Public water system record
Boonville PWS
Serves Boonville, Cooper County, MO · 7,964 people served
Federal records show 7 health-based violations and no monitoring/reporting issues for Boonville PWS in the last ten years. The most serious issue in this window was a resolved Total Trihalomethanes (TTHMs) violation.
System profile
- Health-based violations, last 10 years
- 7
- Resolved
- 7
- Unresolved
- 0
- Any acute record
- No
- Monitoring issues, last 10 years
- 0
Key facts
- Boonville PWS draws water from 1 surface water intake and 1 reservoir.
- Highest measured level in the last 10 years: Total Trihalomethanes (TTHMs), 99 µg/L, federal limit 80 µg/L (1.2 times the limit), 2020.
- Record on file since 1989, with 12 health-based violations before October 19, 2016.
- Lead pipe inventory: 0 lead and 1,134 unknown out of 3,917 service lines.
Check whether Boonville PWS serves your address
Health-based violations
Since October 2016Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.
| Contaminant | Rule family | Start date | Status | Acute |
|---|---|---|---|---|
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 99 µg/L, federal limit 80 µg/L (1.2 times the limit)
|
220 | Jan 1, 2020 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 95 µg/L, federal limit 80 µg/L (1.2 times the limit)
|
220 | Oct 1, 2019 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 93 µg/L, federal limit 80 µg/L (1.2 times the limit)
|
220 | Jul 1, 2019 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 99 µg/L, federal limit 80 µg/L (1.2 times the limit)
|
220 | Apr 1, 2019 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 87 µg/L, federal limit 80 µg/L (1.1 times the limit)
|
220 | Jan 1, 2017 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 89 µg/L, federal limit 80 µg/L (1.1 times the limit)
|
220 | Oct 1, 2016 | Resolved | No |
|
Long Term 2 Enhanced Surface Water Treatment Rule
Treatment technique failure
|
120 | Oct 1, 2016 | Resolved | No |
Full record since 1989
EPA's records for Boonville PWS go back to 1989. Before October 19, 2016 they list 12 health-based violations (12 resolved) and 23 monitoring or reporting violations.
| Violations that began in | Health-based | Monitoring and reporting |
|---|---|---|
| 1980s | 0 | 22 |
| 1990s | 0 | 1 |
| 2000s | 5 | 0 |
| 2010 to October 18, 2016 | 7 | 0 |
| October 19, 2016 to 2019 | 4 | 0 |
| 2020s | 1 | 0 |
Most recent health-based violation before October 19, 2016: Total Trihalomethanes (TTHMs), began October 2016, Resolved.
Show all 12 health-based violations before October 19, 2016
| Contaminant | Start date | Status |
|---|---|---|
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 89 µg/L, federal limit 80 µg/L (1.1 times the limit)
|
Oct 1, 2016 | Resolved |
|
Long Term 2 Enhanced Surface Water Treatment Rule
Treatment technique failure
|
Oct 1, 2016 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 94 µg/L, federal limit 80 µg/L (1.2 times the limit)
|
Jul 1, 2016 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 94 µg/L, federal limit 80 µg/L (1.2 times the limit)
|
Apr 1, 2016 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 91 µg/L, federal limit 80 µg/L (1.1 times the limit)
|
Jan 1, 2016 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 87 µg/L, federal limit 80 µg/L (1.1 times the limit)
|
Oct 1, 2015 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 82 µg/L, federal limit 80 µg/L (at or just above the limit)
|
Jul 1, 2015 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
|
Oct 1, 2005 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
|
Jul 1, 2005 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
|
Apr 1, 2005 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
|
Jan 1, 2005 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
|
Oct 1, 2004 | Resolved |
What the violations mean
Total Trihalomethanes (TTHMs)
6 incidentsDisinfection byproduct levels exceeded the federal limit
Long-term TTHM exposure may increase bladder cancer risk
Long Term 2 Enhanced Surface Water Treatment Rule
1 incidentThe system failed required surface water treatment or filtration standards
Untreated or inadequately treated surface water can contain bacteria and viruses
Where the water comes from
Boonville PWS draws water from 1 surface water intake and 1 reservoir. 1 other community water system buys water from Boonville PWS.
Community systems that buy water from it
- Cooper County Consolidated PWSD # 1 Boonville, MO
Annual water quality report
Boonville PWS must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.
Where the state allows it, systems serving fewer than 10,000 people may publish the report in a local newspaper or news site instead of mailing it, and must provide a copy on request.
Find a posted report with EPA's Consumer Confidence Report search
Testing your own water
To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Missouri.
Certified drinking water labs by state EPA guidance for private wells