them for emergency, seasonal or other part-time use).
- Highest measured level in the last 10 years: Gross Alpha, Excl. Radon and U, 124 pCi/L, federal limit 15 pCi/L (8.3 times the limit), 2025.
- Most recent formal enforcement: compliance order (no penalty) by EPA, September 2016.
- Record on file since 1988, with 119 health-based violations before October 19, 2016.
- Lead pipe inventory: 0 lead and 68 unknown out of 132 service lines.
Check whether Council Creek Village serves your address
Health-based violations
Since October 2016Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.
| Contaminant | Rule family | Start date | Status | Acute |
|---|---|---|---|---|
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 91 pCi/L, federal limit 15 pCi/L (6.1 times the limit)
|
340 | Jul 1, 2025 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 30 pCi/L, federal limit 5 pCi/L (6 times the limit)
|
340 | Jul 1, 2025 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 124 pCi/L, federal limit 15 pCi/L (8.3 times the limit)
|
340 | Jan 1, 2025 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 39 pCi/L, federal limit 5 pCi/L (7.8 times the limit)
|
340 | Jan 1, 2025 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 122 pCi/L, federal limit 15 pCi/L (8.1 times the limit)
|
340 | Oct 1, 2024 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 37 pCi/L, federal limit 5 pCi/L (7.4 times the limit)
|
340 | Oct 1, 2024 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 114 pCi/L, federal limit 15 pCi/L (7.6 times the limit)
|
340 | Jul 1, 2024 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 37 pCi/L, federal limit 5 pCi/L (7.4 times the limit)
|
340 | Jul 1, 2024 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 117 pCi/L, federal limit 15 pCi/L (7.8 times the limit)
|
340 | Apr 1, 2024 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 38 pCi/L, federal limit 5 pCi/L (7.6 times the limit)
|
340 | Apr 1, 2024 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 37 pCi/L, federal limit 5 pCi/L (7.4 times the limit)
|
340 | Jan 1, 2024 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 114 pCi/L, federal limit 15 pCi/L (7.6 times the limit)
|
340 | Jan 1, 2024 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 112 pCi/L, federal limit 15 pCi/L (7.5 times the limit)
|
340 | Oct 1, 2023 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 40 pCi/L, federal limit 5 pCi/L (8 times the limit)
|
340 | Oct 1, 2023 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 102 pCi/L, federal limit 15 pCi/L (6.8 times the limit)
|
340 | Jul 1, 2023 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 41 pCi/L, federal limit 5 pCi/L (8.2 times the limit)
|
340 | Jul 1, 2023 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 92 pCi/L, federal limit 15 pCi/L (6.1 times the limit)
|
340 | Apr 1, 2023 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 39 pCi/L, federal limit 5 pCi/L (7.8 times the limit)
|
340 | Apr 1, 2023 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 89 pCi/L, federal limit 15 pCi/L (5.9 times the limit)
|
340 | Jan 1, 2023 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 38 pCi/L, federal limit 5 pCi/L (7.6 times the limit)
|
340 | Jan 1, 2023 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 41 pCi/L, federal limit 5 pCi/L (8.2 times the limit)
|
340 | Oct 1, 2022 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 94 pCi/L, federal limit 15 pCi/L (6.3 times the limit)
|
340 | Oct 1, 2022 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 41 pCi/L, federal limit 5 pCi/L (8.2 times the limit)
|
340 | Jul 1, 2022 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 101 pCi/L, federal limit 15 pCi/L (6.7 times the limit)
|
340 | Jul 1, 2022 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 41 pCi/L, federal limit 5 pCi/L (8.2 times the limit)
|
340 | Apr 1, 2022 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 109 pCi/L, federal limit 15 pCi/L (7.3 times the limit)
|
340 | Apr 1, 2022 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 105 pCi/L, federal limit 15 pCi/L (7 times the limit)
|
340 | Jan 1, 2022 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 41 pCi/L, federal limit 5 pCi/L (8.2 times the limit)
|
340 | Jan 1, 2022 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 95 pCi/L, federal limit 15 pCi/L (6.3 times the limit)
|
340 | Oct 1, 2021 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 35 pCi/L, federal limit 5 pCi/L (7 times the limit)
|
340 | Oct 1, 2021 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 91 pCi/L, federal limit 15 pCi/L (6.1 times the limit)
|
340 | Jul 1, 2021 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 34 pCi/L, federal limit 5 pCi/L (6.8 times the limit)
|
340 | Jul 1, 2021 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 87 pCi/L, federal limit 15 pCi/L (5.8 times the limit)
|
