Public water system record

Poplar Bluff PWS

Serves Poplar Bluff, Butler County, MO · 17,043 people served

Federal records show 22 health-based violations and no monitoring/reporting issues for Poplar Bluff PWS in the last ten years. The most serious issue in this window was a Haloacetic Acids (HAA5) violation that EPA lists as archived, not resolved.

  • MO4010656
  • POPLAR BLUFF
  • MO
  • 17,043 served

System profile

Source water Surface water
ZIP 63901
EPA system ID MO4010656

Verify this system on EPA ECHO →

Health-based violations, last 10 years
22
Resolved
21
Unresolved
0
Archived by EPA
1
Any acute record
No
Monitoring issues, last 10 years
0

Key facts

  • Poplar Bluff PWS draws water from 2 wells, 1 surface water intake and 1 reservoir.
  • Highest measured level in the last 10 years: Total Trihalomethanes (TTHMs), 92 µg/L, federal limit 80 µg/L (1.2 times the limit), 2016.
  • Record on file since 1988, with 31 health-based violations before October 19, 2016.
  • Lead pipe inventory: 0 lead and 688 unknown out of 7,865 service lines.

Check whether Poplar Bluff PWS serves your address

Address suggestions by Mapbox

Health-based violations

Since October 2016

Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.

Contaminant Rule family Start date Status Acute
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 61.18 µg/L, federal limit 60 µg/L (at or just above the limit)
220 Jul 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 81 µg/L, federal limit 80 µg/L (at or just above the limit)
220 Apr 1, 2017 Resolved No
Long Term 2 Enhanced Surface Water Treatment Rule
Treatment technique failure
120 Mar 1, 2017 Resolved No
Long Term 2 Enhanced Surface Water Treatment Rule
Treatment technique failure
120 Feb 1, 2017 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 86 µg/L, federal limit 80 µg/L (1.1 times the limit)
220 Jan 1, 2017 Resolved No
Long Term 2 Enhanced Surface Water Treatment Rule
Treatment technique failure
120 Jan 1, 2017 Resolved No
Long Term 2 Enhanced Surface Water Treatment Rule
Treatment technique failure
120 Dec 1, 2016 Resolved No
Long Term 2 Enhanced Surface Water Treatment Rule
Treatment technique failure
120 Nov 1, 2016 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 92 µg/L, federal limit 80 µg/L (1.2 times the limit)
220 Oct 1, 2016 Resolved No
Long Term 2 Enhanced Surface Water Treatment Rule
Treatment technique failure
120 Oct 1, 2016 Resolved No
Long Term 2 Enhanced Surface Water Treatment Rule
Treatment technique failure
120 Sep 1, 2016 Resolved No
Long Term 2 Enhanced Surface Water Treatment Rule
Treatment technique failure
120 Aug 1, 2016 Resolved No
Long Term 2 Enhanced Surface Water Treatment Rule
Treatment technique failure
120 Jul 1, 2016 Resolved No
Long Term 2 Enhanced Surface Water Treatment Rule
Treatment technique failure
120 Jun 1, 2016 Resolved No
Long Term 2 Enhanced Surface Water Treatment Rule
Treatment technique failure
120 May 1, 2016 Resolved No
Long Term 2 Enhanced Surface Water Treatment Rule
Treatment technique failure
120 Apr 1, 2016 Resolved No
Long Term 2 Enhanced Surface Water Treatment Rule
Treatment technique failure
120 Mar 1, 2016 Resolved No
Long Term 2 Enhanced Surface Water Treatment Rule
Treatment technique failure
120 Feb 1, 2016 Resolved No
Long Term 2 Enhanced Surface Water Treatment Rule
Treatment technique failure
120 Jan 1, 2016 Resolved No
Long Term 2 Enhanced Surface Water Treatment Rule
Treatment technique failure
120 Dec 1, 2015 Resolved No
Long Term 2 Enhanced Surface Water Treatment Rule
Treatment technique failure
120 Nov 1, 2015 Resolved No
Long Term 2 Enhanced Surface Water Treatment Rule
Treatment technique failure
120 Oct 1, 2015 Resolved No

Full record since 1988

EPA's records for Poplar Bluff PWS go back to 1988. Before October 19, 2016 they list 31 health-based violations (29 resolved, 2 archived by EPA without a recorded fix) and 32 monitoring or reporting violations.

