Public water system record

Town of Oakland

Serves Oakland and Mountain Lake Park, Garrett County, MD · 1,850 people served

Federal records show no health-based violations and 3 monitoring/reporting issues for Town of Oakland in the last ten years.

  • MD0110008
  • OAKLAND
  • MD
  • 1,850 served

System profile

Source water Surface water
ZIP 21550
EPA system ID MD0110008

Verify this system on EPA ECHO →

Health-based violations, last 10 years
0
Resolved
0
Unresolved
0
Any acute record
No
Monitoring issues, last 10 years
3

Key facts

  • Town of Oakland draws water from 1 surface water intake and 1 reservoir.
  • Most recent formal enforcement: administrative penalty by Maryland, January 2010.
  • Record on file since 2004, with 60 health-based violations before October 19, 2016.
  • Lead pipe inventory: 2 lead and 1,064 unknown out of 1,066 service lines.

Check whether Town of Oakland serves your address

Address suggestions by Mapbox

Health-based violations

Since October 2016

Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.

None since October 2016.

Monitoring and reporting issues

Since October 2016

Missed tests or reports, not contaminants found above a limit.

Issue Start date Status
LEAD AND COPPER RULE REVISIONS
RPT
Jul 2, 2025 Resolved
Cryptosporidium
Monitoring and reporting
Feb 1, 2019 Resolved
CARBON, TOTAL
Monitoring and reporting
Oct 1, 2016 Resolved

Full record since 2004

EPA's records for Town of Oakland go back to 2004. Before October 19, 2016 they list 60 health-based violations (60 resolved) and 2 monitoring or reporting violations.

Violations that began in Health-based Monitoring and reporting
2000s 34 0
2010 to October 18, 2016 26 2
October 19, 2016 to 2019 0 1
2020s 0 1

Most recent health-based violation before October 19, 2016: Total Trihalomethanes (TTHMs), began April 2013, Resolved.