340 | Apr 1, 2021 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 36 pCi/L, federal limit 5 pCi/L (7.2 times the limit)
|
340 | Apr 1, 2021 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 88 pCi/L, federal limit 15 pCi/L (5.9 times the limit)
|
340 | Jan 1, 2021 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 36 pCi/L, federal limit 5 pCi/L (7.2 times the limit)
|
340 | Jan 1, 2021 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 88 pCi/L, federal limit 15 pCi/L (5.9 times the limit)
|
340 | Oct 1, 2020 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 36 pCi/L, federal limit 5 pCi/L (7.2 times the limit)
|
340 | Oct 1, 2020 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 99 pCi/L, federal limit 15 pCi/L (6.6 times the limit)
|
340 | Jul 1, 2020 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 35 pCi/L, federal limit 5 pCi/L (7 times the limit)
|
340 | Jul 1, 2020 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 107 pCi/L, federal limit 15 pCi/L (7.1 times the limit)
|
340 | Apr 1, 2020 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 35 pCi/L, federal limit 5 pCi/L (7 times the limit)
|
340 | Apr 1, 2020 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 35 pCi/L, federal limit 5 pCi/L (7 times the limit)
|
340 | Jan 1, 2020 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 114 pCi/L, federal limit 15 pCi/L (7.6 times the limit)
|
340 | Jan 1, 2020 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 115 pCi/L, federal limit 15 pCi/L (7.7 times the limit)
|
340 | Oct 1, 2019 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 36 pCi/L, federal limit 5 pCi/L (7.2 times the limit)
|
340 | Oct 1, 2019 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 101 pCi/L, federal limit 15 pCi/L (6.7 times the limit)
|
340 | Jul 1, 2019 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 36 pCi/L, federal limit 5 pCi/L (7.2 times the limit)
|
340 | Jul 1, 2019 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 100 pCi/L, federal limit 15 pCi/L (6.7 times the limit)
|
340 | Apr 1, 2019 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 34 pCi/L, federal limit 5 pCi/L (6.8 times the limit)
|
340 | Apr 1, 2019 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 102 pCi/L, federal limit 15 pCi/L (6.8 times the limit)
|
340 | Jan 1, 2019 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 36 pCi/L, federal limit 5 pCi/L (7.2 times the limit)
|
340 | Jan 1, 2019 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 113 pCi/L, federal limit 15 pCi/L (7.5 times the limit)
|
340 | Oct 1, 2018 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 36 pCi/L, federal limit 5 pCi/L (7.2 times the limit)
|
340 | Oct 1, 2018 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 37 pCi/L, federal limit 5 pCi/L (7.4 times the limit)
|
340 | Jul 1, 2018 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 123 pCi/L, federal limit 15 pCi/L (8.2 times the limit)
|
340 | Jul 1, 2018 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 38 pCi/L, federal limit 5 pCi/L (7.6 times the limit)
|
340 | Apr 1, 2018 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 113 pCi/L, federal limit 15 pCi/L (7.5 times the limit)
|
340 | Apr 1, 2018 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 110 pCi/L, federal limit 15 pCi/L (7.3 times the limit)
|
340 | Jan 1, 2018 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 36 pCi/L, federal limit 5 pCi/L (7.2 times the limit)
|
340 | Jan 1, 2018 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 100 pCi/L, federal limit 15 pCi/L (6.7 times the limit)
|
340 | Oct 1, 2017 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 36 pCi/L, federal limit 5 pCi/L (7.2 times the limit)
|
340 | Oct 1, 2017 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 34 pCi/L, federal limit 5 pCi/L (6.8 times the limit)
|
340 | Jul 1, 2017 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 94 pCi/L, federal limit 15 pCi/L (6.3 times the limit)
|
340 | Jul 1, 2017 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 90 pCi/L, federal limit 15 pCi/L (6 times the limit)
|
340 | Apr 1, 2017 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 34 pCi/L, federal limit 5 pCi/L (6.8 times the limit)
|
340 | Apr 1, 2017 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 33 pCi/L, federal limit 5 pCi/L (6.6 times the limit)
|
340 | Jan 1, 2017 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 91 pCi/L, federal limit 15 pCi/L (6.1 times the limit)
|
340 | Jan 1, 2017 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 33 pCi/L, federal limit 5 pCi/L (6.6 times the limit)
|
340 | Oct 1, 2016 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 88 pCi/L, federal limit 15 pCi/L (5.9 times the limit)
|
340 | Oct 1, 2016 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
Monitoring and reporting issues
Since October 2016Missed tests or reports, not contaminants found above a limit.
