Public water system record
City of Beeville
Serves Beeville, Bee County, TX · 13,664 people served
Federal records show 19 health-based violations and 32 monitoring/reporting issues for City of Beeville in the last ten years. The most serious issue in this window was a resolved Total Trihalomethanes (TTHMs) violation.
System profile
- Health-based violations, last 10 years
- 19
- Resolved
- 19
- Unresolved
- 0
- Any acute record
- Yes
- Monitoring issues, last 10 years
- 32
Key facts
- City of Beeville draws water from 5 wells and 1 surface water intake.
- Highest measured level in the last 10 years: Haloacetic Acids (HAA5), 0.11 mg/L, federal limit 0.06 mg/L (1.8 times the limit), 2018.
- Most recent formal enforcement: compliance order with a penalty by Texas, August 2022.
- Record on file since 1993, with 26 health-based violations before October 19, 2016.
- Lead pipe inventory: 0 lead and 0 unknown out of 5,510 service lines.
Check whether City of Beeville serves your address
Health-based violations
Since October 2016Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.
| Contaminant | Rule family | Start date | Status | Acute |
|---|---|---|---|---|
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.082 mg/L, federal limit 0.08 mg/L (at or just above the limit)
|
220 | Oct 1, 2024 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.084 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
220 | Jul 1, 2024 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.099 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
220 | Apr 1, 2024 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.114 mg/L, federal limit 0.08 mg/L (1.4 times the limit)
|
220 | Jan 1, 2024 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.104 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
|
220 | Oct 1, 2023 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.087 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
220 | Jul 1, 2023 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.081 mg/L, federal limit 0.08 mg/L (at or just above the limit)
|
220 | Jul 1, 2022 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.081 mg/L, federal limit 0.08 mg/L (at or just above the limit)
|
220 | Apr 1, 2022 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.082 mg/L, federal limit 0.08 mg/L (at or just above the limit)
|
220 | Oct 1, 2021 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.083 mg/L, federal limit 0.08 mg/L (at or just above the limit)
|
220 | Apr 1, 2021 | Resolved | No |
|
Revised Total Coliform Rule
Contaminant limit exceeded
|
110 | Jul 1, 2019 | Resolved | Yes |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.086 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
220 | Jul 1, 2018 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.11 mg/L, federal limit 0.06 mg/L (1.8 times the limit)
|
220 | Jul 1, 2018 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.099 mg/L, federal limit 0.06 mg/L (1.7 times the limit)
|
220 | Apr 1, 2018 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.099 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
220 | Apr 1, 2018 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.1 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
|
220 | Jan 1, 2018 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.1 mg/L, federal limit 0.06 mg/L (1.7 times the limit)
|
220 | Jan 1, 2018 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.094 mg/L, federal limit 0.06 mg/L (1.6 times the limit)
|
220 | Oct 1, 2017 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.094 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
220 | Oct 1, 2017 | Resolved | No |
Monitoring and reporting issues
Since October 2016Missed tests or reports, not contaminants found above a limit.
| Issue | Start date | Status |
|---|---|---|
|
Public Notice
OTHER
|
Oct 26, 2025 | Active |
|
Public Notice
OTHER
|
Aug 3, 2025 | Resolved |
|
Lead and Copper Rule
Monitoring and reporting
|
Oct 1, 2024 | Resolved |
|
Revised Total Coliform Rule
Monitoring violation
|
Jun 1, 2024 | Resolved |
|
Public Notice
OTHER
|
Aug 10, 2023 | Resolved |
|
Total Trihalomethanes (TTHMs)
Monitoring and reporting
|
Jul 12, 2022 | Resolved |
|
Public Notice
OTHER
|
Sep 19, 2019 | Resolved |
|
Public Notice
OTHER
|
Sep 19, 2019 | Resolved |
|
Public Notice
OTHER
|
Sep 1, 2019 | Resolved |
|
Lead and Copper Rule
Monitoring and reporting
|
Apr 1, 2019 | Resolved |
|
Public Notice
OTHER
|
Mar 10, 2019 | Resolved |
|
Public Notice
OTHER
|
Mar 10, 2019 | Resolved |
|
Public Notice
OTHER
|
Jan 29, 2019 | Resolved |
|
Public Notice
OTHER
|
Jan 29, 2019 |
Active
Enforcement action in place
|
|
Haloacetic Acids (HAA5)
Monitoring and reporting
|
Jan 8, 2019 | Resolved |
|
Public Notice
OTHER
|
Oct 9, 2018 |
Active
Enforcement action in place
|
|
Public Notice
OTHER
|
Oct 9, 2018 | Active |
|
Revised Total Coliform Rule
Monitoring violation
|
Aug 1, 2018 | Resolved |
|
Lead and Copper Rule
Monitoring and reporting
|
Jul 1, 2018 | Resolved |
|
Lead and Copper Rule
Monitoring and reporting
|
Jul 1, 2018 | Resolved |
|
Lead and Copper Rule
Monitoring and reporting
|
Jul 1, 2018 | Resolved |
|
Chlorite
Monitoring and reporting
|
Jun 1, 2018 | Resolved |
|
Public Notice
OTHER
|
May 22, 2018 |
Active
Enforcement action in place
|
|
Public Notice
OTHER
|
May 22, 2018 | Resolved |
|
Chlorite
Monitoring and reporting
|
May 1, 2018 | Resolved |
|
Lead and Copper Rule
Monitoring and reporting
|
Apr 1, 2018 | Resolved |
|
Lead and Copper Rule
Monitoring and reporting
|
Jan 1, 2018 | Resolved |
|
Surface Water Treatment Rule
Monitoring and reporting
|
Aug 1, 2017 | Resolved |
|
Chlorite
Monitoring and reporting
|
Aug 1, 2017 | Resolved |
|
Lead and Copper Rule
Monitoring and reporting
|
Jul 1, 2017 | Resolved |
|
Lead and Copper Rule
Monitoring and reporting
|
Jul 1, 2017 | Resolved |
|
Public Notice
OTHER
|
Jan 10, 2016 | Resolved |
Full record since 1993
EPA's records for City of Beeville go back to 1993. Before October 19, 2016 they list 26 health-based violations (26 resolved) and 64 monitoring or reporting violations.
