Public water system record

Tuckahoe S/D

Serves Wake Forest and Rolesville, Wake County, NC · 221 people served

Federal records show no health-based violations and no monitoring or reporting issues for Tuckahoe S/D in the last ten years.

  • NC0392333
  • CHARLOTTE
  • NC
  • 221 served

System profile

Source water Groundwater
ZIP 28224
EPA system ID NC0392333

Verify this system on EPA ECHO →

Health-based violations, last 10 years
0
Resolved
0
Unresolved
0
Any acute record
No
Monitoring issues, last 10 years
0

Key facts

  • Tuckahoe S/D draws water from 3 wells.
  • Most recent formal enforcement: compliance order (no penalty) by North Carolina, October 2007.
  • Record on file since 1986, with 7 health-based violations before October 19, 2016.
  • Lead pipe inventory: 0 lead and 67 unknown out of 87 service lines.

Check whether Tuckahoe S/D serves your address

Address suggestions by Mapbox

Health-based violations

Since October 2016

Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.

None since October 2016, and no monitoring or reporting violations either.

Full record since 1986

EPA's records for Tuckahoe S/D go back to 1986. Before October 19, 2016 they list 7 health-based violations (5 resolved, 2 archived by EPA without a recorded fix) and 9 monitoring or reporting violations.

Violations that began in Health-based Monitoring and reporting
1980s 0 4
1990s 2 2
2000s 5 3

Most recent health-based violation before October 19, 2016: Combined Radium (-226 and -228), began April 2007, Resolved.

Show all 7 health-based violations before October 19, 2016
Contaminant Start date Status
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 6 pCi/L, federal limit 5 pCi/L (1.2 times the limit)
Apr 1, 2007 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 8.2 pCi/L, federal limit 5 pCi/L (1.6 times the limit)
Apr 1, 2005 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 5.1 pCi/L, federal limit 5 pCi/L (at or just above the limit)
Jan 1, 2005 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 6.5 pCi/L, federal limit 5 pCi/L (1.3 times the limit)
Oct 1, 2004 Resolved
Lead and Copper Rule
Treatment technique failure
Jul 1, 2001 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 5.1 pCi/L, federal limit 5 pCi/L (at or just above the limit)
Jan 6, 1992 Archived
Combined Radium (-226 and -228)
Contaminant limit exceeded
Jan 6, 1992 Archived

Enforcement actions

North Carolina regulators took 1 formal enforcement action against Tuckahoe S/D in 2007. The most recent was a compliance order (no penalty) in October 2007.

Date By Action Violations covered
Oct 9, 2007 North Carolina Compliance order (no penalty) 1 violation (1 health-based): Combined Radium (-226 and -228)

Where the water comes from

Tuckahoe S/D draws water from 3 wells.

Annual water quality report

Tuckahoe S/D must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.

Systems serving 500 or fewer people may meet the rule by telling customers the report is available on request, so you may need to ask Tuckahoe S/D for a copy.

Find a posted report with EPA's Consumer Confidence Report search

Testing your own water

To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by North Carolina.