Public water system record

Bayou Shadows Water System

Serves an area of Brazoria County, TX · 174 people served

Federal records show 3 health-based violations and 33 monitoring/reporting issues for Bayou Shadows Water System in the last ten years. The most serious issue in this window was a resolved LEAD AND COPPER RULE REVISIONS violation.

  • TX0200570
  • ALVIN
  • TX
  • 174 served

System profile

Source water Groundwater
ZIP 77511
EPA system ID TX0200570

Verify this system on EPA ECHO →

Health-based violations, last 10 years
3
Resolved
3
Unresolved
0
Any acute record
No
Monitoring issues, last 10 years
33

Key facts

  • Bayou Shadows Water System draws water from 1 well.
  • Most recent formal enforcement: compliance order with a penalty by Texas, March 2013.
  • Record on file since 2003, with 31 health-based violations before October 19, 2016.
  • Lead pipe inventory: 0 lead and 0 unknown out of 48 service lines.

Check whether Bayou Shadows Water System serves your address

Address suggestions by Mapbox

Health-based violations

Since October 2016

Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.

Contaminant Rule family Start date Status Acute
LEAD AND COPPER RULE REVISIONS
Treatment technique failure
350 Oct 17, 2024 Resolved No
Revised Total Coliform Rule
Treatment technique failure
110 Sep 1, 2021 Resolved No
Revised Total Coliform Rule
Treatment technique failure
110 Sep 1, 2021 Resolved No

Monitoring and reporting issues

Since October 2016

Missed tests or reports, not contaminants found above a limit.

Issue Start date Status
Lead and Copper Rule
Monitoring and reporting
Dec 30, 2025 Active
Public Notice
OTHER
May 1, 2025 Resolved
LEAD AND COPPER RULE REVISIONS
RPT
Oct 17, 2024 Resolved
Lead and Copper Rule
Monitoring and reporting
Apr 1, 2023 Resolved
Public Notice
OTHER
Feb 13, 2023 Resolved
Consumer Confidence Rule
OTHER
Jul 1, 2022 Resolved
Lead and Copper Rule
Monitoring and reporting
Jan 1, 2022 Resolved
Lead and Copper Rule
Monitoring and reporting
Sep 29, 2021 Resolved
Public Notice
OTHER
Aug 23, 2021 Resolved
Public Notice
OTHER
Mar 15, 2021 Resolved
Public Notice
OTHER
Feb 25, 2021 Resolved
Public Notice
OTHER
Jan 16, 2021 Resolved
Lead and Copper Rule
Monitoring and reporting
Jan 1, 2021 Resolved
Chlorine
Monitoring and reporting
Oct 1, 2020 Resolved
Lead and Copper Rule
Monitoring and reporting
Jul 1, 2020 Resolved
Public Notice
OTHER
Mar 9, 2020 Resolved
Lead and Copper Rule
Monitoring and reporting
Jan 1, 2020 Resolved
Public Notice
OTHER
Oct 4, 2019 Resolved
Chlorine
Monitoring and reporting
Oct 1, 2019 Resolved
Lead and Copper Rule
Monitoring and reporting
Sep 29, 2019 Resolved
Chlorine
Monitoring and reporting
Jul 1, 2019 Resolved
Public Notice
OTHER
Apr 10, 2019 Resolved
Lead and Copper Rule
Monitoring and reporting
Jan 1, 2019 Resolved
Chlorine
Monitoring and reporting
Apr 1, 2018 Resolved
Chlorine
Monitoring and reporting
Oct 1, 2017 Resolved
Lead and Copper Rule
Monitoring and reporting
Oct 1, 2017 Resolved
Consumer Confidence Rule
OTHER
Jul 1, 2017 Resolved
Public Notice
OTHER
Feb 3, 2017 Resolved
Lead and Copper Rule
Monitoring and reporting
Oct 1, 2016 Resolved
Public Notice
OTHER
Jul 11, 2016 Resolved
Public Notice
OTHER
Apr 20, 2016 Resolved
Public Notice
OTHER
Feb 8, 2016 Resolved
Lead and Copper Rule
Monitoring and reporting
Oct 1, 2015 Resolved

Full record since 2003

EPA's records for Bayou Shadows Water System go back to 2003. Before October 19, 2016 they list 31 health-based violations (31 resolved) and 39 monitoring or reporting violations.

Violations that began in Health-based Monitoring and reporting
2000s 12 15
2010 to October 18, 2016 19 24
October 19, 2016 to 2019 0 11
2020s 3 17

Most recent health-based violation before October 19, 2016: Arsenic, began July 2014, Resolved.

