Public water system record

San Ysidro Water Supply System

Serves San Ysidro, Sandoval County, NM · 166 people served

Federal records show 30 health-based violations and 32 monitoring/reporting issues for San Ysidro Water Supply System in the last ten years, including an unresolved Groundwater Rule violation.

  • NM3509723
  • SAN YSIDRO
  • NM
  • 166 served

System profile

Source water Groundwater
ZIP 87053
EPA system ID NM3509723

Verify this system on EPA ECHO →

Health-based violations, last 10 years
30
Resolved
22
Unresolved
3
Archived by EPA
5
Any acute record
No
Monitoring issues, last 10 years
32

Key facts

  • San Ysidro Water Supply System draws water from 1 well and 2 infiltration galleries.
  • Highest measured level in the last 10 years: Arsenic, 0.11 mg/L, federal limit 0.01 mg/L (11 times the limit), 2022.
  • Most recent formal enforcement: compliance order (no penalty) by New Mexico, September 2022.
  • Record on file since 1984, with 22 health-based violations before October 19, 2016.

Check whether San Ysidro Water Supply System serves your address

Address suggestions by Mapbox

Health-based violations

Since October 2016

Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.

Contaminant Rule family Start date Status Acute
Groundwater Rule
Treatment technique failure
140 Jul 12, 2025 Active No
Groundwater Rule
Treatment technique failure
140 Jul 12, 2025 Active No
LEAD AND COPPER RULE REVISIONS
Treatment technique failure
350 Oct 17, 2024 Active No
Fluoride
Contaminant limit exceeded
Measured 5 mg/L, federal limit 4 mg/L (1.3 times the limit)
330 Jul 1, 2024 Resolved No
Fluoride
Contaminant limit exceeded
Measured 5.2 mg/L, federal limit 4 mg/L (1.3 times the limit)
330 Apr 1, 2024 Resolved No
Fluoride
Contaminant limit exceeded
Measured 5 mg/L, federal limit 4 mg/L (1.3 times the limit)
330 Jan 1, 2024 Resolved No
Fluoride
Contaminant limit exceeded
Measured 4.8 mg/L, federal limit 4 mg/L (1.2 times the limit)
330 Oct 1, 2023 Resolved No
Fluoride
Contaminant limit exceeded
Measured 4.5 mg/L, federal limit 4 mg/L (1.1 times the limit)
330 Jul 1, 2023 Resolved No
Arsenic
Contaminant limit exceeded
Measured 0.038 mg/L, federal limit 0.01 mg/L (3.8 times the limit)
330 Apr 1, 2023 Resolved No
Fluoride
Contaminant limit exceeded
Measured 4.6 mg/L, federal limit 4 mg/L (1.2 times the limit)
330 Apr 1, 2023 Resolved No
Arsenic
Contaminant limit exceeded
Measured 0.056 mg/L, federal limit 0.01 mg/L (5.6 times the limit)
330 Jan 1, 2023 Resolved No
Fluoride
Contaminant limit exceeded
Measured 4.8 mg/L, federal limit 4 mg/L (1.2 times the limit)
330 Jan 1, 2023 Resolved No
Arsenic
Contaminant limit exceeded
Measured 0.11 mg/L, federal limit 0.01 mg/L (11 times the limit)
330 Oct 1, 2022 Resolved No
Fluoride
Contaminant limit exceeded
Measured 5.1 mg/L, federal limit 4 mg/L (1.3 times the limit)
330 Oct 1, 2022 Resolved No
Arsenic
Contaminant limit exceeded
Measured 0.11 mg/L, federal limit 0.01 mg/L (11 times the limit)
330 Jul 1, 2022 Resolved No
Fluoride
Contaminant limit exceeded
Measured 5.6 mg/L, federal limit 4 mg/L (1.4 times the limit)
330 Jul 1, 2022 Resolved No
Fluoride
Contaminant limit exceeded
Measured 5.5 mg/L, federal limit 4 mg/L (1.4 times the limit)
330 Apr 1, 2022 Resolved No
Fluoride
Contaminant limit exceeded
Measured 6.7 mg/L, federal limit 4 mg/L (1.7 times the limit)
330 Jan 1, 2022 Resolved No
Fluoride
Contaminant limit exceeded
Measured 6.1 mg/L, federal limit 4 mg/L (1.5 times the limit)
330 Oct 1, 2021 Resolved No
Fluoride
Contaminant limit exceeded
Measured 5.7 mg/L, federal limit 4 mg/L (1.4 times the limit)
330 Jul 1, 2021 Resolved No
Fluoride
Contaminant limit exceeded
Measured 5.6 mg/L, federal limit 4 mg/L (1.4 times the limit)
330 Apr 1, 2021 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Fluoride
Contaminant limit exceeded
Measured 5.3 mg/L, federal limit 4 mg/L (1.3 times the limit)
330 Jan 1, 2021 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Fluoride
Contaminant limit exceeded
Measured 5.3 mg/L, federal limit 4 mg/L (1.3 times the limit)
330 Oct 1, 2020 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Fluoride
Contaminant limit exceeded
Measured 5.7 mg/L, federal limit 4 mg/L (1.4 times the limit)
330 Jul 1, 2020 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Fluoride
Contaminant limit exceeded
Measured 4.5 mg/L, federal limit 4 mg/L (1.1 times the limit)
330 Apr 1, 2020 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Groundwater Rule
Treatment technique failure
140 Jul 8, 2017 Resolved No
Fluoride
Contaminant limit exceeded
Measured 4.1 mg/L, federal limit 4 mg/L (at or just above the limit)
330 Apr 1, 2017 Resolved No
Fluoride
Contaminant limit exceeded
Measured 5.3 mg/L, federal limit 4 mg/L (1.3 times the limit)
330 Jan 1, 2017 Resolved No
Fluoride
Contaminant limit exceeded
Measured 5.2 mg/L, federal limit 4 mg/L (1.3 times the limit)
330 Oct 1, 2016 Resolved No
Stage 1 Disinfection Byproducts Rule
Treatment technique failure
210 Aug 31, 2012 Resolved No