| Issue | Start date | Status |
|---|---|---|
|
Lead and Copper Rule
Monitoring and reporting
|
Dec 30, 2025 | Active |
|
Lead and Copper Rule
Monitoring and reporting
|
Jun 1, 2025 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
|
Public Notice
OTHER
|
Dec 12, 2024 | Resolved |
|
Public Notice
OTHER
|
Dec 12, 2024 | Resolved |
|
Public Notice
OTHER
|
Mar 5, 2024 | Resolved |
|
Combined Radium (-226 and -228)
Monitoring and reporting
|
Jan 1, 2024 | Resolved |
|
Combined Uranium
Monitoring and reporting
|
Jan 1, 2024 | Resolved |
|
Gross Alpha, Excl. Radon and U
Monitoring and reporting
|
Jan 1, 2024 | Resolved |
|
Public Notice
OTHER
|
Sep 22, 2023 | Resolved |
|
Public Notice
OTHER
|
Sep 22, 2023 | Resolved |
|
Public Notice
OTHER
|
Jun 1, 2022 | Resolved |
|
Public Notice
OTHER
|
Jun 1, 2022 | Resolved |
|
Public Notice
OTHER
|
Apr 16, 2020 | Resolved |
|
Public Notice
OTHER
|
Mar 17, 2020 | Resolved |
|
Public Notice
OTHER
|
Jan 8, 2020 | Resolved |
|
Public Notice
OTHER
|
Jan 8, 2020 | Resolved |
|
Public Notice
OTHER
|
Dec 12, 2019 | Resolved |
|
Public Notice
OTHER
|
Dec 12, 2019 | Resolved |
|
Consumer Confidence Rule
OTHER
|
Jul 1, 2018 | Resolved |
|
Public Notice
OTHER
|
Jan 16, 2018 | Resolved |
|
Public Notice
OTHER
|
Jan 16, 2018 | Resolved |
|
Public Notice
OTHER
|
Aug 23, 2017 | Resolved |
|
Public Notice
OTHER
|
Aug 3, 2017 | Resolved |
|
Public Notice
OTHER
|
Mar 15, 2017 | Resolved |
|
Public Notice
OTHER
|
Mar 15, 2017 | Resolved |
|
Lead and Copper Rule
Monitoring and reporting
|
Dec 30, 2016 | Resolved |
|
Consumer Confidence Rule
OTHER
|
Jul 1, 2016 | Resolved |
|
Public Notice
OTHER
|
Apr 25, 2016 | Resolved |
|
Public Notice
OTHER
|
Feb 8, 2016 | Resolved |
|
Public Notice
OTHER
|
Feb 13, 2015 | Resolved |
|
Public Notice
OTHER
|
Sep 24, 2013 | Resolved |
|
Public Notice
OTHER
|
Sep 12, 2013 | Resolved |
|
Public Notice
OTHER
|
Aug 3, 2012 | Resolved |
|
Public Notice
OTHER
|
Aug 3, 2012 | Resolved |
|
Public Notice
OTHER
|
Jul 2, 2012 | Resolved |
|
Public Notice
OTHER
|
Jul 2, 2012 | Resolved |
|
Public Notice
OTHER
|
Jun 27, 2012 | Resolved |
|
Public Notice
OTHER
|
Dec 14, 2011 | Resolved |
Full record since 1988
EPA's records for Council Creek Village go back to 1988. Before October 19, 2016 they list 119 health-based violations (1 resolved, 118 archived by EPA without a recorded fix) and 49 monitoring or reporting violations.
| Violations that began in | Health-based | Monitoring and reporting |
|---|---|---|
| 1980s | 9 | 0 |
| 1990s | 6 | 2 |
| 2000s | 48 | 16 |
| 2010 to October 18, 2016 | 56 | 31 |
| October 19, 2016 to 2019 | 24 | 10 |
| 2020s | 44 | 16 |
Most recent health-based violation before October 19, 2016: Combined Radium (-226 and -228), began October 2016, Archived.