Violations that began in Health-based Monitoring and reporting
1980s 0 32
1990s 1 0
2000s 7 0
2010 to October 18, 2016 23 0
October 19, 2016 to 2019 7 0
2020s 1 0

Most recent health-based violation before October 19, 2016: Total Trihalomethanes (TTHMs), began October 2016, Resolved.

Show all 31 health-based violations before October 19, 2016
Contaminant Start date Status
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 92 µg/L, federal limit 80 µg/L (1.2 times the limit)
Oct 1, 2016 Resolved
Long Term 2 Enhanced Surface Water Treatment Rule
Treatment technique failure
Oct 1, 2016 Resolved
Long Term 2 Enhanced Surface Water Treatment Rule
Treatment technique failure
Sep 1, 2016 Resolved
Long Term 2 Enhanced Surface Water Treatment Rule
Treatment technique failure
Aug 1, 2016 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 95 µg/L, federal limit 80 µg/L (1.2 times the limit)
Jul 1, 2016 Resolved
Long Term 2 Enhanced Surface Water Treatment Rule
Treatment technique failure
Jul 1, 2016 Resolved
Long Term 2 Enhanced Surface Water Treatment Rule
Treatment technique failure
Jun 1, 2016 Resolved
Long Term 2 Enhanced Surface Water Treatment Rule
Treatment technique failure
May 1, 2016 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 100 µg/L, federal limit 80 µg/L (1.3 times the limit)
Apr 1, 2016 Resolved
Long Term 2 Enhanced Surface Water Treatment Rule
Treatment technique failure
Apr 1, 2016 Resolved
Long Term 2 Enhanced Surface Water Treatment Rule
Treatment technique failure
Mar 1, 2016 Resolved
Long Term 2 Enhanced Surface Water Treatment Rule
Treatment technique failure
Feb 1, 2016 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 85 µg/L, federal limit 80 µg/L (1.1 times the limit)
Jan 1, 2016 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 70 µg/L, federal limit 60 µg/L (1.2 times the limit)
Jan 1, 2016 Resolved
Long Term 2 Enhanced Surface Water Treatment Rule
Treatment technique failure
Jan 1, 2016 Resolved
Long Term 2 Enhanced Surface Water Treatment Rule
Treatment technique failure
Dec 1, 2015 Resolved
Long Term 2 Enhanced Surface Water Treatment Rule
Treatment technique failure
Nov 1, 2015 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 73 µg/L, federal limit 60 µg/L (1.2 times the limit)
Oct 1, 2015 Resolved
Long Term 2 Enhanced Surface Water Treatment Rule
Treatment technique failure
Oct 1, 2015 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 70 µg/L, federal limit 60 µg/L (1.2 times the limit)
Jul 1, 2015 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 64.83 µg/L, federal limit 60 µg/L (1.1 times the limit)
Apr 1, 2015 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 62.23 µg/L, federal limit 60 µg/L (at or just above the limit)
Apr 1, 2010 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 69.44 µg/L, federal limit 60 µg/L (1.2 times the limit)
Jan 1, 2010 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 72.84 µg/L, federal limit 60 µg/L (1.2 times the limit)
Oct 1, 2009 Resolved
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
Jun 1, 2002 Resolved
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
Jun 1, 2002 Resolved
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
May 1, 2002 Resolved
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
May 1, 2002 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Jan 1, 2002 Resolved
Total Coliform
Contaminant limit exceeded
Apr 1, 2001 Archived
Total Coliform
Contaminant limit exceeded
Aug 1, 1993 Archived

What the violations mean

Long Term 2 Enhanced Surface Water Treatment Rule

18 incidents

The system failed required surface water treatment or filtration standards

Untreated or inadequately treated surface water can contain bacteria and viruses

Total Trihalomethanes (TTHMs)

3 incidents

Disinfection byproduct levels exceeded the federal limit

Long-term TTHM exposure may increase bladder cancer risk

Haloacetic Acids (HAA5)

1 incident

Haloacetic acid byproducts exceeded the federal limit

Long-term exposure to HAAs may increase cancer risk

Where the water comes from

Poplar Bluff PWS draws water from 2 wells, 1 surface water intake and 1 reservoir.

Annual water quality report

Poplar Bluff PWS must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.

Systems serving 10,000 or more people must mail or deliver the report to every customer, and from 2027 they must send it twice a year.

Find a posted report with EPA's Consumer Confidence Report search

Testing your own water

To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Missouri.