Monitoring and reporting issues

Since October 2016

Missed tests or reports, not contaminants found above a limit.

Issue Start date Status
LEAD AND COPPER RULE REVISIONS
RPT
Oct 17, 2024 Active
Haloacetic Acids (HAA5)
Monitoring and reporting
Nov 1, 2023 Resolved
Total Trihalomethanes (TTHMs)
Monitoring and reporting
Nov 1, 2023 Resolved
Haloacetic Acids (HAA5)
Monitoring and reporting
Oct 1, 2023 Resolved
Total Trihalomethanes (TTHMs)
Monitoring and reporting
Oct 1, 2023 Resolved
Arsenic
Monitoring and reporting
Oct 1, 2022 Resolved
Public Notice
OTHER
May 8, 2022 Resolved
Arsenic
Monitoring and reporting
Apr 1, 2022 Resolved
Arsenic
Monitoring and reporting
Jan 1, 2022 Resolved
Fluoride
Monitoring and reporting
Jan 1, 2022 Resolved
Fluoride
Monitoring and reporting
Oct 1, 2021 Resolved
Arsenic
Monitoring and reporting
Oct 1, 2021 Resolved
Consumer Confidence Rule
OTHER
Oct 1, 2021 Resolved
Arsenic
Monitoring and reporting
Jul 1, 2021 Resolved
Fluoride
Monitoring and reporting
Jul 1, 2021 Resolved
Arsenic
Monitoring and reporting
Apr 1, 2021 Resolved
Arsenic
Monitoring and reporting
Jan 1, 2021 Resolved
Public Notice
OTHER
Oct 3, 2020 Resolved
Haloacetic Acids (HAA5)
Monitoring and reporting
Oct 1, 2020 Resolved
Arsenic
Monitoring and reporting
Oct 1, 2020 Resolved
Revised Total Coliform Rule
Monitoring violation
Sep 1, 2020 Resolved
Revised Total Coliform Rule
Monitoring violation
Aug 1, 2020 Resolved
Chlorine
Monitoring and reporting
Jul 1, 2020 Resolved
Arsenic
Monitoring and reporting
Jul 1, 2020 Resolved
Consumer Confidence Rule
OTHER
Jul 1, 2020 Resolved
Public Notice
OTHER
Jun 5, 2020 Resolved
Arsenic
Monitoring and reporting
Apr 1, 2020 Resolved
Arsenic
Monitoring and reporting
Jan 1, 2020 Resolved
Total Trihalomethanes (TTHMs)
Monitoring and reporting
Jan 1, 2020 Resolved
Public Notice
OTHER
Apr 20, 2017 Resolved
Lead and Copper Rule
Monitoring and reporting
Oct 1, 2015 Resolved
Public Notice
OTHER
Jul 31, 2015 Resolved

Full record since 1984

EPA's records for San Ysidro Water Supply System go back to 1984. Before October 19, 2016 they list 22 health-based violations (17 resolved, 5 archived by EPA without a recorded fix) and 35 monitoring or reporting violations.

Violations that began in Health-based Monitoring and reporting
1980s 3 0
1990s 3 7
2000s 0 22
2010 to October 18, 2016 16 6
October 19, 2016 to 2019 3 1
2020s 25 29

Most recent health-based violation before October 19, 2016: Fluoride, began October 2016, Resolved.

