Public water system record
Eagle Lake Water & Sewer District
Serves Eagle Lake, Aroostook County, ME · 585 people served
Federal records show no health-based violations and 2 monitoring/reporting issues for Eagle Lake Water & Sewer District in the last ten years.
System profile
- Health-based violations, last 10 years
- 0
- Resolved
- 0
- Unresolved
- 0
- Any acute record
- No
- Monitoring issues, last 10 years
- 2
Key facts
- Eagle Lake Water & Sewer District draws water from 2 wells.
- Most recent formal enforcement: signed compliance agreement by Maine, January 2010.
- Record on file since 2004, with 40 health-based violations before October 19, 2016.
- Lead pipe inventory: 0 lead and 0 unknown out of 283 service lines.
Check whether Eagle Lake Water & Sewer District serves your address
Health-based violations
Since October 2016Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.
None since October 2016.
Monitoring and reporting issues
Since October 2016Missed tests or reports, not contaminants found above a limit.
| Issue | Start date | Status |
|---|---|---|
|
Revised Total Coliform Rule
Monitoring violation
|
Nov 1, 2025 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
|
Consumer Confidence Rule
OTHER
|
Jul 1, 2021 | Resolved |
Full record since 2004
EPA's records for Eagle Lake Water & Sewer District go back to 2004. Before October 19, 2016 they list 40 health-based violations (40 resolved) and no monitoring or reporting violations.
| Violations that began in | Health-based | Monitoring and reporting |
|---|---|---|
| 2000s | 40 | 0 |
| 2020s | 0 | 2 |
Most recent health-based violation before October 19, 2016: Total Trihalomethanes (TTHMs), began April 2009, Resolved.
Show all 40 health-based violations before October 19, 2016
| Contaminant | Start date | Status |
|---|---|---|
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.084 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Apr 1, 2009 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.106 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
|
Jan 1, 2009 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.1229 mg/L, federal limit 0.08 mg/L (1.5 times the limit)
|
Oct 1, 2008 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.1206 mg/L, federal limit 0.08 mg/L (1.5 times the limit)
|
Jul 1, 2008 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.0703 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
|
Apr 1, 2008 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.0962 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
Apr 1, 2008 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.0885 mg/L, federal limit 0.06 mg/L (1.5 times the limit)
|
Jan 1, 2008 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
|
Jan 1, 2008 | Resolved |
|
Surface Water Treatment Rule
Treatment technique failure
|
Jan 1, 2008 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.1036 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
|
Oct 1, 2007 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.1035 mg/L, federal limit 0.06 mg/L (1.7 times the limit)
|
Oct 1, 2007 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.1108 mg/L, federal limit 0.08 mg/L (1.4 times the limit)
|
Jul 1, 2007 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.1585 mg/L, federal limit 0.06 mg/L (2.6 times the limit)
|
Jul 1, 2007 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.125 mg/L, federal limit 0.06 mg/L (2.1 times the limit)
|
Apr 1, 2007 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.128 mg/L, federal limit 0.08 mg/L (1.6 times the limit)
|
Apr 1, 2007 | Resolved |
|
Surface Water Treatment Rule
Treatment technique failure
|
Jan 1, 2007 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.121 mg/L, federal limit 0.08 mg/L (1.5 times the limit)
|
Jan 1, 2007 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.123 mg/L, federal limit 0.06 mg/L (2.1 times the limit)
|
Jan 1, 2007 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.12 mg/L, federal limit 0.08 mg/L (1.5 times the limit)
|
Oct 1, 2006 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.133 mg/L, federal limit 0.06 mg/L (2.2 times the limit)
|
Oct 1, 2006 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.14 mg/L, federal limit 0.08 mg/L (1.8 times the limit)
|
Jul 1, 2006 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.156 mg/L, federal limit 0.06 mg/L (2.6 times the limit)
|
Jul 1, 2006 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.135 mg/L, federal limit 0.08 mg/L (1.7 times the limit)
|
Apr 1, 2006 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.171 mg/L, federal limit 0.06 mg/L (2.9 times the limit)
|
Apr 1, 2006 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.13925 mg/L, federal limit 0.08 mg/L (1.7 times the limit)
|
Jan 1, 2006 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.185 mg/L, federal limit 0.06 mg/L (3.1 times the limit)
|
Jan 1, 2006 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.1395 mg/L, federal limit 0.08 mg/L (1.7 times the limit)
|
Oct 1, 2005 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.15875 mg/L, federal limit 0.06 mg/L (2.6 times the limit)
|
Oct 1, 2005 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.118 mg/L, federal limit 0.08 mg/L (1.5 times the limit)
|
Jul 1, 2005 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.13575 mg/L, federal limit 0.06 mg/L (2.3 times the limit)
|
Jul 1, 2005 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.122 mg/L, federal limit 0.06 mg/L (2 times the limit)
|
Apr 1, 2005 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.1225 mg/L, federal limit 0.08 mg/L (1.5 times the limit)
|
Apr 1, 2005 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.084 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Jan 1, 2005 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.105 mg/L, federal limit 0.06 mg/L (1.8 times the limit)
|
Jan 1, 2005 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.137 mg/L, federal limit 0.08 mg/L (1.7 times the limit)
|
Oct 1, 2004 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.179 mg/L, federal limit 0.06 mg/L (3 times the limit)
|
Oct 1, 2004 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.136 mg/L, federal limit 0.08 mg/L (1.7 times the limit)
|
Jul 1, 2004 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.187 mg/L, federal limit 0.06 mg/L (3.1 times the limit)
|
Jul 1, 2004 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.233 mg/L, federal limit 0.06 mg/L (3.9 times the limit)
|
Apr 1, 2004 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.254 mg/L, federal limit 0.06 mg/L (4.2 times the limit)
|
Jan 1, 2004 | Resolved |
Enforcement actions
Maine regulators took 6 formal enforcement actions against Eagle Lake Water & Sewer District between 2004 and 2010, filed as 7 records in EPA's data. The most recent was a signed compliance agreement in January 2010.
| Date | By | Action | Violations covered |
|---|---|---|---|
| Jan 7, 2010 | Maine | Signed compliance agreement | 38 violations (38 health-based): Haloacetic Acids (HAA5), Total Trihalomethanes (TTHMs) |
| May 1, 2008 | Maine | Signed compliance agreement | 40 violations (40 health-based): Haloacetic Acids (HAA5), Total Trihalomethanes (TTHMs), Surface Water Treatment Rule |
| Nov 29, 2007 | Maine | Signed compliance agreement | 6 violations (6 health-based): Haloacetic Acids (HAA5), Total Trihalomethanes (TTHMs) |
| Aug 9, 2006 | Maine | Compliance order (no penalty) | 20 violations (20 health-based): Haloacetic Acids (HAA5), Total Trihalomethanes (TTHMs) |
| Aug 8, 2006 | Maine | Signed compliance agreement | 44 violations (44 health-based): Haloacetic Acids (HAA5), Total Trihalomethanes (TTHMs) |
| Aug 27, 2004 | Maine | Compliance order (no penalty) | 3 violations (3 health-based): Total Trihalomethanes (TTHMs), Haloacetic Acids (HAA5) |
Where the water comes from
Eagle Lake Water & Sewer District draws water from 2 wells.
Annual water quality report
Eagle Lake Water & Sewer District must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.
Where the state allows it, systems serving fewer than 10,000 people may publish the report in a local newspaper or news site instead of mailing it, and must provide a copy on request.
Find a posted report with EPA's Consumer Confidence Report search
Testing your own water
To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Maine.
Certified drinking water labs by state EPA guidance for private wells