Public water system record
Cedar Meadows Water Corp
Serves an area of Dutchess County, NY · 250 people served
Federal records show 5 health-based violations and 8 monitoring/reporting issues for Cedar Meadows Water Corp in the last ten years. The most serious issue in this window was a resolved Combined Radium (-226 and -228) violation.
System profile
- Health-based violations, last 10 years
- 5
- Resolved
- 5
- Unresolved
- 0
- Any acute record
- No
- Monitoring issues, last 10 years
- 8
Key facts
- Cedar Meadows Water Corp draws water from 2 wells.
- Highest measured level in the last 10 years: Combined Radium (-226 and -228), 10.21 pCi/L, federal limit 5 pCi/L (2 times the limit), 2017.
- Most recent formal enforcement: compliance order with a penalty by New York, July 2017.
- Record on file since 1999, with 20 health-based violations before October 19, 2016.
- Lead pipe inventory: 0 lead and 0 unknown out of 68 service lines.
Check whether Cedar Meadows Water Corp serves your address
Health-based violations
Since October 2016Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.
| Contaminant | Rule family | Start date | Status | Acute |
|---|---|---|---|---|
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 5.94 pCi/L, federal limit 5 pCi/L (1.2 times the limit)
|
340 | Oct 1, 2019 | Resolved | No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 10.2 pCi/L, federal limit 5 pCi/L (2 times the limit)
|
340 | Apr 1, 2017 | Resolved | No |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 15.8 pCi/L, federal limit 15 pCi/L (1.1 times the limit)
|
340 | Jan 1, 2017 | Resolved | No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 10.21 pCi/L, federal limit 5 pCi/L (2 times the limit)
|
340 | Jan 1, 2017 | Resolved | No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 9.76 pCi/L, federal limit 5 pCi/L (2 times the limit)
|
340 | Oct 1, 2016 | Resolved | No |
Monitoring and reporting issues
Since October 2016Missed tests or reports, not contaminants found above a limit.
| Issue | Start date | Status |
|---|---|---|
|
Consumer Confidence Rule
OTHER
|
Jul 1, 2018 | Resolved |
|
Consumer Confidence Rule
OTHER
|
Jul 1, 2017 | Resolved |
|
Radium-228
Monitoring and reporting
|
Apr 1, 2017 | Resolved |
|
Radium-226
Monitoring and reporting
|
Apr 1, 2017 | Resolved |
|
Combined Radium (-226 and -228)
Monitoring and reporting
|
Apr 1, 2017 | Resolved |
|
Combined Uranium
Monitoring and reporting
|
Apr 1, 2017 | Resolved |
|
Consumer Confidence Rule
OTHER
|
Sep 1, 2016 | Resolved |
|
Lead and Copper Rule
Monitoring and reporting
|
Oct 1, 2005 | Resolved |
Full record since 1999
EPA's records for Cedar Meadows Water Corp go back to 1999. Before October 19, 2016 they list 20 health-based violations (20 resolved) and 45 monitoring or reporting violations.
| Violations that began in | Health-based | Monitoring and reporting |
|---|---|---|
| 1990s | 0 | 1 |
| 2000s | 0 | 36 |
| 2010 to October 18, 2016 | 20 | 8 |
| October 19, 2016 to 2019 | 4 | 6 |
Most recent health-based violation before October 19, 2016: Combined Radium (-226 and -228), began October 2016, Resolved.
Show all 20 health-based violations before October 19, 2016
| Contaminant | Start date | Status |
|---|---|---|
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 9.76 pCi/L, federal limit 5 pCi/L (2 times the limit)
|
Oct 1, 2016 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 9.3 pCi/L, federal limit 5 pCi/L (1.9 times the limit)
|
Jul 1, 2016 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 8.87 pCi/L, federal limit 5 pCi/L (1.8 times the limit)
|
Apr 1, 2016 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 9.225 pCi/L, federal limit 5 pCi/L (1.8 times the limit)
|
Jan 1, 2016 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 8.9 pCi/L, federal limit 5 pCi/L (1.8 times the limit)
|
Oct 1, 2015 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 9.22 pCi/L, federal limit 5 pCi/L (1.8 times the limit)
|
Jul 1, 2015 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 9.87 pCi/L, federal limit 5 pCi/L (2 times the limit)
|
Apr 1, 2015 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 9.39 pCi/L, federal limit 5 pCi/L (1.9 times the limit)
|
Jan 1, 2015 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 8.96 pCi/L, federal limit 5 pCi/L (1.8 times the limit)
|
Oct 1, 2014 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 9.71 pCi/L, federal limit 5 pCi/L (1.9 times the limit)
|
Jul 1, 2014 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 10.26 pCi/L, federal limit 5 pCi/L (2.1 times the limit)
|
Apr 1, 2014 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 6.42 pCi/L, federal limit 5 pCi/L (1.3 times the limit)
|
Jan 1, 2014 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 6.31 pCi/L, federal limit 5 pCi/L (1.3 times the limit)
|
Oct 1, 2013 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 6.18 pCi/L, federal limit 5 pCi/L (1.2 times the limit)
|
Jul 1, 2013 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 6.8 pCi/L, federal limit 5 pCi/L (1.4 times the limit)
|
Apr 1, 2012 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 6.8 pCi/L, federal limit 5 pCi/L (1.4 times the limit)
|
Jan 1, 2012 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 7.78 pCi/L, federal limit 5 pCi/L (1.6 times the limit)
|
Oct 1, 2011 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 7.78 pCi/L, federal limit 5 pCi/L (1.6 times the limit)
|
Jul 1, 2011 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 8.99 pCi/L, federal limit 5 pCi/L (1.8 times the limit)
|
Apr 1, 2011 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 10.5 pCi/L, federal limit 5 pCi/L (2.1 times the limit)
|
Jan 1, 2011 | Resolved |
Enforcement actions
New York regulators and EPA took 3 formal enforcement actions against Cedar Meadows Water Corp between 2015 and 2017. The most recent was a compliance order with a penalty in July 2017.
| Date | By | Action | Violations covered |
|---|---|---|---|
| Jul 17, 2017 | New York | Compliance order with a penalty | 16 violations (16 health-based): Combined Radium (-226 and -228), Gross Alpha, Excl. Radon and U |
| Feb 20, 2015 | New York | Compliance order with a penalty | 1 violation (1 health-based): Combined Radium (-226 and -228) |
| Jan 14, 2015 | EPA | Compliance order (no penalty) | 11 violations (11 health-based): Combined Radium (-226 and -228) |
What the violations mean
Combined Radium (-226 and -228)
4 incidentsTest results for Combined Radium (-226 and -228) were above the federal limit (a maximum contaminant level violation).
The utility had to notify customers about each of these violations.
Gross Alpha, Excl. Radon and U
1 incidentTest results for Gross Alpha, Excl. Radon and U were above the federal limit (a maximum contaminant level violation).
The utility had to notify customers about this violation.
Where the water comes from
Cedar Meadows Water Corp draws water from 2 wells.
Annual water quality report
Cedar Meadows Water Corp must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.
Systems serving 500 or fewer people may meet the rule by telling customers the report is available on request, so you may need to ask Cedar Meadows Water Corp for a copy.
Find a posted report with EPA's Consumer Confidence Report search
Testing your own water
To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by New York.
Certified drinking water labs by state EPA guidance for private wells