Public water system record

City of Blanco

Serves Blanco, Blanco County, TX · 3,192 people served

Federal records show 21 health-based violations and 33 monitoring/reporting issues for City of Blanco in the last ten years. The most serious issue in this window was a Total Trihalomethanes (TTHMs) violation that EPA lists as archived, not resolved.

  • TX0160002
  • BLANCO
  • TX
  • 3,192 served

System profile

Source water Surface water
ZIP 78606
EPA system ID TX0160002

Verify this system on EPA ECHO →

Health-based violations, last 10 years
21
Resolved
15
Unresolved
0
Archived by EPA
6
Any acute record
No
Monitoring issues, last 10 years
33

Key facts

  • City of Blanco draws water from 1 surface water intake.
  • Highest measured level in the last 10 years: Total Trihalomethanes (TTHMs), 0.12 mg/L, federal limit 0.08 mg/L (1.5 times the limit), 2020.
  • Most recent formal enforcement: compliance order with a penalty by Texas, April 2020.
  • Record on file since 1993, with 23 health-based violations before October 19, 2016.
  • Lead pipe inventory: 0 lead and 0 unknown out of 1,100 service lines.

Check whether City of Blanco serves your address

Address suggestions by Mapbox

Health-based violations

Since October 2016

Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.

Contaminant Rule family Start date Status Acute
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.101 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
220 Oct 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.097 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
220 Jul 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.085 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
220 Apr 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.085 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
220 Jan 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.085 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
220 Oct 1, 2024 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.083 mg/L, federal limit 0.08 mg/L (at or just above the limit)
220 Jul 1, 2024 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.082 mg/L, federal limit 0.08 mg/L (at or just above the limit)
220 Jul 1, 2022 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.099 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
220 Apr 1, 2021 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.111 mg/L, federal limit 0.08 mg/L (1.4 times the limit)
220 Jan 1, 2021 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.112 mg/L, federal limit 0.08 mg/L (1.4 times the limit)
220 Oct 1, 2020 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.12 mg/L, federal limit 0.08 mg/L (1.5 times the limit)
220 Oct 1, 2020 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.115 mg/L, federal limit 0.08 mg/L (1.4 times the limit)
220 Jul 1, 2020 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.111 mg/L, federal limit 0.08 mg/L (1.4 times the limit)
220 Apr 1, 2020 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.111 mg/L, federal limit 0.08 mg/L (1.4 times the limit)
220 Jan 1, 2020 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.1 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
220 Jan 1, 2020 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.109 mg/L, federal limit 0.08 mg/L (1.4 times the limit)
220 Oct 1, 2019 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.104 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
220 Jul 1, 2019 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.098 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
220 Apr 1, 2019 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.083 mg/L, federal limit 0.08 mg/L (at or just above the limit)
220 Jan 1, 2019 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.081 mg/L, federal limit 0.08 mg/L (at or just above the limit)
220 Apr 1, 2017 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.085 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
220 Jan 1, 2017 Resolved No

Monitoring and reporting issues

Since October 2016

Missed tests or reports, not contaminants found above a limit.

Issue Start date Status
Public Notice
OTHER
Jul 2, 2025 Resolved
Interim Enhanced Surface Water Treatment Rule
Monitoring and reporting
Apr 1, 2025 Resolved
Public Notice
OTHER
Sep 22, 2024 Resolved
Public Notice
OTHER
Mar 9, 2021 Resolved
Public Notice
OTHER
Mar 9, 2021 Resolved
Public Notice
OTHER
Jan 13, 2021 Resolved
Total Trihalomethanes (TTHMs)
Monitoring and reporting
Jun 16, 2020 Resolved
Interim Enhanced Surface Water Treatment Rule
Monitoring and reporting
Jun 1, 2020 Resolved
Public Notice
OTHER
Feb 3, 2020 Resolved
Public Notice
OTHER
Jan 21, 2020 Resolved
Public Notice
OTHER
Sep 24, 2019 Active
Public Notice
OTHER
May 18, 2019 Resolved
Total Trihalomethanes (TTHMs)
Monitoring and reporting
Mar 14, 2019 Resolved
Total Trihalomethanes (TTHMs)
Monitoring and reporting
Jan 1, 2019 Resolved
Public Notice
OTHER
Jul 2, 2018 Resolved
Lead and Copper Rule
Monitoring and reporting
Dec 30, 2017 Resolved
Public Notice
OTHER
Aug 3, 2017 Resolved
Public Notice
OTHER
Jun 23, 2017 Resolved
Public Notice
OTHER
Jun 12, 2017 Resolved
Surface Water Treatment Rule
Monitoring and reporting
May 1, 2017 Resolved
Public Notice
OTHER
Mar 13, 2017 Resolved
Public Notice
OTHER
Jan 23, 2017 Resolved
Interim Enhanced Surface Water Treatment Rule
Monitoring and reporting
Jan 1, 2017 Resolved
Public Notice
OTHER
Dec 14, 2016 Resolved
Public Notice
OTHER
Dec 14, 2016 Resolved
Public Notice
OTHER
Dec 14, 2016 Resolved
Public Notice
OTHER
Dec 14, 2016 Resolved
Public Notice
OTHER
Dec 14, 2016 Resolved
Public Notice
OTHER
Dec 14, 2016 Resolved
Interim Enhanced Surface Water Treatment Rule
Monitoring and reporting
Oct 1, 2016 Resolved
Public Notice
OTHER
Aug 16, 2016 Resolved
Consumer Confidence Rule
OTHER
Jul 1, 2016 Resolved
Public Notice
OTHER
Feb 1, 2012 Resolved

