Public water system record

Socorro Water System

Serves Socorro, Socorro County, NM · 12,026 people served

Federal records show no health-based violations and 2 monitoring/reporting issues for Socorro Water System in the last ten years.

  • NM3523728
  • SOCORRO
  • NM
  • 12,026 served

System profile

Source water Groundwater
ZIP 87801
EPA system ID NM3523728

Verify this system on EPA ECHO →

Health-based violations, last 10 years
0
Resolved
0
Unresolved
0
Any acute record
No
Monitoring issues, last 10 years
2

Key facts

  • Socorro Water System draws water from 3 wells and 2 springs.
  • Most recent formal enforcement: compliance order (no penalty) by New Mexico, December 2009.
  • Record on file since 1992, with 36 health-based violations before October 19, 2016.
  • Lead pipe inventory: 0 lead and 3,749 unknown out of 3,749 service lines.

Check whether Socorro Water System serves your address

Address suggestions by Mapbox

Health-based violations

Since October 2016

Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.

None since October 2016.

Monitoring and reporting issues

Since October 2016

Missed tests or reports, not contaminants found above a limit.

Issue Start date Status
Consumer Confidence Rule
OTHER
Oct 1, 2022 Resolved
Public Notice
OTHER
May 15, 2015 Resolved

Full record since 1992

EPA's records for Socorro Water System go back to 1992. Before October 19, 2016 they list 36 health-based violations (36 resolved) and 17 monitoring or reporting violations.

Violations that began in Health-based Monitoring and reporting
1990s 1 1
2000s 18 12
2010 to October 18, 2016 17 4
2020s 0 1

Most recent health-based violation before October 19, 2016: Arsenic, began July 2013, Resolved.

Show all 36 health-based violations before October 19, 2016
Contaminant Start date Status
Arsenic
Contaminant limit exceeded
Measured 0.014 mg/L, federal limit 0.01 mg/L (1.4 times the limit)
Jul 1, 2013 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.024 mg/L, federal limit 0.01 mg/L (2.4 times the limit)
Apr 1, 2013 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.014 mg/L, federal limit 0.01 mg/L (1.4 times the limit)
Apr 1, 2013 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.033 mg/L, federal limit 0.01 mg/L (3.3 times the limit)
Jan 1, 2013 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.019 mg/L, federal limit 0.01 mg/L (1.9 times the limit)
Jan 1, 2013 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.038 mg/L, federal limit 0.01 mg/L (3.8 times the limit)
Oct 1, 2012 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.033 mg/L, federal limit 0.01 mg/L (3.3 times the limit)
Jul 1, 2012 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.032 mg/L, federal limit 0.01 mg/L (3.2 times the limit)
Apr 1, 2012 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.028 mg/L, federal limit 0.01 mg/L (2.8 times the limit)
Jan 1, 2012 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.032 mg/L, federal limit 0.01 mg/L (3.2 times the limit)
Oct 1, 2011 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.037 mg/L, federal limit 0.01 mg/L (3.7 times the limit)
Jul 1, 2011 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.036 mg/L, federal limit 0.01 mg/L (3.6 times the limit)
Apr 1, 2011 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.038 mg/L, federal limit 0.01 mg/L (3.8 times the limit)
Jan 1, 2011 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.037 mg/L, federal limit 0.01 mg/L (3.7 times the limit)
Oct 1, 2010 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.04 mg/L, federal limit 0.01 mg/L (4 times the limit)
Jul 1, 2010 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.04 mg/L, federal limit 0.01 mg/L (4 times the limit)
Apr 1, 2010 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.037 mg/L, federal limit 0.01 mg/L (3.7 times the limit)
Jan 1, 2010 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.039 mg/L, federal limit 0.01 mg/L (3.9 times the limit)
Oct 1, 2009 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.036 mg/L, federal limit 0.01 mg/L (3.6 times the limit)
Jul 1, 2009 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.048 mg/L, federal limit 0.01 mg/L (4.8 times the limit)
Apr 1, 2009 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.048 mg/L, federal limit 0.01 mg/L (4.8 times the limit)
Jan 1, 2009 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.05 mg/L, federal limit 0.01 mg/L (5 times the limit)
Oct 1, 2008 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.024 mg/L, federal limit 0.01 mg/L (2.4 times the limit)
Jul 1, 2008 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.042 mg/L, federal limit 0.01 mg/L (4.2 times the limit)
Jul 1, 2008 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.091 mg/L, federal limit 0.01 mg/L (9.1 times the limit)
Jul 1, 2008 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.051 mg/L, federal limit 0.01 mg/L (5.1 times the limit)
Apr 1, 2008 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.021 mg/L, federal limit 0.01 mg/L (2.1 times the limit)
Apr 1, 2008 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.017 mg/L, federal limit 0.01 mg/L (1.7 times the limit)
Apr 1, 2008 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.041 mg/L, federal limit 0.01 mg/L (4.1 times the limit)
Jan 1, 2008 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.041 mg/L, federal limit 0.01 mg/L (4.1 times the limit)
Jan 1, 2008 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.011 mg/L, federal limit 0.01 mg/L (1.1 times the limit)
Jan 1, 2008 Resolved
Combined Uranium
Contaminant limit exceeded
Measured 36 µg/L, federal limit 30 µg/L (1.2 times the limit)
Jul 1, 2006 Resolved
Combined Uranium
Contaminant limit exceeded
Measured 39.5 µg/L, federal limit 30 µg/L (1.3 times the limit)
Apr 1, 2006 Resolved
Combined Uranium
Contaminant limit exceeded
Measured 43.5 µg/L, federal limit 30 µg/L (1.5 times the limit)
Jan 1, 2006 Resolved
Combined Uranium
Contaminant limit exceeded
Measured 42.5 µg/L, federal limit 30 µg/L (1.4 times the limit)
Oct 1, 2005 Resolved
Total Coliform (acute)
Contaminant limit exceeded
Oct 1, 1995 Resolved

Enforcement actions

New Mexico regulators took 1 formal enforcement action against Socorro Water System and issued 1 boil water order between 1995 and 2009, filed as 6 records in EPA's data. The most recent was a compliance order (no penalty) in December 2009.

Date By Action Violations covered
Dec 1, 2009 New Mexico Compliance order (no penalty) 25 violations (25 health-based): Arsenic
Nov 2, 1995 New Mexico Boil water order 1 violation (1 health-based): Total Coliform

Where the water comes from

Socorro Water System draws water from 3 wells and 2 springs. 1 smaller public system such as schools, businesses or campgrounds buys water from Socorro Water System.

Annual water quality report

Socorro Water System must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.

Systems serving 10,000 or more people must mail or deliver the report to every customer, and from 2027 they must send it twice a year.

Find a posted report with EPA's Consumer Confidence Report search

Testing your own water