Public water system record

Pittsburg Co. PWA (Crowder)

Serves an area of Pittsburg County, OK that includes Crowder and Canadian · 2,203 people served

Federal records show 5 health-based violations and 8 monitoring/reporting issues for Pittsburg Co. PWA (Crowder) in the last ten years. The most serious issue in this window was a CARBON, TOTAL violation that EPA lists as archived, not resolved.

  • OK1020603
  • CROWDER
  • OK
  • 2,203 served

System profile

Source water Surface water
ZIP 74430
EPA system ID OK1020603

Verify this system on EPA ECHO →

Health-based violations, last 10 years
5
Resolved
4
Unresolved
0
Archived by EPA
1
Any acute record
No
Monitoring issues, last 10 years
8

Key facts

  • Pittsburg Co. PWA (Crowder) draws water from 1 surface water intake.
  • Highest measured level in the last 10 years: Total Trihalomethanes (TTHMs), 0.083 mg/L, federal limit 0.08 mg/L (at or just above the limit), 2022.
  • Most recent formal enforcement: compliance order (no penalty) by Oklahoma, November 2022.
  • Record on file since 1993, with 86 health-based violations before October 20, 2016.
  • Lead pipe inventory: 0 lead and 86 unknown out of 873 service lines.

Check whether Pittsburg Co. PWA (Crowder) serves your address

Address suggestions by Mapbox

Health-based violations

Since October 2016

Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.

Contaminant Rule family Start date Status Acute
CARBON, TOTAL
Treatment technique failure
210 Oct 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
LEAD AND COPPER RULE REVISIONS
Treatment technique failure
350 Oct 17, 2024 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.081 mg/L, federal limit 0.08 mg/L (at or just above the limit)
220 Jul 1, 2022 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.082 mg/L, federal limit 0.08 mg/L (at or just above the limit)
220 Apr 1, 2022 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.083 mg/L, federal limit 0.08 mg/L (at or just above the limit)
220 Apr 1, 2022 Resolved No

Monitoring and reporting issues

Since October 2016

Missed tests or reports, not contaminants found above a limit.

Issue Start date Status
Interim Enhanced Surface Water Treatment Rule
Monitoring and reporting
Jun 1, 2025 Resolved
LEAD AND COPPER RULE REVISIONS
RPT
Oct 17, 2024 Resolved
Total Trihalomethanes (TTHMs)
Monitoring and reporting
Apr 1, 2022 Resolved
Interim Enhanced Surface Water Treatment Rule
Monitoring and reporting
May 1, 2020 Resolved
Gross Beta Particle Activity
Monitoring and reporting
Jan 1, 2017 Resolved
Combined Radium (-226 and -228)
Monitoring and reporting
Jan 1, 2017 Resolved
Combined Uranium
Monitoring and reporting
Jan 1, 2017 Resolved
Gross Alpha, Excl. Radon and U
Monitoring and reporting
Jan 1, 2017 Resolved

Full record since 1993

EPA's records for Pittsburg Co. PWA (Crowder) go back to 1993. Before October 20, 2016 they list 86 health-based violations (81 resolved, 5 archived by EPA without a recorded fix) and 35 monitoring or reporting violations.

Violations that began in Health-based Monitoring and reporting
1990s 12 3
2000s 56 23
2010 to October 19, 2016 18 9
October 20, 2016 to 2019 0 4
2020s 5 4

Most recent health-based violation before October 20, 2016: Interim Enhanced Surface Water Treatment Rule (acute), began June 2015, Resolved.

