Public water system record

Town of Perry

Serves an area of Aiken County, SC that includes Perry · 796 people served

Federal records show no health-based violations and no monitoring or reporting issues for Town of Perry in the last ten years.

  • SC0210006
  • PERRY
  • SC
  • 796 served

System profile

Source water Groundwater
ZIP 29137
EPA system ID SC0210006

Verify this system on EPA ECHO →

Health-based violations, last 10 years
0
Resolved
0
Unresolved
0
Any acute record
No
Monitoring issues, last 10 years
0

Key facts

  • Town of Perry draws water from 2 wells.
  • Most recent formal enforcement: signed compliance agreement by South Carolina, October 2003.
  • Record on file since 1997, with 27 health-based violations before October 19, 2016.
  • Lead pipe inventory: 0 lead and 15 unknown out of 34 service lines.

Check whether Town of Perry serves your address

Address suggestions by Mapbox

Health-based violations

Since October 2016

Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.

None since October 2016, and no monitoring or reporting violations either.

Full record since 1997

EPA's records for Town of Perry go back to 1997. Before October 19, 2016 they list 27 health-based violations (26 resolved, 1 archived by EPA without a recorded fix) and 5 monitoring or reporting violations.

Violations that began in Health-based Monitoring and reporting
1990s 1 0
2000s 26 4
2010 to October 18, 2016 0 1

Most recent health-based violation before October 19, 2016: Combined Radium (-226 and -228), began October 2004, Resolved.

Show all 27 health-based violations before October 19, 2016
Contaminant Start date Status
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 8 pCi/L, federal limit 5 pCi/L (1.6 times the limit)
Oct 1, 2004 Resolved
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 36 pCi/L, federal limit 15 pCi/L (2.4 times the limit)
Jul 1, 2004 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 8 pCi/L, federal limit 5 pCi/L (1.6 times the limit)
Jul 1, 2004 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 10 pCi/L, federal limit 5 pCi/L (2 times the limit)
Jul 1, 2004 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 29 pCi/L, federal limit 5 pCi/L (5.8 times the limit)
Jul 1, 2004 Resolved
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 37 pCi/L, federal limit 15 pCi/L (2.5 times the limit)
Apr 1, 2004 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 7 pCi/L, federal limit 5 pCi/L (1.4 times the limit)
Apr 1, 2004 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 10 pCi/L, federal limit 5 pCi/L (2 times the limit)
Apr 1, 2004 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 26 pCi/L, federal limit 5 pCi/L (5.2 times the limit)
Apr 1, 2004 Resolved
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 44 pCi/L, federal limit 15 pCi/L (2.9 times the limit)
Jan 1, 2004 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 7.2 pCi/L, federal limit 5 pCi/L (1.4 times the limit)
Jan 1, 2004 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 9.4 pCi/L, federal limit 5 pCi/L (1.9 times the limit)
Jan 1, 2004 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 24.38 pCi/L, federal limit 5 pCi/L (4.9 times the limit)
Jan 1, 2004 Resolved
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 21.98 pCi/L, federal limit 15 pCi/L (1.5 times the limit)
Jul 1, 2003 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 11.489 pCi/L, federal limit 5 pCi/L (2.3 times the limit)
Jul 1, 2003 Resolved
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 18.321 pCi/L, federal limit 15 pCi/L (1.2 times the limit)
Apr 1, 2003 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 13.416 pCi/L, federal limit 5 pCi/L (2.7 times the limit)
Apr 1, 2003 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 12.305 pCi/L, federal limit 5 pCi/L (2.5 times the limit)
Jan 1, 2003 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 13.62 pCi/L, federal limit 5 pCi/L (2.7 times the limit)
Oct 1, 2002 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 12.75 pCi/L, federal limit 5 pCi/L (2.6 times the limit)
Jul 1, 2002 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 12.99 pCi/L, federal limit 5 pCi/L (2.6 times the limit)
Apr 1, 2002 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 11.81 pCi/L, federal limit 5 pCi/L (2.4 times the limit)
Jan 1, 2002 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 14.66 pCi/L, federal limit 5 pCi/L (2.9 times the limit)
Oct 1, 2001 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 16.84 pCi/L, federal limit 5 pCi/L (3.4 times the limit)
Oct 1, 2001 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 7.75 pCi/L, federal limit 5 pCi/L (1.6 times the limit)
Oct 1, 2001 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 11.519 pCi/L, federal limit 5 pCi/L (2.3 times the limit)
Jul 1, 2001 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Oct 1, 1997 Archived

Enforcement actions

South Carolina regulators took 2 formal enforcement actions against Town of Perry between 2001 and 2003, filed as 5 records in EPA's data. The most recent was a signed compliance agreement in October 2003.

Date By Action Violations covered
Oct 1, 2003 South Carolina Signed compliance agreement 2 violations (2 health-based): Combined Radium (-226 and -228), Gross Alpha, Excl. Radon and U
Jul 11, 2001 South Carolina Signed compliance agreement 13 violations (13 health-based): Combined Radium (-226 and -228)

Where the water comes from

Town of Perry draws water from 2 wells.

Annual water quality report

Town of Perry must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.

Where the state allows it, systems serving fewer than 10,000 people may publish the report in a local newspaper or news site instead of mailing it, and must provide a copy on request.

Find a posted report with EPA's Consumer Confidence Report search

Testing your own water

To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by South Carolina.