Full record since 1993

EPA's records for City of Blanco go back to 1993. Before October 19, 2016 they list 23 health-based violations (22 resolved, 1 archived by EPA without a recorded fix) and 102 monitoring or reporting violations.

Violations that began in Health-based Monitoring and reporting
1990s 1 0
2000s 14 21
2010 to October 18, 2016 8 81
October 19, 2016 to 2019 6 19
2020s 15 10

Most recent health-based violation before October 19, 2016: Total Trihalomethanes (TTHMs), began July 2016, Resolved.

Show all 23 health-based violations before October 19, 2016
Contaminant Start date Status
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.088 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
Jul 1, 2016 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.087 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
Apr 1, 2016 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.091 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
Jan 1, 2016 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.081 mg/L, federal limit 0.08 mg/L (at or just above the limit)
Jul 1, 2015 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.082 mg/L, federal limit 0.08 mg/L (at or just above the limit)
Oct 1, 2013 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.081 mg/L, federal limit 0.08 mg/L (at or just above the limit)
Jul 1, 2013 Resolved
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
Feb 1, 2012 Resolved
Total Coliform
Contaminant limit exceeded
Dec 1, 2010 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.082 mg/L, federal limit 0.08 mg/L (at or just above the limit)
Jul 1, 2009 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.09 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
Apr 1, 2009 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.09 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
Jan 1, 2009 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.082 mg/L, federal limit 0.08 mg/L (at or just above the limit)
Oct 1, 2008 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.1 mg/L, federal limit 0.06 mg/L (1.7 times the limit)
Jul 1, 2005 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.144 mg/L, federal limit 0.08 mg/L (1.8 times the limit)
Apr 1, 2005 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.126 mg/L, federal limit 0.06 mg/L (2.1 times the limit)
Apr 1, 2005 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.164 mg/L, federal limit 0.08 mg/L (2.1 times the limit)
Jan 1, 2005 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.163 mg/L, federal limit 0.06 mg/L (2.7 times the limit)
Jan 1, 2005 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.179 mg/L, federal limit 0.08 mg/L (2.2 times the limit)
Oct 1, 2004 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.17 mg/L, federal limit 0.06 mg/L (2.8 times the limit)
Oct 1, 2004 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.116 mg/L, federal limit 0.08 mg/L (1.5 times the limit)
Jul 1, 2004 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.114 mg/L, federal limit 0.06 mg/L (1.9 times the limit)
Jul 1, 2004 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.063 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
Apr 1, 2004 Resolved
Surface Water Treatment Rule
Treatment technique failure
Aug 1, 1993 Archived

Enforcement actions

Texas regulators took 4 formal enforcement actions against City of Blanco between 2005 and 2020. The most recent was a compliance order with a penalty in April 2020.

Date By Action Violations covered
Apr 2, 2020 Texas Compliance order with a penalty 17 violations (12 health-based): Total Trihalomethanes (TTHMs), Lead and Copper Rule, Public Notice
Jul 18, 2017 Texas Compliance order with a penalty 8 violations (5 health-based): Total Trihalomethanes (TTHMs), Public Notice
Sep 21, 2009 Texas Compliance order with a penalty 4 violations (4 health-based): Total Trihalomethanes (TTHMs)
Apr 29, 2005 Texas Compliance order with a penalty 10 violations (10 health-based): Total Trihalomethanes (TTHMs), Haloacetic Acids (HAA5)

What the violations mean

Total Trihalomethanes (TTHMs)

21 incidents

Disinfection byproduct levels exceeded the federal limit

Long-term TTHM exposure may increase bladder cancer risk

Where the water comes from

City of Blanco draws water from 1 surface water intake. It also buys water from CLWSC Canyon Lake Shores. 1 smaller public system such as schools, businesses or campgrounds buys water from City of Blanco.

Buys water from

Annual water quality report

City of Blanco must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.

Where the state allows it, systems serving fewer than 10,000 people may publish the report in a local newspaper or news site instead of mailing it, and must provide a copy on request.

Find a posted report with EPA's Consumer Confidence Report search

Testing your own water

To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Texas.