Public water system record
Providence Water Works
Serves an area of Webster County, KY that includes Providence · 4,538 people served
Federal records show 30 health-based violations and 6 monitoring/reporting issues for Providence Water Works in the last ten years. The most serious issue in this window was a Total Trihalomethanes (TTHMs) violation that EPA lists as archived, not resolved.
System profile
- Health-based violations, last 10 years
- 30
- Resolved
- 27
- Unresolved
- 0
- Archived by EPA
- 3
- Any acute record
- No
- Monitoring issues, last 10 years
- 6
Key facts
- Providence Water Works draws water from 2 surface water intakes (1 of them for emergency, seasonal or other part-time use).
- Highest measured level in the last 10 years: Haloacetic Acids (HAA5), 0.082 mg/L, federal limit 0.06 mg/L (1.4 times the limit), 2023.
- Most recent formal enforcement: compliance order with a penalty by Kentucky, August 2023.
- Record on file since 1993, with 23 health-based violations before October 19, 2016.
- Lead pipe inventory: 1 lead and 1,187 unknown out of 1,575 service lines.
Check whether Providence Water Works serves your address
Health-based violations
Since October 2016Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.
| Contaminant | Rule family | Start date | Status | Acute |
|---|---|---|---|---|
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.087 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
220 | Oct 1, 2025 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.061 mg/L, federal limit 0.06 mg/L (at or just above the limit)
|
220 | Oct 1, 2025 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.084 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
220 | Jul 1, 2025 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.086 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
220 | Jan 1, 2025 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.066 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
|
220 | Jan 1, 2025 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.088 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
220 | Oct 1, 2024 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.067 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
|
220 | Oct 1, 2024 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.09 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
220 | Jul 1, 2024 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.067 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
|
220 | Jul 1, 2024 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.069 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
|
220 | Apr 1, 2024 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.1 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
|
220 | Apr 1, 2024 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.091 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
220 | Jan 1, 2024 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.063 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
|
220 | Jan 1, 2024 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.1 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
|
220 | Oct 1, 2023 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.072 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
|
220 | Oct 1, 2023 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.101 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
|
220 | Jul 1, 2023 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.072 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
|
220 | Jul 1, 2023 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.092 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
220 | Apr 1, 2023 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.077 mg/L, federal limit 0.06 mg/L (1.3 times the limit)
|
220 | Apr 1, 2023 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.095 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
220 | Jan 1, 2023 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.082 mg/L, federal limit 0.06 mg/L (1.4 times the limit)
|
220 | Jan 1, 2023 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.09 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
220 | Oct 1, 2022 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.074 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
|
220 | Oct 1, 2022 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.083 mg/L, federal limit 0.08 mg/L (at or just above the limit)
|
220 | Jul 1, 2022 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.07 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
|
220 | Jul 1, 2022 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.089 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
220 | Apr 1, 2022 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.07 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
|
220 | Apr 1, 2022 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.063 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
|
220 | Jan 1, 2022 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.062 mg/L, federal limit 0.06 mg/L (at or just above the limit)
|
220 | Oct 1, 2018 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.062 mg/L, federal limit 0.06 mg/L (at or just above the limit)
|
220 | Apr 1, 2018 | Resolved | No |
Monitoring and reporting issues
Since October 2016Missed tests or reports, not contaminants found above a limit.
| Issue | Start date | Status |
|---|---|---|
|
Public Notice
OTHER
|
Jun 24, 2025 | Resolved |
|
Public Notice
OTHER
|
Jun 24, 2025 | Resolved |
|
LEAD AND COPPER RULE REVISIONS
RPT
|
Oct 17, 2024 | Resolved |
|
Consumer Confidence Rule
OTHER
|
Jul 1, 2021 | Resolved |
|
Public Notice
OTHER
|
Mar 1, 2017 | Resolved |
|
Public Notice
OTHER
|
Mar 1, 2017 | Resolved |
Full record since 1993
EPA's records for Providence Water Works go back to 1993. Before October 19, 2016 they list 23 health-based violations (23 resolved) and 49 monitoring or reporting violations.
| Violations that began in | Health-based | Monitoring and reporting |
|---|---|---|
| 1990s | 0 | 36 |
| 2000s | 9 | 7 |
| 2010 to October 18, 2016 | 14 | 6 |
| October 19, 2016 to 2019 | 2 | 2 |
| 2020s | 28 | 4 |
Most recent health-based violation before October 19, 2016: Total Trihalomethanes (TTHMs), began July 2016, Resolved.