Show all 22 health-based violations before October 19, 2016
Contaminant Start date Status
Fluoride
Contaminant limit exceeded
Measured 5.2 mg/L, federal limit 4 mg/L (1.3 times the limit)
Oct 1, 2016 Resolved
Fluoride
Contaminant limit exceeded
Measured 5.2 mg/L, federal limit 4 mg/L (1.3 times the limit)
Jul 1, 2016 Resolved
Fluoride
Contaminant limit exceeded
Measured 5.2 mg/L, federal limit 4 mg/L (1.3 times the limit)
Apr 1, 2016 Resolved
Fluoride
Contaminant limit exceeded
Measured 5.3 mg/L, federal limit 4 mg/L (1.3 times the limit)
Jan 1, 2016 Resolved
Fluoride
Contaminant limit exceeded
Measured 5.5 mg/L, federal limit 4 mg/L (1.4 times the limit)
Oct 1, 2015 Resolved
Fluoride
Contaminant limit exceeded
Measured 5.8 mg/L, federal limit 4 mg/L (1.5 times the limit)
Jul 1, 2015 Resolved
Fluoride
Contaminant limit exceeded
Measured 5.8 mg/L, federal limit 4 mg/L (1.5 times the limit)
Apr 1, 2015 Resolved
Fluoride
Contaminant limit exceeded
Measured 5.9 mg/L, federal limit 4 mg/L (1.5 times the limit)
Jan 1, 2015 Resolved
Fluoride
Contaminant limit exceeded
Measured 5.8 mg/L, federal limit 4 mg/L (1.5 times the limit)
Oct 1, 2014 Resolved
Fluoride
Contaminant limit exceeded
Measured 5.6 mg/L, federal limit 4 mg/L (1.4 times the limit)
Jul 1, 2014 Resolved
Fluoride
Contaminant limit exceeded
Measured 4.3 mg/L, federal limit 4 mg/L (1.1 times the limit)
Apr 1, 2014 Resolved
Stage 1 Disinfection Byproducts Rule
Treatment technique failure
Aug 31, 2012 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.13 mg/L, federal limit 0.08 mg/L (1.6 times the limit)
Jan 1, 2011 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.115 mg/L, federal limit 0.08 mg/L (1.4 times the limit)
Oct 1, 2010 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.125 mg/L, federal limit 0.08 mg/L (1.6 times the limit)
Jul 1, 2010 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.082 mg/L, federal limit 0.08 mg/L (at or just above the limit)
Apr 1, 2010 Resolved
Total Coliform
Contaminant limit exceeded
Aug 1, 1999 Resolved
Arsenic
Contaminant limit exceeded
Jan 1, 1996 Archived
Fluoride
Contaminant limit exceeded
Jan 1, 1996 Archived
Arsenic
Contaminant limit exceeded
Jan 1, 1986 Archived
Fluoride
Contaminant limit exceeded
Jul 1, 1984 Archived
Arsenic
Contaminant limit exceeded
Jul 1, 1984 Archived

Enforcement actions

New Mexico regulators and EPA took 3 formal enforcement actions against San Ysidro Water Supply System between 1999 and 2022. The most recent was a compliance order (no penalty) in September 2022.

Date By Action Violations covered
Sep 16, 2022 New Mexico Compliance order (no penalty) 17 violations (17 health-based): Fluoride
Sep 22, 2000 EPA Compliance order (no penalty) 2 violations: Consumer Confidence Rule
Mar 31, 1999 EPA Compliance order (no penalty) 3 violations (2 health-based): Fluoride, Arsenic, Total Coliform

What the violations mean

Fluoride

21 incidents

Fluoride exceeded the federal limit

Excessive fluoride can cause dental and skeletal fluorosis

Arsenic

4 incidents

Arsenic exceeded the federal limit

Long-term arsenic exposure is linked to cancer and cardiovascular effects

Groundwater Rule

3 incidents

The system did not complete a treatment step or action that the Groundwater Rule requires (a treatment technique violation).

The utility had to notify customers about each of these violations.

LEAD AND COPPER RULE REVISIONS

1 incident

The system did not complete a treatment step or action that the LEAD AND COPPER RULE REVISIONS requires (a treatment technique violation).

The utility had to notify customers about this violation.

Stage 1 Disinfection Byproducts Rule

1 incident

The system did not meet a treatment requirement of the Stage 1 Disinfectants and Disinfection Byproducts Rule

Byproducts form when disinfectants react with natural material in water. Long-term exposure above federal limits may increase cancer risk

Where the water comes from

San Ysidro Water Supply System draws water from 1 well and 2 infiltration galleries.

Annual water quality report

San Ysidro Water Supply System must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.

Systems serving 500 or fewer people may meet the rule by telling customers the report is available on request, so you may need to ask San Ysidro Water Supply System for a copy.

Find a posted report with EPA's Consumer Confidence Report search

Testing your own water

To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by New Mexico.