Show all 86 health-based violations before October 20, 2016
Contaminant Start date Status
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
Jun 1, 2015 Resolved
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
Jun 1, 2015 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.083 mg/L, federal limit 0.08 mg/L (at or just above the limit)
Jul 1, 2013 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.088 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
Jan 1, 2013 Resolved
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
Jan 1, 2013 Resolved
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
Dec 1, 2012 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.09 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
Oct 1, 2012 Resolved
CARBON, TOTAL
Treatment technique failure
Oct 1, 2011 Resolved
CARBON, TOTAL
Treatment technique failure
Jul 1, 2011 Resolved
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
Apr 1, 2011 Resolved
CARBON, TOTAL
Treatment technique failure
Apr 1, 2011 Resolved
CARBON, TOTAL
Treatment technique failure
Jan 1, 2011 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.063 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
Jan 1, 2011 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.066 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
Oct 1, 2010 Resolved
CARBON, TOTAL
Treatment technique failure
Jul 1, 2010 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.074 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
Jul 1, 2010 Resolved
CARBON, TOTAL
Treatment technique failure
Apr 1, 2010 Resolved
CARBON, TOTAL
Treatment technique failure
Jan 1, 2010 Resolved
CARBON, TOTAL
Treatment technique failure
Oct 1, 2009 Resolved
CARBON, TOTAL
Treatment technique failure
Apr 1, 2009 Resolved
CARBON, TOTAL
Treatment technique failure
Jan 1, 2009 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.084 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
Oct 1, 2008 Resolved
CARBON, TOTAL
Treatment technique failure
Oct 1, 2008 Resolved
CARBON, TOTAL
Treatment technique failure
Jul 1, 2008 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.065 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
Jul 1, 2008 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.123 mg/L, federal limit 0.08 mg/L (1.5 times the limit)
Jul 1, 2008 Resolved
CARBON, TOTAL
Treatment technique failure
Apr 1, 2008 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.062 mg/L, federal limit 0.06 mg/L (at or just above the limit)
Apr 1, 2008 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.135 mg/L, federal limit 0.08 mg/L (1.7 times the limit)
Apr 1, 2008 Resolved
CARBON, TOTAL
Treatment technique failure
Jan 1, 2008 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.131 mg/L, federal limit 0.08 mg/L (1.6 times the limit)
Jan 1, 2008 Resolved
CARBON, TOTAL
Treatment technique failure
Oct 1, 2007 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.138 mg/L, federal limit 0.08 mg/L (1.7 times the limit)
Oct 1, 2007 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.136 mg/L, federal limit 0.08 mg/L (1.7 times the limit)
Jul 1, 2007 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.061 mg/L, federal limit 0.06 mg/L (at or just above the limit)
Jul 1, 2007 Resolved
CARBON, TOTAL
Treatment technique failure
Apr 1, 2007 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.166 mg/L, federal limit 0.08 mg/L (2.1 times the limit)
Apr 1, 2007 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.061 mg/L, federal limit 0.06 mg/L (at or just above the limit)
Apr 1, 2007 Resolved
CARBON, TOTAL
Treatment technique failure
Jan 1, 2007 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.165 mg/L, federal limit 0.08 mg/L (2.1 times the limit)
Jan 1, 2007 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.081 mg/L, federal limit 0.06 mg/L (1.4 times the limit)
Jan 1, 2007 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.079 mg/L, federal limit 0.06 mg/L (1.3 times the limit)
Oct 1, 2006 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.171 mg/L, federal limit 0.08 mg/L (2.1 times the limit)
Oct 1, 2006 Resolved
CARBON, TOTAL
Treatment technique failure
Oct 1, 2006 Resolved
CARBON, TOTAL
Treatment technique failure
Jul 1, 2006 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.072 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
Jul 1, 2006 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.155 mg/L, federal limit 0.08 mg/L (1.9 times the limit)
Jul 1, 2006 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.077 mg/L, federal limit 0.06 mg/L (1.3 times the limit)
Apr 1, 2006 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.131 mg/L, federal limit 0.08 mg/L (1.6 times the limit)
Apr 1, 2006 Resolved
CARBON, TOTAL
Treatment technique failure
Apr 1, 2006 Resolved

36 older violations are not listed here. EPA ECHO has the complete list.

Enforcement actions

Oklahoma regulators took 25 formal enforcement actions against Pittsburg Co. PWA (Crowder) and issued 3 boil water orders between 1994 and 2022, filed as 31 records in EPA's data. The most recent was a compliance order (no penalty) in November 2022.