Show all 119 health-based violations before October 19, 2016
| Contaminant | Start date | Status |
|---|---|---|
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 33 pCi/L, federal limit 5 pCi/L (6.6 times the limit)
|
Oct 1, 2016 | Archived |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 88 pCi/L, federal limit 15 pCi/L (5.9 times the limit)
|
Oct 1, 2016 | Archived |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 35 pCi/L, federal limit 5 pCi/L (7 times the limit)
|
Jul 1, 2016 | Archived |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 96 pCi/L, federal limit 15 pCi/L (6.4 times the limit)
|
Jul 1, 2016 | Archived |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 34 pCi/L, federal limit 5 pCi/L (6.8 times the limit)
|
Apr 1, 2016 | Archived |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 110 pCi/L, federal limit 15 pCi/L (7.3 times the limit)
|
Apr 1, 2016 | Archived |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 35 pCi/L, federal limit 5 pCi/L (7 times the limit)
|
Jan 1, 2016 | Archived |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 113 pCi/L, federal limit 15 pCi/L (7.5 times the limit)
|
Jan 1, 2016 | Archived |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 35 pCi/L, federal limit 5 pCi/L (7 times the limit)
|
Oct 1, 2015 | Archived |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 112 pCi/L, federal limit 15 pCi/L (7.5 times the limit)
|
Oct 1, 2015 | Archived |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 35 pCi/L, federal limit 5 pCi/L (7 times the limit)
|
Jul 1, 2015 | Archived |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 110 pCi/L, federal limit 15 pCi/L (7.3 times the limit)
|
Jul 1, 2015 | Archived |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 100 pCi/L, federal limit 15 pCi/L (6.7 times the limit)
|
Apr 1, 2015 | Archived |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 36 pCi/L, federal limit 5 pCi/L (7.2 times the limit)
|
Apr 1, 2015 | Archived |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 38 pCi/L, federal limit 5 pCi/L (7.6 times the limit)
|
Jan 1, 2015 | Archived |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 99 pCi/L, federal limit 15 pCi/L (6.6 times the limit)
|
Jan 1, 2015 | Archived |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 102 pCi/L, federal limit 15 pCi/L (6.8 times the limit)
|
Oct 1, 2014 | Archived |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 38 pCi/L, federal limit 5 pCi/L (7.6 times the limit)
|
Oct 1, 2014 | Archived |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 37 pCi/L, federal limit 5 pCi/L (7.4 times the limit)
|
Jul 1, 2014 | Archived |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 99 pCi/L, federal limit 15 pCi/L (6.6 times the limit)
|
Jul 1, 2014 | Archived |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 95 pCi/L, federal limit 15 pCi/L (6.3 times the limit)
|
Apr 1, 2014 | Archived |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 36 pCi/L, federal limit 5 pCi/L (7.2 times the limit)
|
Apr 1, 2014 | Archived |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 49 pCi/L, federal limit 5 pCi/L (9.8 times the limit)
|
Jan 1, 2014 | Archived |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 113 pCi/L, federal limit 15 pCi/L (7.5 times the limit)
|
Jan 1, 2014 | Archived |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 51 pCi/L, federal limit 5 pCi/L (10 times the limit)
|
Oct 1, 2013 | Archived |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 113 pCi/L, federal limit 15 pCi/L (7.5 times the limit)
|
Oct 1, 2013 | Archived |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 54 pCi/L, federal limit 5 pCi/L (11 times the limit)
|
Jul 1, 2013 | Archived |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 116 pCi/L, federal limit 15 pCi/L (7.7 times the limit)
|
Jul 1, 2013 | Archived |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 118 pCi/L, federal limit 15 pCi/L (7.9 times the limit)
|
Apr 1, 2013 | Archived |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 56 pCi/L, federal limit 5 pCi/L (11 times the limit)
|
Apr 1, 2013 | Archived |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 41 pCi/L, federal limit 5 pCi/L (8.2 times the limit)
|
Jan 1, 2013 | Archived |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 96 pCi/L, federal limit 15 pCi/L (6.4 times the limit)
|
Jan 1, 2013 | Archived |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 96 pCi/L, federal limit 15 pCi/L (6.4 times the limit)
