Public water system record

Cabo Rojo

Serves an area of Cabo Rojo Municipio, PR that includes Cabo Rojo, Boquerón, Puerto Real and 4 more places · 20,749 people served

Federal records show 10 health-based violations and 26 monitoring/reporting issues for Cabo Rojo in the last ten years. The most serious issue in this window was a resolved Interim Enhanced Surface Water Treatment Rule violation.

  • PR0003373
  • CABO ROJO
  • PR
  • 20,749 served

System profile

Source water Surface water
ZIP 00623
EPA system ID PR0003373

Verify this system on EPA ECHO →

Health-based violations, last 10 years
10
Resolved
10
Unresolved
0
Any acute record
Yes
Monitoring issues, last 10 years
26

Key facts

  • Cabo Rojo draws water from 2 surface water intakes.
  • Highest measured level in the last 10 years: Total Trihalomethanes (TTHMs), 0.104 mg/L, federal limit 0.08 mg/L (1.3 times the limit), 2017.
  • Most recent formal enforcement: civil case filed in court by Puerto Rico, February 2022.
  • Record on file since 1980, with 56 health-based violations before October 19, 2016.
  • Lead pipe inventory: 0 lead and 1,733 unknown out of 8,697 service lines.

Check whether Cabo Rojo serves your address

Address suggestions by Mapbox

Health-based violations

Since October 2016

Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.

Contaminant Rule family Start date Status Acute
Interim Enhanced Surface Water Treatment Rule
Treatment technique failure
120 Dec 1, 2021 Resolved Yes
Interim Enhanced Surface Water Treatment Rule
Treatment technique failure
120 Dec 1, 2021 Resolved Yes
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.089 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
220 Oct 1, 2021 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.093 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
220 Apr 1, 2021 Resolved No
Long Term 2 Enhanced Surface Water Treatment Rule
Treatment technique failure
120 May 16, 2018 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.086 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
220 Apr 1, 2018 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.087 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
220 Jan 1, 2018 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.104 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
220 Jan 1, 2017 Resolved No
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.068 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
220 Oct 1, 2016 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.092 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
220 Oct 1, 2016 Resolved No

Monitoring and reporting issues

Since October 2016

Missed tests or reports, not contaminants found above a limit.

Issue Start date Status
Consumer Confidence Rule
OTHER
Jul 1, 2020 Resolved
Consumer Confidence Rule
OTHER
Oct 1, 2018 Resolved
E. coli
Monitoring and reporting
Jul 1, 2017 Resolved
Cryptosporidium
Monitoring and reporting
Jul 1, 2017 Resolved
Turbidity
Monitoring and reporting
Jul 1, 2017 Resolved
E. coli
Monitoring and reporting
Jul 1, 2017 Resolved
Cryptosporidium
Monitoring and reporting
Jul 1, 2017 Resolved
Turbidity
Monitoring and reporting
Jul 1, 2017 Resolved
E. coli
Monitoring and reporting
May 1, 2017 Resolved
Cryptosporidium
Monitoring and reporting
May 1, 2017 Resolved
Turbidity
Monitoring and reporting
May 1, 2017 Resolved
E. coli
Monitoring and reporting
Feb 1, 2017 Resolved
Cryptosporidium
Monitoring and reporting
Feb 1, 2017 Resolved
Turbidity
Monitoring and reporting
Feb 1, 2017 Resolved
E. coli
Monitoring and reporting
Jan 1, 2017 Resolved
Cryptosporidium
Monitoring and reporting
Jan 1, 2017 Resolved
Turbidity
Monitoring and reporting
Jan 1, 2017 Resolved
E. coli
Monitoring and reporting
Dec 1, 2016 Resolved
Cryptosporidium
Monitoring and reporting
Dec 1, 2016 Resolved
Turbidity
Monitoring and reporting
Dec 1, 2016 Resolved
E. coli
Monitoring and reporting
Oct 1, 2016 Resolved
Cryptosporidium
Monitoring and reporting
Oct 1, 2016 Resolved
Turbidity
Monitoring and reporting
Oct 1, 2016 Resolved
Lead and Copper Rule
Monitoring and reporting
Jan 1, 2015 Resolved
Lead and Copper Rule
Monitoring and reporting
Jul 1, 2011 Resolved
Lead and Copper Rule
Monitoring and reporting
Jan 1, 2009 Resolved

Full record since 1980

EPA's records for Cabo Rojo go back to 1980. Before October 19, 2016 they list 56 health-based violations (35 resolved, 21 archived by EPA without a recorded fix) and 179 monitoring or reporting violations.

Violations that began in Health-based Monitoring and reporting
1980s 0 2
1990s 6 76
2000s 17 79
2010 to October 18, 2016 33 22
October 19, 2016 to 2019 4 19
2020s 4 1

Most recent health-based violation before October 19, 2016: Haloacetic Acids (HAA5), began October 2016, Resolved.

