Public water system record
US Coast Guard Station-Jonesport
On record as serving Washington County, ME · Serves 25 people
Federal records show 18 health-based violations and 5 monitoring/reporting issues for US Coast Guard Station-Jonesport in the last ten years. The most serious issue in this window was a Interim Enhanced Surface Water Treatment Rule violation that EPA lists as archived, not resolved.
System profile
- Health-based violations, last 10 years
- 18
- Resolved
- 15
- Unresolved
- 0
- Archived by EPA
- 3
- Any acute record
- Yes
- Monitoring issues, last 10 years
- 5
Key facts
- US Coast Guard Station-Jonesport draws water from 1 spring.
- Highest measured level in the last 10 years: Haloacetic Acids (HAA5), 0.082 mg/L, federal limit 0.06 mg/L (1.4 times the limit), 2024.
- Record on file since 1995, with 4 health-based violations before October 19, 2016.
- Lead pipe inventory: 0 lead and 0 unknown out of 3 service lines.
Check whether US Coast Guard Station-Jonesport serves your address
Health-based violations
Since October 2016Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.
| Contaminant | Rule family | Start date | Status | Acute |
|---|---|---|---|---|
|
Interim Enhanced Surface Water Treatment Rule
Treatment technique failure
|
120 | Nov 1, 2025 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
Yes |
|
Surface Water Treatment Rule
Treatment technique failure
|
120 | Nov 1, 2025 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Interim Enhanced Surface Water Treatment Rule
Treatment technique failure
|
120 | Oct 1, 2025 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
Yes |
|
Surface Water Treatment Rule
Treatment technique failure
|
120 | Jun 1, 2025 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.084 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
220 | Oct 1, 2024 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.075 mg/L, federal limit 0.06 mg/L (1.3 times the limit)
|
220 | Jul 1, 2024 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.089 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
220 | Jul 1, 2024 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.086 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
220 | Apr 1, 2024 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.082 mg/L, federal limit 0.06 mg/L (1.4 times the limit)
|
220 | Apr 1, 2024 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.084 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
220 | Jan 1, 2024 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.079 mg/L, federal limit 0.06 mg/L (1.3 times the limit)
|
220 | Jan 1, 2024 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.073 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
|
220 | Oct 1, 2023 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.081 mg/L, federal limit 0.08 mg/L (at or just above the limit)
|
220 | Jan 1, 2023 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.086 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
220 | Oct 1, 2022 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.093 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
220 | Jul 1, 2022 | Resolved | No |
|
Surface Water Treatment Rule
Treatment technique failure
|
120 | Jul 1, 2020 | Resolved | No |
|
Surface Water Treatment Rule
Treatment technique failure
|
120 | Aug 1, 2019 | Resolved | No |
|
Lead and Copper Rule
Treatment technique failure
|
350 | Apr 1, 2018 | Resolved | No |
Monitoring and reporting issues
Since October 2016Missed tests or reports, not contaminants found above a limit.
| Issue | Start date | Status |
|---|---|---|
|
Lead and Copper Rule
Monitoring and reporting
|
Oct 1, 2022 | Resolved |
|
Lead and Copper Rule
Monitoring and reporting
|
Jul 1, 2020 | Resolved |
|
Lead and Copper Rule
Monitoring and reporting
|
Jul 1, 2020 | Resolved |
|
Lead and Copper Rule
Monitoring and reporting
|
Apr 1, 2019 | Resolved |
|
Revised Total Coliform Rule
Monitoring violation
|
Dec 1, 2016 | Resolved |
Full record since 1995
EPA's records for US Coast Guard Station-Jonesport go back to 1995. Before October 19, 2016 they list 4 health-based violations (4 resolved) and 7 monitoring or reporting violations.
| Violations that began in | Health-based | Monitoring and reporting |
|---|---|---|
| 1990s | 1 | 2 |
| 2000s | 1 | 1 |
| 2010 to October 18, 2016 | 2 | 4 |
| October 19, 2016 to 2019 | 2 | 2 |
| 2020s | 16 | 3 |
Most recent health-based violation before October 19, 2016: Surface Water Treatment Rule, began December 2011, Resolved.
Show all 4 health-based violations before October 19, 2016
| Contaminant | Start date | Status |
|---|---|---|
|
Surface Water Treatment Rule
Treatment technique failure
|
Dec 1, 2011 | Resolved |
|
Surface Water Treatment Rule
Treatment technique failure
|
Nov 1, 2011 | Resolved |
|
Surface Water Treatment Rule
Treatment technique failure
|
Mar 1, 2003 | Resolved |
|
Surface Water Treatment Rule
Treatment technique failure
|
Mar 3, 1997 | Resolved |
What the violations mean
Total Trihalomethanes (TTHMs)
7 incidentsDisinfection byproduct levels exceeded the federal limit
Long-term TTHM exposure may increase bladder cancer risk
Surface Water Treatment Rule
4 incidentsThe system did not complete a treatment step or action that the Surface Water Treatment Rule requires (a treatment technique violation).
The utility had to notify customers about each of these violations.
Haloacetic Acids (HAA5)
4 incidentsHaloacetic acid byproducts exceeded the federal limit
Long-term exposure to HAAs may increase cancer risk
Interim Enhanced Surface Water Treatment Rule
2 incidentsThe system did not meet a filtration or treatment requirement for surface water
Inadequate treatment of surface water can let pathogens such as Cryptosporidium and Giardia through
Lead and Copper Rule
1 incidentThe system did not complete a treatment step or action that the Lead and Copper Rule requires (a treatment technique violation).
The utility had to notify customers about this violation.
Where the water comes from
US Coast Guard Station-Jonesport draws water from 1 spring.
Annual water quality report
US Coast Guard Station-Jonesport must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.
Systems serving 500 or fewer people may meet the rule by telling customers the report is available on request, so you may need to ask US Coast Guard Station-Jonesport for a copy.
Find a posted report with EPA's Consumer Confidence Report search
Testing your own water
To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Maine.
Certified drinking water labs by state EPA guidance for private wells