Date By Action Violations covered
Nov 15, 2022 Oklahoma Compliance order (no penalty) 1 violation (1 health-based): Total Trihalomethanes (TTHMs)
Sep 14, 2022 Oklahoma Compliance order (no penalty) 2 violations (2 health-based): Total Trihalomethanes (TTHMs)
Aug 19, 2015 Oklahoma Compliance order with a penalty 2 violations (2 health-based): Interim Enhanced Surface Water Treatment Rule
Mar 14, 2014 Oklahoma Compliance order with a penalty 1 violation (1 health-based): Total Trihalomethanes (TTHMs)
Jun 11, 2013 Oklahoma Compliance order with a penalty 2 violations (2 health-based): Total Trihalomethanes (TTHMs)
Feb 21, 2013 Oklahoma Compliance order with a penalty 4 violations (2 health-based): Interim Enhanced Surface Water Treatment Rule, Total Coliform
Sep 28, 2011 Oklahoma Compliance order with a penalty 58 violations (58 health-based): Haloacetic Acids (HAA5), CARBON, TOTAL, Total Trihalomethanes (TTHMs)
Aug 30, 2011 Oklahoma Compliance order with a penalty 1 violation (1 health-based): Interim Enhanced Surface Water Treatment Rule
Feb 25, 2009 Oklahoma Compliance order with a penalty 48 violations (48 health-based): CARBON, TOTAL, Total Trihalomethanes (TTHMs), Haloacetic Acids (HAA5)
Mar 24, 2008 Oklahoma Compliance order with a penalty 2 violations: Total Trihalomethanes (TTHMs), Haloacetic Acids (HAA5)
Dec 17, 2007 Oklahoma Compliance order with a penalty 3 violations (3 health-based): CARBON, TOTAL, Haloacetic Acids (HAA5), Total Trihalomethanes (TTHMs)
Jun 8, 2007 Oklahoma Compliance order with a penalty 3 violations (3 health-based): Total Trihalomethanes (TTHMs), CARBON, TOTAL, Haloacetic Acids (HAA5)
Feb 20, 2007 Oklahoma Compliance order with a penalty 3 violations (3 health-based): Total Trihalomethanes (TTHMs), Haloacetic Acids (HAA5), CARBON, TOTAL
Nov 7, 2006 Oklahoma Compliance order with a penalty 3 violations (3 health-based): Total Trihalomethanes (TTHMs), Haloacetic Acids (HAA5), CARBON, TOTAL
Sep 27, 2006 Oklahoma Compliance order with a penalty 3 violations (3 health-based): CARBON, TOTAL, Haloacetic Acids (HAA5), Total Trihalomethanes (TTHMs)
Sep 5, 2006 Oklahoma Compliance order with a penalty 3 violations (3 health-based): CARBON, TOTAL, Total Trihalomethanes (TTHMs), Haloacetic Acids (HAA5)
Jul 28, 2006 Oklahoma Compliance order (no penalty) 62 violations (60 health-based): CARBON, TOTAL, Total Trihalomethanes (TTHMs), Haloacetic Acids (HAA5)
Apr 6, 2006 Oklahoma Compliance order with a penalty 3 violations (3 health-based): Total Trihalomethanes (TTHMs), CARBON, TOTAL, Haloacetic Acids (HAA5)
Jan 9, 2006 Oklahoma Compliance order with a penalty 1 violation: Chlorine
Jan 3, 2006 Oklahoma Compliance order with a penalty 6 violations (6 health-based): CARBON, TOTAL, Total Trihalomethanes (TTHMs), Haloacetic Acids (HAA5)
Sep 7, 2005 Oklahoma Compliance order with a penalty 3 violations (3 health-based): CARBON, TOTAL, Total Trihalomethanes (TTHMs), Haloacetic Acids (HAA5)
Aug 9, 2005 Oklahoma Compliance order with a penalty 4 violations (4 health-based): Interim Enhanced Surface Water Treatment Rule
May 11, 2005 Oklahoma Compliance order with a penalty 2 violations (2 health-based): Interim Enhanced Surface Water Treatment Rule
Apr 7, 2005 Oklahoma Compliance order with a penalty 3 violations (3 health-based): Haloacetic Acids (HAA5), Total Trihalomethanes (TTHMs), CARBON, TOTAL
Dec 17, 1996 Oklahoma Compliance order (no penalty) 1 violation (1 health-based): Surface Water Treatment Rule
Jun 7, 1995 Oklahoma Boil water order 1 violation
Jul 29, 1994 Oklahoma Boil water order 1 violation
Apr 14, 1994 Oklahoma Boil water order 1 violation

What the violations mean

Total Trihalomethanes (TTHMs)

3 incidents

Disinfection byproduct levels exceeded the federal limit

Long-term TTHM exposure may increase bladder cancer risk

CARBON, TOTAL

1 incident

The system did not complete a treatment step or action that federal rules require for CARBON, TOTAL (a treatment technique violation).

The utility had to notify customers about this violation.

LEAD AND COPPER RULE REVISIONS

1 incident

The system did not complete a treatment step or action that the LEAD AND COPPER RULE REVISIONS requires (a treatment technique violation).

The utility had to notify customers about this violation.

Where the water comes from

Pittsburg Co. PWA (Crowder) draws water from 1 surface water intake. 1 other community water system buys water from Pittsburg Co. PWA (Crowder).

Community systems that buy water from it

Annual water quality report

Pittsburg Co. PWA (Crowder) must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.

Where the state allows it, systems serving fewer than 10,000 people may publish the report in a local newspaper or news site instead of mailing it, and must provide a copy on request.

Find a posted report with EPA's Consumer Confidence Report search

Testing your own water

To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Oklahoma.