Public water system record
Mineral Point PWS
Serves Mineral Point, Washington County, MO · 231 people served
Federal records show 2 health-based violations and 8 monitoring/reporting issues for Mineral Point PWS in the last ten years. The most serious issue in this window was a resolved Groundwater Rule violation.
System profile
- Health-based violations, last 10 years
- 2
- Resolved
- 2
- Unresolved
- 0
- Any acute record
- No
- Monitoring issues, last 10 years
- 8
Key facts
- Mineral Point PWS draws water from 1 well.
- Highest measured level in the last 10 years: Combined Radium (-226 and -228), 5.73 pCi/L, federal limit 5 pCi/L (1.1 times the limit), 2019.
- Most recent formal enforcement: compliance order with a penalty by Missouri, September 2011.
- Record on file since 1992, with 83 health-based violations before October 20, 2016.
Check whether Mineral Point PWS serves your address
Health-based violations
Since October 2016Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.
| Contaminant | Rule family | Start date | Status | Acute |
|---|---|---|---|---|
|
Groundwater Rule
Treatment technique failure
|
140 | Sep 14, 2022 | Resolved | No |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 5.73 pCi/L, federal limit 5 pCi/L (1.1 times the limit)
|
340 | Jul 1, 2019 | Resolved | No |
Monitoring and reporting issues
Since October 2016Missed tests or reports, not contaminants found above a limit.
| Issue | Start date | Status |
|---|---|---|
|
Consumer Confidence Rule
OTHER
|
Jul 1, 2025 | Resolved |
|
LEAD AND COPPER RULE REVISIONS
RPT
|
Oct 17, 2024 | Active |
|
Public Notice
OTHER
|
Jun 1, 2023 | Resolved |
|
Groundwater Rule
OTHER
|
Feb 3, 2023 | Resolved |
|
Public Notice
OTHER
|
Dec 5, 2022 | Resolved |
|
Consumer Confidence Rule
OTHER
|
Jul 1, 2022 | Resolved |
|
Revised Total Coliform Rule
Monitoring violation
|
Apr 1, 2022 | Resolved |
|
Public Notice
OTHER
|
Oct 6, 2020 | Resolved |
Full record since 1992
EPA's records for Mineral Point PWS go back to 1992. Before October 20, 2016 they list 83 health-based violations (57 resolved, 26 archived by EPA without a recorded fix) and 14 monitoring or reporting violations.
| Violations that began in | Health-based | Monitoring and reporting |
|---|---|---|
| 1990s | 0 | 1 |
| 2000s | 56 | 10 |
| 2010 to October 19, 2016 | 27 | 3 |
| October 20, 2016 to 2019 | 1 | 0 |
| 2020s | 1 | 8 |
Most recent health-based violation before October 20, 2016: Combined Radium (-226 and -228), began July 2013, Resolved.
Show all 83 health-based violations before October 20, 2016
| Contaminant | Start date | Status |
|---|---|---|
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 6.35 pCi/L, federal limit 5 pCi/L (1.3 times the limit)
|
Jul 1, 2013 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 8.72 pCi/L, federal limit 5 pCi/L (1.7 times the limit)
|
Apr 1, 2013 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 10.55 pCi/L, federal limit 5 pCi/L (2.1 times the limit)
|
Jan 1, 2013 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 13.52 pCi/L, federal limit 5 pCi/L (2.7 times the limit)
|
Oct 1, 2012 | Resolved |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 15.62 pCi/L, federal limit 15 pCi/L (at or just above the limit)
|
Oct 1, 2012 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 18.1 pCi/L, federal limit 5 pCi/L (3.6 times the limit)
|
Jul 1, 2012 | Resolved |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 18.65 pCi/L, federal limit 15 pCi/L (1.2 times the limit)
|
Jul 1, 2012 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 18.25 pCi/L, federal limit 5 pCi/L (3.7 times the limit)
|
Apr 1, 2012 | Resolved |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 18.38 pCi/L, federal limit 15 pCi/L (1.2 times the limit)
|
Apr 1, 2012 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 19.2 pCi/L, federal limit 5 pCi/L (3.8 times the limit)
|
Jan 1, 2012 | Resolved |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 19.03 pCi/L, federal limit 15 pCi/L (1.3 times the limit)
|
Jan 1, 2012 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 18.35 pCi/L, federal limit 5 pCi/L (3.7 times the limit)
|
Oct 1, 2011 | Resolved |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 18.33 pCi/L, federal limit 15 pCi/L (1.2 times the limit)
|
Oct 1, 2011 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 18.43 pCi/L, federal limit 5 pCi/L (3.7 times the limit)
|
Jul 1, 2011 | Resolved |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 18.6 pCi/L, federal limit 15 pCi/L (1.2 times the limit)
|
Jul 1, 2011 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 17.03 pCi/L, federal limit 5 pCi/L (3.4 times the limit)
|
Apr 1, 2011 | Resolved |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 19.5 pCi/L, federal limit 15 pCi/L (1.3 times the limit)
|
Apr 1, 2011 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 16 pCi/L, federal limit 5 pCi/L (3.2 times the limit)
|
Jan 1, 2011 | Resolved |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 19.15 pCi/L, federal limit 15 pCi/L (1.3 times the limit)
|
Jan 1, 2011 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 16.23 pCi/L, federal limit 5 pCi/L (3.2 times the limit)
|
Oct 1, 2010 | Resolved |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 19.2 pCi/L, federal limit 15 pCi/L (1.3 times the limit)
|
Oct 1, 2010 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 16.76 pCi/L, federal limit 5 pCi/L (3.4 times the limit)
|
