Public water system record

Bucklin PWS

Serves Bucklin and New Cambria, Linn County and Macon County, MO · 408 people served

Federal records show no health-based violations and 6 monitoring/reporting issues for Bucklin PWS in the last ten years. At least one of these issues remains unresolved.

  • MO2010112
  • BUCKLIN
  • MO
  • 408 served

System profile

Source water Purchased surface water
ZIP 64631
EPA system ID MO2010112

Verify this system on EPA ECHO →

Health-based violations, last 10 years
0
Resolved
0
Unresolved
0
Any acute record
No
Monitoring issues, last 10 years
6

Key facts

  • Bucklin PWS buys its water from Chariton Linn County PWSD 3.
  • Most recent formal enforcement: signed compliance agreement by Missouri, October 2008.
  • Record on file since 1997, with 27 health-based violations before October 19, 2016.
  • Lead pipe inventory: 1 lead and 0 unknown out of 193 service lines.

Check whether Bucklin PWS serves your address

Address suggestions by Mapbox

Health-based violations

Since October 2016

Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.

None since October 2016.

Monitoring and reporting issues

Since October 2016

Missed tests or reports, not contaminants found above a limit.

Issue Start date Status
Revised Total Coliform Rule
Monitoring violation
Aug 1, 2025 Resolved
Lead and Copper Rule
Monitoring and reporting
Oct 1, 2024 Active
Consumer Confidence Rule
OTHER
Jul 1, 2024 Resolved
Consumer Confidence Rule
OTHER
Jul 1, 2023 Resolved
Consumer Confidence Rule
OTHER
Jul 1, 2021 Resolved
Revised Total Coliform Rule
Monitoring violation
Sep 1, 2017 Resolved

Full record since 1997

EPA's records for Bucklin PWS go back to 1997. Before October 19, 2016 they list 27 health-based violations (27 resolved) and 5 monitoring or reporting violations.

Violations that began in Health-based Monitoring and reporting
1990s 2 0
2000s 13 0
2010 to October 18, 2016 12 5
October 19, 2016 to 2019 0 1
2020s 0 5

Most recent health-based violation before October 19, 2016: Total Coliform, began August 2015, Resolved.

Show all 27 health-based violations before October 19, 2016
Contaminant Start date Status
Total Coliform
Contaminant limit exceeded
Aug 1, 2015 Resolved
Total Coliform
Contaminant limit exceeded
Aug 1, 2014 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 100.1 µg/L, federal limit 80 µg/L (1.3 times the limit)
Jan 1, 2012 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 96.23 µg/L, federal limit 80 µg/L (1.2 times the limit)
Oct 1, 2011 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 96.94 µg/L, federal limit 80 µg/L (1.2 times the limit)
Jul 1, 2011 Resolved
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
Jul 1, 2011 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 84.44 µg/L, federal limit 80 µg/L (1.1 times the limit)
Apr 1, 2011 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 83.47 µg/L, federal limit 80 µg/L (at or just above the limit)
Jan 1, 2011 Resolved
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
Sep 1, 2010 Resolved
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
Aug 1, 2010 Resolved
Interim Enhanced Surface Water Treatment Rule (acute)
Treatment technique failure
Jul 1, 2010 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 65.48 µg/L, federal limit 60 µg/L (1.1 times the limit)
Jan 1, 2010 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 69.73 µg/L, federal limit 60 µg/L (1.2 times the limit)
Oct 1, 2009 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 82.12 µg/L, federal limit 60 µg/L (1.4 times the limit)
Jul 1, 2009 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 92.75 µg/L, federal limit 60 µg/L (1.5 times the limit)
Apr 1, 2009 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 82.51 µg/L, federal limit 60 µg/L (1.4 times the limit)
Jan 1, 2009 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 82.53 µg/L, federal limit 60 µg/L (1.4 times the limit)
Oct 1, 2008 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 75.15 µg/L, federal limit 60 µg/L (1.3 times the limit)
Jul 1, 2008 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 61.96 µg/L, federal limit 60 µg/L (at or just above the limit)
Apr 1, 2008 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 64.35 µg/L, federal limit 60 µg/L (1.1 times the limit)
Jan 1, 2008 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 80.59 µg/L, federal limit 60 µg/L (1.3 times the limit)
Oct 1, 2007 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 78.05 µg/L, federal limit 60 µg/L (1.3 times the limit)
Jul 1, 2007 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 81.21 µg/L, federal limit 60 µg/L (1.4 times the limit)
Apr 1, 2007 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 78.45 µg/L, federal limit 60 µg/L (1.3 times the limit)
Jan 1, 2007 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 66.32 µg/L, federal limit 60 µg/L (1.1 times the limit)
Oct 1, 2006 Resolved
Atrazine
Contaminant limit exceeded
Jul 1, 1997 Resolved
Atrazine
Contaminant limit exceeded
Jan 1, 1997 Resolved

Enforcement actions

Missouri regulators took 1 formal enforcement action against Bucklin PWS in 2008. The most recent was a signed compliance agreement in October 2008.

Date By Action Violations covered
Oct 9, 2008 Missouri Signed compliance agreement 12 violations (12 health-based): Haloacetic Acids (HAA5)

Where the water comes from

Bucklin PWS buys its water from Chariton Linn County PWSD 3. EPA also lists 2 surface water intakes and 2 reservoirs, all for emergency, seasonal or other part-time use.

Buys water from

Annual water quality report

Bucklin PWS must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.

Systems serving 500 or fewer people may meet the rule by telling customers the report is available on request, so you may need to ask Bucklin PWS for a copy.

Find a posted report with EPA's Consumer Confidence Report search

Testing your own water

To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Missouri.