| Violations that began in | Health-based | Monitoring and reporting |
|---|---|---|
| 1990s | 0 | 2 |
| 2000s | 8 | 40 |
| 2010 to October 18, 2016 | 18 | 22 |
| October 19, 2016 to 2019 | 9 | 25 |
| 2020s | 10 | 6 |
Most recent health-based violation before October 19, 2016: Total Coliform, began September 2015, Resolved.
Show all 26 health-based violations before October 19, 2016
| Contaminant | Start date | Status |
|---|---|---|
|
Total Coliform
Contaminant limit exceeded
|
Sep 1, 2015 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.084 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Apr 1, 2015 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.099 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
Jan 1, 2015 | Resolved |
|
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
|
Nov 1, 2014 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.09 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Oct 1, 2014 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.082 mg/L, federal limit 0.08 mg/L (at or just above the limit)
|
Jul 1, 2014 | Resolved |
|
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
|
Apr 1, 2014 | Resolved |
|
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
|
Dec 1, 2013 | Resolved |
|
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
|
Dec 1, 2013 | Resolved |
|
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
|
Nov 1, 2013 | Resolved |
|
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
|
Nov 1, 2013 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.088 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Jul 1, 2013 | Resolved |
|
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
|
Jul 1, 2013 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.089 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Oct 1, 2010 | Resolved |
|
Total Coliform
Contaminant limit exceeded
|
Jul 1, 2010 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.085 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Jul 1, 2010 | Resolved |
|
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
|
Jan 1, 2010 | Resolved |
|
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
|
Jan 1, 2010 | Resolved |
|
Total Coliform
Contaminant limit exceeded
|
Jun 1, 2009 | Resolved |
|
Total Coliform
Contaminant limit exceeded
|
Nov 1, 2007 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.062 mg/L, federal limit 0.06 mg/L (at or just above the limit)
|
Jul 1, 2006 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.061 mg/L, federal limit 0.06 mg/L (at or just above the limit)
|
Jan 1, 2005 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.062 mg/L, federal limit 0.06 mg/L (at or just above the limit)
|
Oct 1, 2004 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.069 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
|
Jul 1, 2004 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.067 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
|
Apr 1, 2004 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.062 mg/L, federal limit 0.06 mg/L (at or just above the limit)
|
Oct 1, 2002 | Resolved |
Enforcement actions
Texas regulators took 4 formal enforcement actions against City of Beeville between 2004 and 2022. The most recent was a compliance order with a penalty in August 2022.
| Date | By | Action | Violations covered |
|---|---|---|---|
| Aug 15, 2022 | Texas | Compliance order with a penalty | 8 violations: Lead and Copper Rule, Public Notice |
| Jul 9, 2019 | Texas | Compliance order with a penalty | 13 violations (8 health-based): Lead and Copper Rule, Haloacetic Acids (HAA5), Total Trihalomethanes (TTHMs) |
| Dec 19, 2014 | Texas | Compliance order with a penalty | 19 violations (11 health-based): Total Trihalomethanes (TTHMs), Public Notice, Interim Enhanced Surface Water Treatment Rule |
| Mar 14, 2004 | Texas | Compliance order with a penalty | 5 violations (5 health-based): Haloacetic Acids (HAA5) |
What the violations mean
Total Trihalomethanes (TTHMs)
14 incidentsDisinfection byproduct levels exceeded the federal limit
Long-term TTHM exposure may increase bladder cancer risk
Haloacetic Acids (HAA5)
4 incidentsHaloacetic acid byproducts exceeded the federal limit
Long-term exposure to HAAs may increase cancer risk
Revised Total Coliform Rule
1 incidentThe system did not meet a requirement of the Revised Total Coliform Rule
Coliform and E. coli rules protect against bacteria in the distribution system
Where the water comes from
City of Beeville draws water from 5 wells and 1 surface water intake.
Annual water quality report
City of Beeville must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.
Systems serving 10,000 or more people must mail or deliver the report to every customer, and from 2027 they must send it twice a year.
Find a posted report with EPA's Consumer Confidence Report search
Testing your own water
To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Texas.
Certified drinking water labs by state EPA guidance for private wells