Jul 1, 2010 | Resolved |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 20.83 pCi/L, federal limit 15 pCi/L (1.4 times the limit)
|
Jul 1, 2010 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 18.98 pCi/L, federal limit 5 pCi/L (3.8 times the limit)
|
Apr 1, 2010 | Resolved |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 21.65 pCi/L, federal limit 15 pCi/L (1.4 times the limit)
|
Apr 1, 2010 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 18.525 pCi/L, federal limit 5 pCi/L (3.7 times the limit)
|
Jan 1, 2010 | Resolved |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 21.375 pCi/L, federal limit 15 pCi/L (1.4 times the limit)
|
Jan 1, 2010 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 19.45 pCi/L, federal limit 5 pCi/L (3.9 times the limit)
|
Oct 1, 2009 | Resolved |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 22.75 pCi/L, federal limit 15 pCi/L (1.5 times the limit)
|
Oct 1, 2009 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 19.1 pCi/L, federal limit 5 pCi/L (3.8 times the limit)
|
Jul 1, 2009 | Resolved |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 19.38 pCi/L, federal limit 15 pCi/L (1.3 times the limit)
|
Jul 1, 2009 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 19.27 pCi/L, federal limit 5 pCi/L (3.9 times the limit)
|
Apr 1, 2009 | Resolved |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 17.5 pCi/L, federal limit 15 pCi/L (1.2 times the limit)
|
Apr 1, 2009 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 18.9 pCi/L, federal limit 5 pCi/L (3.8 times the limit)
|
Jan 1, 2009 | Resolved |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 17.33 pCi/L, federal limit 15 pCi/L (1.2 times the limit)
|
Jan 1, 2009 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 17.98 pCi/L, federal limit 5 pCi/L (3.6 times the limit)
|
Oct 1, 2008 | Archived |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 17.68 pCi/L, federal limit 15 pCi/L (1.2 times the limit)
|
Oct 1, 2008 | Archived |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 20.28 pCi/L, federal limit 15 pCi/L (1.4 times the limit)
|
Jul 1, 2008 | Archived |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 17.08 pCi/L, federal limit 5 pCi/L (3.4 times the limit)
|
Jul 1, 2008 | Archived |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 17.08 pCi/L, federal limit 5 pCi/L (3.4 times the limit)
|
Apr 1, 2008 | Resolved |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 21.6 pCi/L, federal limit 15 pCi/L (1.4 times the limit)
|
Apr 1, 2008 | Archived |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 15.85 pCi/L, federal limit 5 pCi/L (3.2 times the limit)
|
Jan 1, 2008 | Resolved |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 21.1 pCi/L, federal limit 15 pCi/L (1.4 times the limit)
|
Jan 1, 2008 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 15.58 pCi/L, federal limit 5 pCi/L (3.1 times the limit)
|
Oct 1, 2007 | Resolved |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 22.8 pCi/L, federal limit 15 pCi/L (1.5 times the limit)
|
Oct 1, 2007 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 16.08 pCi/L, federal limit 5 pCi/L (3.2 times the limit)
|
Jul 1, 2007 | Resolved |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 20.63 pCi/L, federal limit 15 pCi/L (1.4 times the limit)
|
Jul 1, 2007 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 15.73 pCi/L, federal limit 5 pCi/L (3.1 times the limit)
|
Apr 1, 2007 | Resolved |
|
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 23.35 pCi/L, federal limit 15 pCi/L (1.6 times the limit)
|
Apr 1, 2007 | Resolved |
|
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 17.73 pCi/L, federal limit 5 pCi/L (3.5 times the limit)
|
Jan 1, 2007 | Resolved |
33 older violations are not listed here. EPA ECHO has the complete list.
Enforcement actions
Missouri regulators took 3 formal enforcement actions against Mineral Point PWS between 2005 and 2011. The most recent was a compliance order with a penalty in September 2011.
| Date | By | Action | Violations covered |
|---|---|---|---|
| Sep 21, 2011 | Missouri | Compliance order with a penalty | 58 violations (48 health-based): Gross Alpha, Excl. Radon and U, Combined Radium (-226 and -228), Public Notice |
| Nov 6, 2007 | Missouri | Signed compliance agreement | 32 violations (24 health-based): Gross Alpha, Excl. Radon and U, Combined Radium (-226 and -228) |
| Dec 6, 2005 | Missouri | Signed compliance agreement | 38 violations (33 health-based): Gross Alpha, Excl. Radon and U, Combined Radium (-226 and -228) |
What the violations mean
Groundwater Rule
1 incidentThe system did not complete a treatment step or action that the Groundwater Rule requires (a treatment technique violation).
The utility had to notify customers about this violation.
Combined Radium (-226 and -228)
1 incidentTest results for Combined Radium (-226 and -228) were above the federal limit (a maximum contaminant level violation).
The utility had to notify customers about this violation.
Where the water comes from
Mineral Point PWS draws water from 1 well.
Annual water quality report
Mineral Point PWS must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.
Systems serving 500 or fewer people may meet the rule by telling customers the report is available on request, so you may need to ask Mineral Point PWS for a copy.
Find a posted report with EPA's Consumer Confidence Report search
Testing your own water
To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Missouri.
Certified drinking water labs by state EPA guidance for private wells