Show all 23 health-based violations before October 19, 2016
| Contaminant | Start date | Status |
|---|---|---|
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.093 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
Jul 1, 2016 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.077 mg/L, federal limit 0.06 mg/L (1.3 times the limit)
|
Jul 1, 2016 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.1 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
|
Apr 1, 2016 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.076 mg/L, federal limit 0.06 mg/L (1.3 times the limit)
|
Apr 1, 2016 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.106 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
|
Jan 1, 2016 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.085 mg/L, federal limit 0.06 mg/L (1.4 times the limit)
|
Jan 1, 2016 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.101 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
|
Oct 1, 2015 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.075 mg/L, federal limit 0.06 mg/L (1.3 times the limit)
|
Oct 1, 2015 | Resolved |
|
Total Coliform
Contaminant limit exceeded
|
Oct 1, 2015 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.092 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
Jul 1, 2015 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.067 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
|
Jul 1, 2015 | Resolved |
|
Total Coliform
Contaminant limit exceeded
|
Dec 1, 2010 | Resolved |
|
Total Coliform
Contaminant limit exceeded
|
May 1, 2010 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.085 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Apr 1, 2010 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.082 mg/L, federal limit 0.08 mg/L (at or just above the limit)
|
Apr 1, 2009 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.088 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Jan 1, 2009 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.084 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Oct 1, 2008 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.094 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
Jul 1, 2008 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.09 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Jan 1, 2008 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.095 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
|
Oct 1, 2007 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.062 mg/L, federal limit 0.06 mg/L (at or just above the limit)
|
Apr 1, 2005 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.091 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
|
Jan 1, 2005 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.1 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
|
Oct 1, 2004 | Resolved |
Enforcement actions
Kentucky regulators took 2 formal enforcement actions against Providence Water Works between 2017 and 2023. The most recent was a compliance order with a penalty in August 2023.
| Date | By | Action | Violations covered |
|---|---|---|---|
| Aug 14, 2023 | Kentucky | Compliance order with a penalty | 34 violations (30 health-based): Public Notice, Total Trihalomethanes (TTHMs), Haloacetic Acids (HAA5), LEAD AND COPPER RULE REVISIONS, Consumer Confidence Rule |
| May 15, 2017 | Kentucky | Compliance order with a penalty | 17 violations (11 health-based): Surface Water Treatment Rule, Total Trihalomethanes (TTHMs), Total Coliform, Haloacetic Acids (HAA5), Public Notice |
What the violations mean
Haloacetic Acids (HAA5)
16 incidentsHaloacetic acid byproducts exceeded the federal limit
Long-term exposure to HAAs may increase cancer risk
Total Trihalomethanes (TTHMs)
14 incidentsDisinfection byproduct levels exceeded the federal limit
Long-term TTHM exposure may increase bladder cancer risk
Where the water comes from
Providence Water Works draws water from 2 surface water intakes (1 of them for emergency, seasonal or other part-time use). It also buys water from Webster Co Water District.
Buys water from
- Webster Co Water District Dixon, KY
Annual water quality report
Providence Water Works must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.
Where the state allows it, systems serving fewer than 10,000 people may publish the report in a local newspaper or news site instead of mailing it, and must provide a copy on request.
Find a posted report with EPA's Consumer Confidence Report search
Testing your own water
To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Kentucky.
Certified drinking water labs by state EPA guidance for private wells