Public water system record
Wyaconda PWS
Serves Wyaconda, Clark County, MO · 209 people served
Federal records show no health-based violations and 1 monitoring/reporting issue for Wyaconda PWS in the last ten years.
System profile
- Health-based violations, last 10 years
- 0
- Resolved
- 0
- Unresolved
- 0
- Any acute record
- No
- Monitoring issues, last 10 years
- 1
Key facts
- Wyaconda PWS buys its water from Clark County Cons PWSD 1.
- Most recent formal enforcement: signed compliance agreement by Missouri, February 2009.
- Record on file since 2004, with 21 health-based violations before October 19, 2016.
- Lead pipe inventory: 0 lead and 0 unknown out of 176 service lines.
Check whether Wyaconda PWS serves your address
Health-based violations
Since October 2016Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.
None since October 2016.
Monitoring and reporting issues
Since October 2016Missed tests or reports, not contaminants found above a limit.
| Issue | Start date | Status |
|---|---|---|
|
Revised Total Coliform Rule
Monitoring violation
|
Feb 1, 2022 | Resolved |
Full record since 2004
EPA's records for Wyaconda PWS go back to 2004. Before October 19, 2016 they list 21 health-based violations (21 resolved) and 19 monitoring or reporting violations.
| Violations that began in | Health-based | Monitoring and reporting |
|---|---|---|
| 2000s | 21 | 16 |
| 2010 to October 18, 2016 | 0 | 3 |
| 2020s | 0 | 1 |
Most recent health-based violation before October 19, 2016: Interim Enhanced Surface Water Treatment Rule (acute), began March 2009, Resolved.
Show all 21 health-based violations before October 19, 2016
| Contaminant | Start date | Status |
|---|---|---|
|
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
|
Mar 1, 2009 | Resolved |
|
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
|
Feb 1, 2009 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 105.47 µg/L, federal limit 60 µg/L (1.8 times the limit)
|
Jan 1, 2009 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 183.83 µg/L, federal limit 80 µg/L (2.3 times the limit)
|
Jan 1, 2009 | Resolved |
|
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
|
Jan 1, 2009 | Resolved |
|
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
|
Dec 1, 2008 | Resolved |
|
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
|
Nov 1, 2008 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 77.54 µg/L, federal limit 60 µg/L (1.3 times the limit)
|
Oct 1, 2008 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 146.45 µg/L, federal limit 80 µg/L (1.8 times the limit)
|
Oct 1, 2008 | Resolved |
|
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
|
Oct 1, 2008 | Resolved |
|
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
|
Sep 1, 2008 | Resolved |
|
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
|
Aug 1, 2008 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 65.78 µg/L, federal limit 60 µg/L (1.1 times the limit)
|
Jul 1, 2008 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 123.21 µg/L, federal limit 80 µg/L (1.5 times the limit)
|
Jul 1, 2008 | Resolved |
|
CARBON, TOTAL
Treatment technique failure
|
Jan 1, 2008 | Resolved |
|
CARBON, TOTAL
Treatment technique failure
|
Oct 1, 2007 | Resolved |
|
Atrazine
Contaminant limit exceeded
|
Jan 1, 2006 | Resolved |
|
Atrazine
Contaminant limit exceeded
|
Oct 1, 2005 | Resolved |
|
Atrazine
Contaminant limit exceeded
|
Jul 1, 2005 | Resolved |
|
Atrazine
Contaminant limit exceeded
|
Apr 1, 2005 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
|
Jan 1, 2005 | Resolved |
Enforcement actions
Missouri regulators took 1 formal enforcement action against Wyaconda PWS in 2009. The most recent was a signed compliance agreement in February 2009.
| Date | By | Action | Violations covered |
|---|---|---|---|
| Feb 10, 2009 | Missouri | Signed compliance agreement | 21 violations (14 health-based): CARBON, TOTAL, Interim Enhanced Surface Water Treatment Rule, Total Trihalomethanes (TTHMs), Haloacetic Acids (HAA5), Public Notice |
Where the water comes from
Wyaconda PWS buys its water from Clark County Cons PWSD 1. It lists no wells or intakes of its own.
Buys water from
- Clark County Cons PWSD 1 Williamstown, MO
Annual water quality report
Wyaconda PWS must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.
Systems serving 500 or fewer people may meet the rule by telling customers the report is available on request, so you may need to ask Wyaconda PWS for a copy.
Find a posted report with EPA's Consumer Confidence Report search
Testing your own water
To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Missouri.
Certified drinking water labs by state EPA guidance for private wells