Show all 60 health-based violations before October 19, 2016
Contaminant Start date Status
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 93.3 µg/L, federal limit 80 µg/L (1.2 times the limit)
Apr 1, 2013 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 125 µg/L, federal limit 80 µg/L (1.6 times the limit)
Jan 1, 2013 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 86.97 µg/L, federal limit 60 µg/L (1.4 times the limit)
Jan 1, 2013 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 122.5 µg/L, federal limit 80 µg/L (1.5 times the limit)
Oct 1, 2012 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 87.33 µg/L, federal limit 60 µg/L (1.5 times the limit)
Oct 1, 2012 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 91.58 µg/L, federal limit 60 µg/L (1.5 times the limit)
Jul 1, 2012 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 120.61 µg/L, federal limit 80 µg/L (1.5 times the limit)
Jul 1, 2012 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 84.05 µg/L, federal limit 60 µg/L (1.4 times the limit)
Apr 1, 2012 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 153.77 µg/L, federal limit 80 µg/L (1.9 times the limit)
Apr 1, 2012 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 133 µg/L, federal limit 80 µg/L (1.7 times the limit)
Jan 1, 2012 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 66.5 µg/L, federal limit 60 µg/L (1.1 times the limit)
Jan 1, 2012 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 64.04 µg/L, federal limit 60 µg/L (1.1 times the limit)
Oct 1, 2011 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 132.54 µg/L, federal limit 80 µg/L (1.7 times the limit)
Oct 1, 2011 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 156 µg/L, federal limit 80 µg/L (2 times the limit)
Jul 1, 2011 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 73 µg/L, federal limit 60 µg/L (1.2 times the limit)
Jul 1, 2011 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 140.21 µg/L, federal limit 80 µg/L (1.8 times the limit)
Apr 1, 2011 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 89 µg/L, federal limit 60 µg/L (1.5 times the limit)
Apr 1, 2011 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 93 µg/L, federal limit 60 µg/L (1.6 times the limit)
Jan 1, 2011 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 147 µg/L, federal limit 80 µg/L (1.8 times the limit)
Jan 1, 2011 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 97 µg/L, federal limit 60 µg/L (1.6 times the limit)
Oct 1, 2010 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 149 µg/L, federal limit 80 µg/L (1.9 times the limit)
Oct 1, 2010 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 86.9 µg/L, federal limit 60 µg/L (1.4 times the limit)
Jul 1, 2010 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 133.5 µg/L, federal limit 80 µg/L (1.7 times the limit)
Jul 1, 2010 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 105 µg/L, federal limit 80 µg/L (1.3 times the limit)
Apr 1, 2010 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 72 µg/L, federal limit 60 µg/L (1.2 times the limit)
Apr 1, 2010 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 103.2 µg/L, federal limit 80 µg/L (1.3 times the limit)
Jan 1, 2010 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 109 µg/L, federal limit 80 µg/L (1.4 times the limit)
Oct 1, 2009 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 64 µg/L, federal limit 60 µg/L (1.1 times the limit)
Oct 1, 2009 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 68 µg/L, federal limit 60 µg/L (1.1 times the limit)
Jul 1, 2009 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 103 µg/L, federal limit 80 µg/L (1.3 times the limit)
Jul 1, 2009 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 82 µg/L, federal limit 60 µg/L (1.4 times the limit)
Apr 1, 2009 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 94 µg/L, federal limit 80 µg/L (1.2 times the limit)
Apr 1, 2009 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 84 µg/L, federal limit 60 µg/L (1.4 times the limit)
Jan 1, 2009 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 88 µg/L, federal limit 80 µg/L (1.1 times the limit)
Jan 1, 2009 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 85 µg/L, federal limit 60 µg/L (1.4 times the limit)
Oct 1, 2008 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 84.01 µg/L, federal limit 80 µg/L (1.1 times the limit)
Oct 1, 2008 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 92 µg/L, federal limit 80 µg/L (1.2 times the limit)
Jul 1, 2008 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 84 µg/L, federal limit 60 µg/L (1.4 times the limit)
Jul 1, 2008 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 84 µg/L, federal limit 60 µg/L (1.4 times the limit)
Apr 1, 2008 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 96.8 µg/L, federal limit 80 µg/L (1.2 times the limit)
Apr 1, 2008 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 108.16 µg/L, federal limit 60 µg/L (1.8 times the limit)
Jan 1, 2008 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 128.18 µg/L, federal limit 80 µg/L (1.6 times the limit)
Jan 1, 2008 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 99 µg/L, federal limit 60 µg/L (1.7 times the limit)
Oct 1, 2007 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 125 µg/L, federal limit 80 µg/L (1.6 times the limit)
Oct 1, 2007 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 98 µg/L, federal limit 60 µg/L (1.6 times the limit)
Jul 1, 2007 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 119.9 µg/L, federal limit 80 µg/L (1.5 times the limit)
Jul 1, 2007 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 84 µg/L, federal limit 60 µg/L (1.4 times the limit)
Apr 1, 2007 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 123 µg/L, federal limit 80 µg/L (1.5 times the limit)
Apr 1, 2007 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 87 µg/L, federal limit 80 µg/L (1.1 times the limit)
Jan 1, 2007 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 68 µg/L, federal limit 60 µg/L (1.1 times the limit)
Oct 1, 2006 Resolved

10 older violations are not listed here. EPA ECHO has the complete list.

Enforcement actions

Maryland regulators took 3 formal enforcement actions against Town of Oakland between 2009 and 2010, filed as 53 records in EPA's data. The most recent was an administrative penalty in January 2010.

Date By Action Violations covered
Jan 26, 2010 Maryland Administrative penalty 4 violations (4 health-based): Haloacetic Acids (HAA5), Total Trihalomethanes (TTHMs)
Jan 1, 2010 Maryland Signed compliance agreement 47 violations (47 health-based): Haloacetic Acids (HAA5), Total Trihalomethanes (TTHMs)
Jun 26, 2009 Maryland Administrative penalty 2 violations (2 health-based): Haloacetic Acids (HAA5), Total Trihalomethanes (TTHMs)

Where the water comes from

Town of Oakland draws water from 1 surface water intake and 1 reservoir. 1 other public water system has an emergency connection to Town of Oakland.

Annual water quality report

Town of Oakland must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.

Where the state allows it, systems serving fewer than 10,000 people may publish the report in a local newspaper or news site instead of mailing it, and must provide a copy on request.

Find a posted report with EPA's Consumer Confidence Report search

Testing your own water