Show all 56 health-based violations before October 19, 2016
Contaminant Start date Status
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.068 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
Oct 1, 2016 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.092 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
Oct 1, 2016 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.095 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
Jul 1, 2016 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.102 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
Apr 1, 2016 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.101 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
Jan 1, 2016 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.103 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
Oct 1, 2015 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.108 mg/L, federal limit 0.08 mg/L (1.4 times the limit)
Jul 1, 2015 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.091 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
Apr 1, 2015 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.081 mg/L, federal limit 0.08 mg/L (at or just above the limit)
Jan 1, 2015 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.085 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
Oct 1, 2014 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.083 mg/L, federal limit 0.08 mg/L (at or just above the limit)
Jul 1, 2014 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.088 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
Apr 1, 2014 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.091 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
Jan 1, 2014 Resolved
CARBON, TOTAL
Treatment technique failure
Oct 1, 2013 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.096 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
Oct 1, 2013 Archived
CARBON, TOTAL
Treatment technique failure
Jul 1, 2013 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.1 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
Jul 1, 2013 Archived
CARBON, TOTAL
Treatment technique failure
Apr 1, 2013 Resolved
CARBON, TOTAL
Treatment technique failure
Jan 1, 2013 Resolved
CARBON, TOTAL
Treatment technique failure
Jan 1, 2012 Resolved
CARBON, TOTAL
Treatment technique failure
Oct 1, 2011 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.065 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
Jul 1, 2011 Resolved
CARBON, TOTAL
Treatment technique failure
Jul 1, 2011 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.074 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
Apr 1, 2011 Resolved
CARBON, TOTAL
Treatment technique failure
Apr 1, 2011 Resolved
CARBON, TOTAL
Treatment technique failure
Jan 1, 2011 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.07 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
Jan 1, 2011 Resolved
CARBON, TOTAL
Treatment technique failure
Oct 1, 2010 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.065 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
Oct 1, 2010 Resolved
CARBON, TOTAL
Treatment technique failure
Jul 1, 2010 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.066 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
Jul 1, 2010 Resolved
CARBON, TOTAL
Treatment technique failure
Apr 1, 2010 Resolved
CARBON, TOTAL
Treatment technique failure
Jan 1, 2010 Resolved
CARBON, TOTAL
Treatment technique failure
Oct 1, 2009 Resolved
CARBON, TOTAL
Treatment technique failure
Apr 1, 2009 Resolved
CARBON, TOTAL
Treatment technique failure
Jan 1, 2009 Resolved
Total Coliform (acute)
Contaminant limit exceeded
Jun 1, 2006 Resolved
Total Coliform
Contaminant limit exceeded
May 1, 2005 Archived
Total Coliform
Contaminant limit exceeded
Oct 1, 2004 Archived
CARBON, TOTAL
Treatment technique failure
Jul 1, 2004 Archived
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
May 1, 2004 Archived
CARBON, TOTAL
Treatment technique failure
Apr 1, 2004 Archived
CARBON, TOTAL
Treatment technique failure
Jan 1, 2004 Archived
CARBON, TOTAL
Treatment technique failure
Oct 1, 2003 Archived
CARBON, TOTAL
Treatment technique failure
Jul 1, 2003 Archived
CARBON, TOTAL
Treatment technique failure
Apr 1, 2003 Archived
Total Coliform
Contaminant limit exceeded
Jul 1, 2002 Archived
Total Coliform
Contaminant limit exceeded
May 1, 2002 Archived
Total Coliform (acute)
Contaminant limit exceeded
May 1, 2002 Archived
Surface Water Treatment Rule
Treatment technique failure
Aug 1, 2001 Archived

6 older violations are not listed here. EPA ECHO has the complete list.

Enforcement actions

Puerto Rico regulators took 10 formal enforcement actions against Cabo Rojo between 2007 and 2022, filed as 13 records in EPA's data. The most recent was a civil case filed in court in February 2022.

Date By Action Violations covered
Feb 8, 2022 Puerto Rico Civil case filed in court 1 violation (1 health-based): Total Trihalomethanes (TTHMs)
Jul 20, 2021 Puerto Rico Civil case filed in court 1 violation (1 health-based): Total Trihalomethanes (TTHMs)
Jan 27, 2017 Puerto Rico Civil case filed in court 1 violation (1 health-based): Haloacetic Acids (HAA5)
Oct 27, 2014 Puerto Rico Civil case filed in court 8 violations (8 health-based): Total Trihalomethanes (TTHMs)
Oct 22, 2013 Puerto Rico Civil case filed in court 11 violations (11 health-based): Total Trihalomethanes (TTHMs)
Oct 21, 2013 Puerto Rico Civil case filed in court 4 violations (4 health-based): CARBON, TOTAL
Aug 16, 2011 Puerto Rico Civil case filed in court 2 violations (2 health-based): Haloacetic Acids (HAA5)
Jun 30, 2011 Puerto Rico Civil case filed in court 3 violations (3 health-based): Haloacetic Acids (HAA5)
Jun 24, 2008 Puerto Rico Civil case filed in court 11 violations (11 health-based): CARBON, TOTAL
Feb 5, 2007 Puerto Rico Compliance order (no penalty) 12 violations (12 health-based): CARBON, TOTAL

What the violations mean

Total Trihalomethanes (TTHMs)

6 incidents

Disinfection byproduct levels exceeded the federal limit

Long-term TTHM exposure may increase bladder cancer risk

Interim Enhanced Surface Water Treatment Rule

2 incidents

The system did not meet a filtration or treatment requirement for surface water

Inadequate treatment of surface water can let pathogens such as Cryptosporidium and Giardia through

Long Term 2 Enhanced Surface Water Treatment Rule

1 incident

The system failed required surface water treatment or filtration standards

Untreated or inadequately treated surface water can contain bacteria and viruses

Haloacetic Acids (HAA5)

1 incident

Haloacetic acid byproducts exceeded the federal limit

Long-term exposure to HAAs may increase cancer risk

Where the water comes from

Cabo Rojo draws water from 2 surface water intakes.

Annual water quality report

Cabo Rojo must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.

Systems serving 10,000 or more people must mail or deliver the report to every customer, and from 2027 they must send it twice a year.

Find a posted report with EPA's Consumer Confidence Report search

Testing your own water

To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Puerto Rico.