Public water system record
439 WSC
Serves an area of Bell County, TX · 7,836 people served
Federal records show 7 health-based violations and 6 monitoring/reporting issues for 439 WSC in the last ten years. The most serious issue in this window was a resolved Haloacetic Acids (HAA5) violation.
System profile
- Health-based violations, last 10 years
- 7
- Resolved
- 7
- Unresolved
- 0
- Any acute record
- No
- Monitoring issues, last 10 years
- 6
Key facts
- 439 WSC buys its water from Bell County WCID 1.
- Highest measured level in the last 10 years: Haloacetic Acids (HAA5), 0.081 mg/L, federal limit 0.06 mg/L (1.4 times the limit), 2016.
- Most recent formal enforcement: compliance order with a penalty by Texas, February 2018.
- Record on file since 1992, with 3 health-based violations before October 19, 2016.
- Lead pipe inventory: 0 lead and 0 unknown out of 2,585 service lines.
Check whether 439 WSC serves your address
Health-based violations
Since October 2016Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.
| Contaminant | Rule family | Start date | Status | Acute |
|---|---|---|---|---|
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.062 mg/L, federal limit 0.06 mg/L (at or just above the limit)
|
220 | Jul 1, 2017 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.091 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
220 | Apr 1, 2017 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.076 mg/L, federal limit 0.06 mg/L (1.3 times the limit)
|
220 | Apr 1, 2017 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.078 mg/L, federal limit 0.06 mg/L (1.3 times the limit)
|
220 | Jan 1, 2017 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.093 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
220 | Jan 1, 2017 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.096 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
220 | Oct 1, 2016 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.081 mg/L, federal limit 0.06 mg/L (1.4 times the limit)
|
220 | Oct 1, 2016 | Resolved | No |
Monitoring and reporting issues
Since October 2016Missed tests or reports, not contaminants found above a limit.
| Issue | Start date | Status |
|---|---|---|
|
Public Notice
OTHER
|
Nov 1, 2024 | Resolved |
|
Revised Total Coliform Rule
Monitoring violation
|
Oct 1, 2023 | Resolved |
|
Consumer Confidence Rule
OTHER
|
Jul 1, 2020 | Resolved |
|
Lead and Copper Rule
Monitoring and reporting
|
Dec 30, 2019 | Resolved |
|
Chlorine
Monitoring and reporting
|
Jan 1, 2019 | Resolved |
|
Lead and Copper Rule
Monitoring and reporting
|
Dec 30, 2016 | Resolved |
Full record since 1992
EPA's records for 439 WSC go back to 1992. Before October 19, 2016 they list 3 health-based violations (2 resolved, 1 archived by EPA without a recorded fix) and 3 monitoring or reporting violations.
| Violations that began in | Health-based | Monitoring and reporting |
|---|---|---|
| 1990s | 1 | 1 |
| 2010 to October 18, 2016 | 2 | 2 |
| October 19, 2016 to 2019 | 5 | 3 |
| 2020s | 0 | 3 |
Most recent health-based violation before October 19, 2016: Total Trihalomethanes (TTHMs), began October 2016, Resolved.
Show all 3 health-based violations before October 19, 2016
| Contaminant | Start date | Status |
|---|---|---|
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.096 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
Oct 1, 2016 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.081 mg/L, federal limit 0.06 mg/L (1.4 times the limit)
|
Oct 1, 2016 | Resolved |
|
Total Coliform
Contaminant limit exceeded
|
Jul 1, 1992 | Archived |
Enforcement actions
Texas regulators took 1 formal enforcement action against 439 WSC in 2018. The most recent was a compliance order with a penalty in February 2018.
| Date | By | Action | Violations covered |
|---|---|---|---|
| Feb 14, 2018 | Texas | Compliance order with a penalty | 7 violations (7 health-based): Haloacetic Acids (HAA5), Total Trihalomethanes (TTHMs) |
What the violations mean
Haloacetic Acids (HAA5)
4 incidentsHaloacetic acid byproducts exceeded the federal limit
Long-term exposure to HAAs may increase cancer risk
Total Trihalomethanes (TTHMs)
3 incidentsDisinfection byproduct levels exceeded the federal limit
Long-term TTHM exposure may increase bladder cancer risk
Where the water comes from
439 WSC buys its water from Bell County WCID 1. It lists no wells or intakes of its own.
Buys water from
- Bell County WCID 1 Killeen, TX
Annual water quality report
439 WSC must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.
Where the state allows it, systems serving fewer than 10,000 people may publish the report in a local newspaper or news site instead of mailing it, and must provide a copy on request.
Find a posted report with EPA's Consumer Confidence Report search
Testing your own water
To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Texas.
Certified drinking water labs by state EPA guidance for private wells