Public water system record

Town of Yanceyville

Serves Yanceyville, Caswell County, NC · 1,937 people served

Federal records show 10 health-based violations and 17 monitoring/reporting issues for Town of Yanceyville in the last ten years. The most serious issue in this window was a Total Trihalomethanes (TTHMs) violation that EPA lists as archived, not resolved.

  • NC0217010
  • BANNER ELK
  • NC
  • 1,937 served

System profile

Source water Surface water
ZIP 28604
EPA system ID NC0217010

Verify this system on EPA ECHO →

Health-based violations, last 10 years
10
Resolved
7
Unresolved
0
Archived by EPA
3
Any acute record
Yes
Monitoring issues, last 10 years
17

Key facts

  • Town of Yanceyville draws water from 1 surface water intake.
  • Highest measured level in the last 10 years: Total Trihalomethanes (TTHMs), 0.093 mg/L, federal limit 0.08 mg/L (1.2 times the limit), 2025.
  • Most recent formal enforcement: compliance order (no penalty) by North Carolina, October 2025.
  • Record on file since 1991, with 22 health-based violations before October 19, 2016.
  • Lead pipe inventory: 0 lead and 409 unknown out of 812 service lines.

Check whether Town of Yanceyville serves your address

Address suggestions by Mapbox

Health-based violations

Since October 2016

Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.

Contaminant Rule family Start date Status Acute
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.092 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
220 Oct 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.093 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
220 Jul 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.09 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
220 Apr 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
CARBON, TOTAL
Treatment technique failure
210 Oct 1, 2022 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.089 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
220 Oct 1, 2022 Resolved No
CARBON, TOTAL
Treatment technique failure
210 Jul 1, 2022 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.086 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
220 Jul 1, 2022 Resolved No
Interim Enhanced Surface Water Treatment Rule
Treatment technique failure
120 Feb 1, 2019 Resolved Yes
Interim Enhanced Surface Water Treatment Rule
Treatment technique failure
120 Nov 1, 2018 Resolved Yes
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.081 mg/L, federal limit 0.08 mg/L (at or just above the limit)
220 Apr 1, 2018 Resolved No

Monitoring and reporting issues

Since October 2016

Missed tests or reports, not contaminants found above a limit.

Issue Start date Status
Total Trihalomethanes (TTHMs)
Monitoring and reporting
Aug 31, 2025 Active
Enforcement action in place
Dalapon
Monitoring and reporting
Jan 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
Revised Total Coliform Rule
Monitoring violation
Aug 1, 2022 Resolved
Chlorine
Monitoring and reporting
Jul 1, 2022 Resolved
Revised Total Coliform Rule
Monitoring violation
Jul 1, 2022 Resolved
Haloacetic Acids (HAA5)
Monitoring and reporting
Jun 1, 2020 Resolved
Total Trihalomethanes (TTHMs)
Monitoring and reporting
Jun 1, 2020 Resolved
Combined Radium (-226 and -228)
Monitoring and reporting
Jan 1, 2020 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
Haloacetic Acids (HAA5)
Monitoring and reporting
Dec 1, 2019 Resolved
Total Trihalomethanes (TTHMs)
Monitoring and reporting
Dec 1, 2019 Resolved
Consumer Confidence Rule
OTHER
Jul 1, 2019 Resolved
Revised Total Coliform Rule
RPT
Apr 11, 2019 Resolved
Public Notice
OTHER
Jan 1, 2019 Resolved
Lead and Copper Rule
Monitoring and reporting
Jan 1, 2018 Resolved
Combined Uranium
Monitoring and reporting
Jan 1, 2017 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
Gross Alpha, Excl. Radon and U
Monitoring and reporting
Jan 1, 2017 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
Haloacetic Acids (HAA5)
Monitoring and reporting
Jan 1, 2016 Resolved

Full record since 1991

EPA's records for Town of Yanceyville go back to 1991. Before October 19, 2016 they list 22 health-based violations (20 resolved, 2 archived by EPA without a recorded fix) and 69 monitoring or reporting violations.

Violations that began in Health-based Monitoring and reporting
1990s 2 60
2000s 7 6
2010 to October 18, 2016 13 3
October 19, 2016 to 2019 3 8
2020s 7 8

Most recent health-based violation before October 19, 2016: Haloacetic Acids (HAA5), began April 2014, Resolved.

