Public water system record

Lajitas on the Rio Grande

Serves an area of Brewster County, TX · 942 people served

Federal records show no health-based violations and 7 monitoring/reporting issues for Lajitas on the Rio Grande in the last ten years.

  • TX0220018
  • DALLAS
  • TX
  • 942 served

System profile

Source water Groundwater
ZIP 75254
EPA system ID TX0220018

Verify this system on EPA ECHO →

Health-based violations, last 10 years
0
Resolved
0
Unresolved
0
Any acute record
No
Monitoring issues, last 10 years
7

Key facts

  • Lajitas on the Rio Grande draws water from 2 wells.
  • Most recent formal enforcement: signed compliance agreement by Texas, June 2010.
  • Record on file since 1984, with 21 health-based violations before October 19, 2016.
  • Lead pipe inventory: 0 lead and 0 unknown out of 76 service lines.

Check whether Lajitas on the Rio Grande serves your address

Address suggestions by Mapbox

Health-based violations

Since October 2016

Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.

None since October 2016.

Monitoring and reporting issues

Since October 2016

Missed tests or reports, not contaminants found above a limit.

Issue Start date Status
Chlorine
Monitoring and reporting
Jul 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
Consumer Confidence Rule
OTHER
Jul 1, 2023 Resolved
Public Notice
OTHER
Apr 1, 2023 Resolved
Consumer Confidence Rule
OTHER
Jul 1, 2022 Resolved
Chlorine
Monitoring and reporting
Oct 1, 2021 Resolved
Revised Total Coliform Rule
Monitoring violation
Feb 1, 2021 Resolved
Public Notice
OTHER
Dec 22, 2009 Resolved

Full record since 1984

EPA's records for Lajitas on the Rio Grande go back to 1984. Before October 19, 2016 they list 21 health-based violations (19 resolved, 2 archived by EPA without a recorded fix) and 21 monitoring or reporting violations.

Violations that began in Health-based Monitoring and reporting
1980s 1 0
1990s 1 2
2000s 14 14
2010 to October 18, 2016 5 5
2020s 0 6

Most recent health-based violation before October 19, 2016: Gross Alpha, Excl. Radon and U, began July 2010, Resolved.

Show all 21 health-based violations before October 19, 2016
Contaminant Start date Status
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 22 pCi/L, federal limit 15 pCi/L (1.5 times the limit)
Jul 1, 2010 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 9 pCi/L, federal limit 5 pCi/L (1.8 times the limit)
Apr 1, 2010 Resolved
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 32 pCi/L, federal limit 15 pCi/L (2.1 times the limit)
Apr 1, 2010 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 11 pCi/L, federal limit 5 pCi/L (2.2 times the limit)
Jan 1, 2010 Resolved
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 36 pCi/L, federal limit 15 pCi/L (2.4 times the limit)
Jan 1, 2010 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 10 pCi/L, federal limit 5 pCi/L (2 times the limit)
Oct 1, 2009 Resolved
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 35 pCi/L, federal limit 15 pCi/L (2.3 times the limit)
Oct 1, 2009 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 10 pCi/L, federal limit 5 pCi/L (2 times the limit)
Jul 1, 2009 Resolved
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 30 pCi/L, federal limit 15 pCi/L (2 times the limit)
Jul 1, 2009 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 10 pCi/L, federal limit 5 pCi/L (2 times the limit)
Apr 1, 2009 Resolved
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 27 pCi/L, federal limit 15 pCi/L (1.8 times the limit)
Apr 1, 2009 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 10 pCi/L, federal limit 5 pCi/L (2 times the limit)
Jan 1, 2009 Resolved
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 27 pCi/L, federal limit 15 pCi/L (1.8 times the limit)
Jan 1, 2009 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 10 pCi/L, federal limit 5 pCi/L (2 times the limit)
Oct 1, 2008 Resolved
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 26 pCi/L, federal limit 15 pCi/L (1.7 times the limit)
Oct 1, 2008 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 10 pCi/L, federal limit 5 pCi/L (2 times the limit)
Jul 1, 2008 Resolved
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 25 pCi/L, federal limit 15 pCi/L (1.7 times the limit)
Jul 1, 2008 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 10 pCi/L, federal limit 5 pCi/L (2 times the limit)
Apr 1, 2008 Resolved
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 24 pCi/L, federal limit 15 pCi/L (1.6 times the limit)
Apr 1, 2008 Resolved
Total Coliform
Contaminant limit exceeded
Oct 1, 1992 Archived
Fluoride
Contaminant limit exceeded
Feb 15, 1984 Archived

Enforcement actions

Texas regulators took 1 formal enforcement action against Lajitas on the Rio Grande in 2010. The most recent was a signed compliance agreement in June 2010.

Date By Action Violations covered
Jun 26, 2010 Texas Signed compliance agreement 16 violations (16 health-based): Gross Alpha, Excl. Radon and U, Combined Radium (-226 and -228)

Where the water comes from

Lajitas on the Rio Grande draws water from 2 wells.

Annual water quality report

Lajitas on the Rio Grande must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.

Where the state allows it, systems serving fewer than 10,000 people may publish the report in a local newspaper or news site instead of mailing it, and must provide a copy on request.

Find a posted report with EPA's Consumer Confidence Report search

Testing your own water

To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Texas.