|
Oct 1, 2012 | Archived |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 42 pCi/L, federal limit 5 pCi/L (8.4 times the limit)
|
Oct 1, 2012 | Archived |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 97 pCi/L, federal limit 15 pCi/L (6.5 times the limit)
|
Jul 1, 2012 | Archived |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 40 pCi/L, federal limit 5 pCi/L (8 times the limit)
|
Jul 1, 2012 | Archived |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 39 pCi/L, federal limit 5 pCi/L (7.8 times the limit)
|
Apr 1, 2012 | Archived |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 100 pCi/L, federal limit 15 pCi/L (6.7 times the limit)
|
Apr 1, 2012 | Archived |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 39 pCi/L, federal limit 5 pCi/L (7.8 times the limit)
|
Jan 1, 2012 | Archived |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 99 pCi/L, federal limit 15 pCi/L (6.6 times the limit)
|
Jan 1, 2012 | Archived |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 101 pCi/L, federal limit 15 pCi/L (6.7 times the limit)
|
Oct 1, 2011 | Archived |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 39 pCi/L, federal limit 5 pCi/L (7.8 times the limit)
|
Oct 1, 2011 | Archived |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 88 pCi/L, federal limit 15 pCi/L (5.9 times the limit)
|
Jul 1, 2011 | Archived |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 27 pCi/L, federal limit 5 pCi/L (5.4 times the limit)
|
Jul 1, 2011 | Archived |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 103 pCi/L, federal limit 15 pCi/L (6.9 times the limit)
|
Apr 1, 2011 | Archived |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 43 pCi/L, federal limit 5 pCi/L (8.6 times the limit)
|
Apr 1, 2011 | Archived |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 113 pCi/L, federal limit 15 pCi/L (7.5 times the limit)
|
Jan 1, 2011 | Archived |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 43 pCi/L, federal limit 5 pCi/L (8.6 times the limit)
|
Jan 1, 2011 | Archived |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 45 pCi/L, federal limit 5 pCi/L (9 times the limit)
|
Oct 1, 2010 | Archived |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 110 pCi/L, federal limit 15 pCi/L (7.3 times the limit)
|
Oct 1, 2010 | Archived |
69 older violations are not listed here. EPA ECHO has the complete list.
Enforcement actions
Texas regulators and EPA took 4 formal enforcement actions against Council Creek Village between 1994 and 2016, filed as 6 records in EPA's data. The most recent was a compliance order (no penalty) in September 2016.
| Date | By | Action | Violations covered |
|---|---|---|---|
| Sep 16, 2016 | EPA | Compliance order (no penalty) | 208 violations (186 health-based): Combined Radium (-226 and -228), Public Notice, Gross Alpha, Excl. Radon and U |
| Nov 16, 2011 | EPA | Compliance order (no penalty) | 88 violations (80 health-based): Combined Radium (-226 and -228), Gross Alpha, Excl. Radon and U, Public Notice |
| Apr 10, 2007 | Texas | Signed compliance agreement | 46 violations (46 health-based): Combined Radium (-226 and -228), Gross Alpha, Excl. Radon and U |
| May 6, 1994 | Texas | Signed compliance agreement | 7 violations (7 health-based): Gross Alpha, Excl. Radon and U, Combined Radium (-226 and -228) |
What the violations mean
Gross Alpha, Excl. Radon and U
35 incidentsTest results for Gross Alpha, Excl. Radon and U were above the federal limit (a maximum contaminant level violation).
The utility had to notify customers about each of these violations.
Combined Radium (-226 and -228)
35 incidentsTest results for Combined Radium (-226 and -228) were above the federal limit (a maximum contaminant level violation).
The utility had to notify customers about each of these violations.
Where the water comes from
Council Creek Village draws water from 4 wells (2 of them for emergency, seasonal or other part-time use).
Annual water quality report
Council Creek Village must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.
Systems serving 500 or fewer people may meet the rule by telling customers the report is available on request, so you may need to ask Council Creek Village for a copy.
Find a posted report with EPA's Consumer Confidence Report search
Testing your own water
To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Texas.
Certified drinking water labs by state EPA guidance for private wells