Public water system record
Barberton City
Serves Barberton, Summit County, OH · 31,298 people served
Federal records show no health-based violations and 1 monitoring/reporting issue for Barberton City in the last ten years.
System profile
- Health-based violations, last 10 years
- 0
- Resolved
- 0
- Unresolved
- 0
- Any acute record
- No
- Monitoring issues, last 10 years
- 1
Key facts
- Barberton City draws water from 3 wells and 1 surface water intake.
- Most recent enforcement action: boil water order by Ohio, September 1989.
- Record on file since 1984, with 17 health-based violations before October 19, 2016.
- Lead pipe inventory: 0 lead and 8,966 unknown out of 12,771 service lines.
Check whether Barberton City serves your address
Health-based violations
Since October 2016Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.
None since October 2016.
Monitoring and reporting issues
Since October 2016Missed tests or reports, not contaminants found above a limit.
| Issue | Start date | Status |
|---|---|---|
|
Turbidity
Monitoring and reporting
|
Sep 1, 2017 | Resolved |
Full record since 1984
EPA's records for Barberton City go back to 1984. Before October 19, 2016 they list 17 health-based violations (15 resolved, 2 archived by EPA without a recorded fix) and 42 monitoring or reporting violations.
| Violations that began in | Health-based | Monitoring and reporting |
|---|---|---|
| 1980s | 2 | 0 |
| 1990s | 0 | 4 |
| 2000s | 3 | 37 |
| 2010 to October 18, 2016 | 12 | 1 |
| October 19, 2016 to 2019 | 0 | 1 |
Most recent health-based violation before October 19, 2016: Interim Enhanced Surface Water Treatment Rule (acute), began July 2015, Resolved.
Show all 17 health-based violations before October 19, 2016
| Contaminant | Start date | Status |
|---|---|---|
|
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
|
Jul 1, 2015 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.063 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
|
Jul 1, 2014 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.092 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
Jul 1, 2014 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.075 mg/L, federal limit 0.06 mg/L (1.3 times the limit)
|
Apr 1, 2014 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.094 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
Apr 1, 2014 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.073 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
|
Jan 1, 2014 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.092 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
Jan 1, 2014 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.075 mg/L, federal limit 0.06 mg/L (1.3 times the limit)
|
Oct 1, 2013 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.089 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Oct 1, 2013 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.082 mg/L, federal limit 0.08 mg/L (at or just above the limit)
|
Apr 1, 2012 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.064 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
|
Jan 1, 2012 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.084 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Apr 1, 2010 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.063 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
|
Apr 1, 2006 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
|
Jan 1, 2006 | Resolved |
|
Surface Water Treatment Rule
Treatment technique failure
|
Aug 1, 2004 | Resolved |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
|
Aug 29, 1984 | Archived |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
|
Jun 1, 1984 | Archived |
Enforcement actions
Ohio regulators issued 1 boil water order to Barberton City in 1989. The most recent was a boil water order in September 1989.
| Date | By | Action | Violations covered |
|---|---|---|---|
| Sep 11, 1989 | Ohio | Boil water order | 1 violation |
Where the water comes from
Barberton City draws water from 3 wells and 1 surface water intake.
Annual water quality report
Barberton City must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.
Systems serving 10,000 or more people must mail or deliver the report to every customer, and from 2027 they must send it twice a year.
Find a posted report with EPA's Consumer Confidence Report search
Testing your own water
To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Ohio.
Certified drinking water labs by state EPA guidance for private wells