Show all 31 health-based violations before October 19, 2016
Contaminant Start date Status
Arsenic
Contaminant limit exceeded
Measured 0.017 mg/L, federal limit 0.01 mg/L (1.7 times the limit)
Jul 1, 2014 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.029 mg/L, federal limit 0.01 mg/L (2.9 times the limit)
Apr 1, 2014 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.035 mg/L, federal limit 0.01 mg/L (3.5 times the limit)
Jan 1, 2014 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.04 mg/L, federal limit 0.01 mg/L (4 times the limit)
Oct 1, 2013 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.026 mg/L, federal limit 0.01 mg/L (2.6 times the limit)
Jul 1, 2013 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.013 mg/L, federal limit 0.01 mg/L (1.3 times the limit)
Apr 1, 2013 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.021 mg/L, federal limit 0.01 mg/L (2.1 times the limit)
Jan 1, 2013 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.029 mg/L, federal limit 0.01 mg/L (2.9 times the limit)
Oct 1, 2012 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.041 mg/L, federal limit 0.01 mg/L (4.1 times the limit)
Jul 1, 2012 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.055 mg/L, federal limit 0.01 mg/L (5.5 times the limit)
Apr 1, 2012 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.055 mg/L, federal limit 0.01 mg/L (5.5 times the limit)
Jan 1, 2012 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.054 mg/L, federal limit 0.01 mg/L (5.4 times the limit)
Oct 1, 2011 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.055 mg/L, federal limit 0.01 mg/L (5.5 times the limit)
Jul 1, 2011 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.054 mg/L, federal limit 0.01 mg/L (5.4 times the limit)
Apr 1, 2011 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.054 mg/L, federal limit 0.01 mg/L (5.4 times the limit)
Jan 1, 2011 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.054 mg/L, federal limit 0.01 mg/L (5.4 times the limit)
Oct 1, 2010 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.053625 mg/L, federal limit 0.01 mg/L (5.4 times the limit)
Jul 1, 2010 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.05465 mg/L, federal limit 0.01 mg/L (5.5 times the limit)
Apr 1, 2010 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.0549 mg/L, federal limit 0.01 mg/L (5.5 times the limit)
Jan 1, 2010 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.05565 mg/L, federal limit 0.01 mg/L (5.6 times the limit)
Oct 1, 2009 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.053725 mg/L, federal limit 0.01 mg/L (5.4 times the limit)
Jul 1, 2009 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.05135 mg/L, federal limit 0.01 mg/L (5.1 times the limit)
Apr 1, 2009 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.049525 mg/L, federal limit 0.01 mg/L (5 times the limit)
Jan 1, 2009 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.03595 mg/L, federal limit 0.01 mg/L (3.6 times the limit)
Oct 1, 2008 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.03525 mg/L, federal limit 0.01 mg/L (3.5 times the limit)
Jul 1, 2008 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.036725 mg/L, federal limit 0.01 mg/L (3.7 times the limit)
Apr 1, 2008 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.0479 mg/L, federal limit 0.01 mg/L (4.8 times the limit)
Oct 1, 2007 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.0367 mg/L, federal limit 0.01 mg/L (3.7 times the limit)
Jul 1, 2007 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.023575 mg/L, federal limit 0.01 mg/L (2.4 times the limit)
Apr 1, 2007 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.01115 mg/L, federal limit 0.01 mg/L (1.1 times the limit)
Jan 1, 2007 Resolved
Arsenic
Contaminant limit exceeded
Jan 1, 2006 Resolved

Enforcement actions

Texas regulators and EPA took 3 formal enforcement actions against Bayou Shadows Water System between 2007 and 2013. The most recent was a compliance order with a penalty in March 2013.

Date By Action Violations covered
Mar 21, 2013 Texas Compliance order with a penalty 9 violations: Chlorine
Jul 19, 2011 EPA Compliance order (no penalty) 33 violations (31 health-based): Arsenic
Oct 29, 2007 Texas Signed compliance agreement 16 violations (16 health-based): Arsenic

What the violations mean

Revised Total Coliform Rule

2 incidents

The system did not meet a requirement of the Revised Total Coliform Rule

Coliform and E. coli rules protect against bacteria in the distribution system

LEAD AND COPPER RULE REVISIONS

1 incident

The system did not complete a treatment step or action that the LEAD AND COPPER RULE REVISIONS requires (a treatment technique violation).

The utility had to notify customers about this violation.

Where the water comes from

Bayou Shadows Water System draws water from 1 well.

Annual water quality report

Bayou Shadows Water System must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.

Systems serving 500 or fewer people may meet the rule by telling customers the report is available on request, so you may need to ask Bayou Shadows Water System for a copy.

Find a posted report with EPA's Consumer Confidence Report search

Testing your own water