Show all 22 health-based violations before October 19, 2016
Contaminant Start date Status
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.062 mg/L, federal limit 0.06 mg/L (at or just above the limit)
Apr 1, 2014 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.064 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
Jan 1, 2014 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.067 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
Oct 1, 2013 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.065 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
Jul 1, 2013 Resolved
CARBON, TOTAL
Treatment technique failure
Jan 1, 2013 Resolved
CARBON, TOTAL
Treatment technique failure
Oct 1, 2012 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.083 mg/L, federal limit 0.08 mg/L (at or just above the limit)
Oct 1, 2012 Resolved
CARBON, TOTAL
Treatment technique failure
Jul 1, 2012 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.087 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
Jul 1, 2012 Resolved
CARBON, TOTAL
Treatment technique failure
Apr 1, 2012 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.089 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
Apr 1, 2012 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.086 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
Jan 1, 2012 Resolved
CARBON, TOTAL
Treatment technique failure
Oct 1, 2011 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.061 mg/L, federal limit 0.06 mg/L (at or just above the limit)
Jan 1, 2009 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.065 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
Oct 1, 2008 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.066 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
Jul 1, 2008 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.068 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
Apr 1, 2008 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.0649 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
Apr 1, 2005 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.06478 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
Jan 1, 2005 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.06603 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
Oct 1, 2004 Resolved
Surface Water Treatment Rule
Treatment technique failure
Jul 1, 1993 Archived
Surface Water Treatment Rule
Treatment technique failure
Jul 1, 1993 Archived

Enforcement actions

North Carolina regulators took 19 formal enforcement actions against Town of Yanceyville between 2008 and 2025, filed as 23 records in EPA's data. The most recent was a compliance order (no penalty) in October 2025.

Date By Action Violations covered
Oct 1, 2025 North Carolina Compliance order (no penalty) 1 violation: Total Trihalomethanes (TTHMs)
Jun 6, 2025 North Carolina Compliance order (no penalty) 3 violations (3 health-based): Total Trihalomethanes (TTHMs)
Oct 26, 2022 North Carolina Compliance order (no penalty) 2 violations (2 health-based): CARBON, TOTAL
Oct 14, 2022 North Carolina Compliance order (no penalty) 1 violation: Revised Total Coliform Rule
Sep 28, 2022 North Carolina Compliance order (no penalty) 2 violations (2 health-based): Total Trihalomethanes (TTHMs)
Sep 22, 2022 North Carolina Compliance order (no penalty) 2 violations: Chlorine, Revised Total Coliform Rule
Sep 21, 2020 North Carolina Compliance order (no penalty) 2 violations: Total Trihalomethanes (TTHMs), Haloacetic Acids (HAA5)
Mar 25, 2020 North Carolina Compliance order (no penalty) 2 violations: Haloacetic Acids (HAA5), Total Trihalomethanes (TTHMs)
Apr 30, 2019 North Carolina Compliance order (no penalty) 1 violation: Revised Total Coliform Rule
Feb 19, 2019 North Carolina Compliance order (no penalty) 1 violation (1 health-based): Interim Enhanced Surface Water Treatment Rule
Feb 5, 2019 North Carolina Compliance order (no penalty) 1 violation: Public Notice
Dec 14, 2018 North Carolina Compliance order (no penalty) 1 violation (1 health-based): Interim Enhanced Surface Water Treatment Rule
Jun 20, 2018 North Carolina Compliance order (no penalty) 1 violation (1 health-based): Total Trihalomethanes (TTHMs)
May 14, 2018 North Carolina Compliance order (no penalty) 1 violation: Lead and Copper Rule
Feb 16, 2015 North Carolina Compliance order (no penalty) 1 violation: Haloacetic Acids (HAA5)
Jan 17, 2014 North Carolina Compliance order (no penalty) 6 violations (6 health-based): Haloacetic Acids (HAA5)
Aug 29, 2013 North Carolina Compliance order (no penalty) 3 violations (3 health-based): CARBON, TOTAL
Jun 27, 2012 North Carolina Compliance order (no penalty) 6 violations (6 health-based): CARBON, TOTAL, Total Trihalomethanes (TTHMs)
Nov 3, 2008 North Carolina Compliance order (no penalty) 2 violations (2 health-based): Haloacetic Acids (HAA5)

What the violations mean

Total Trihalomethanes (TTHMs)

6 incidents

Disinfection byproduct levels exceeded the federal limit

Long-term TTHM exposure may increase bladder cancer risk

CARBON, TOTAL

2 incidents

The system did not complete a treatment step or action that federal rules require for CARBON, TOTAL (a treatment technique violation).

The utility had to notify customers about each of these violations.

Interim Enhanced Surface Water Treatment Rule

2 incidents

The system did not meet a filtration or treatment requirement for surface water

Inadequate treatment of surface water can let pathogens such as Cryptosporidium and Giardia through

Where the water comes from

Town of Yanceyville draws water from 1 surface water intake. It also has an emergency connection to City of Danville. 1 other public water system has an emergency connection to Town of Yanceyville.

Emergency or part-time connections to

Annual water quality report

Town of Yanceyville must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.

Where the state allows it, systems serving fewer than 10,000 people may publish the report in a local newspaper or news site instead of mailing it, and must provide a copy on request.

Find a posted report with EPA's Consumer Confidence Report search

Testing your own water

To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by North Carolina.