Public water system record
McKinney Water District
Serves an area of Lincoln County, KY that includes McKinney · 5,423 people served
Federal records show 8 health-based violations and 7 monitoring/reporting issues for McKinney Water District in the last ten years. The most serious issue in this window was a resolved Haloacetic Acids (HAA5) violation.
System profile
- Health-based violations, last 10 years
- 8
- Resolved
- 8
- Unresolved
- 0
- Any acute record
- No
- Monitoring issues, last 10 years
- 7
Key facts
- McKinney Water District buys its water from Stanford Water Works and Eubank Water System.
- Highest measured level in the last 10 years: Haloacetic Acids (HAA5), 0.08 mg/L, federal limit 0.06 mg/L (1.3 times the limit), 2018.
- Most recent formal enforcement: compliance order with a penalty by Kentucky, October 2016.
- Record on file since 1996, with 5 health-based violations before October 19, 2016.
- Lead pipe inventory: 0 lead and 1,467 unknown out of 2,358 service lines.
Check whether McKinney Water District serves your address
Health-based violations
Since October 2016Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.
| Contaminant | Rule family | Start date | Status | Acute |
|---|---|---|---|---|
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.07 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
|
220 | Jan 1, 2019 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.071 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
|
220 | Oct 1, 2018 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.075 mg/L, federal limit 0.06 mg/L (1.3 times the limit)
|
220 | Jul 1, 2018 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.08 mg/L, federal limit 0.06 mg/L (1.3 times the limit)
|
220 | Apr 1, 2018 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.07 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
|
220 | Jan 1, 2018 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.074 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
|
220 | Oct 1, 2017 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.071 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
|
220 | Jul 1, 2017 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.063 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
|
220 | Jan 1, 2017 | Resolved | No |
Monitoring and reporting issues
Since October 2016Missed tests or reports, not contaminants found above a limit.
| Issue | Start date | Status |
|---|---|---|
|
Revised Total Coliform Rule
Monitoring violation
|
Oct 1, 2017 | Resolved |
|
Public Notice
OTHER
|
Feb 10, 2017 | Resolved |
|
Public Notice
OTHER
|
Dec 1, 2015 | Resolved |
|
Public Notice
OTHER
|
Dec 1, 2015 | Resolved |
|
Public Notice
OTHER
|
Jul 7, 2015 | Resolved |
|
Consumer Confidence Rule
OTHER
|
Jul 1, 2015 | Resolved |
|
Consumer Confidence Rule
OTHER
|
Jul 1, 2014 | Resolved |
Full record since 1996
EPA's records for McKinney Water District go back to 1996. Before October 19, 2016 they list 5 health-based violations (5 resolved) and 17 monitoring or reporting violations.
| Violations that began in | Health-based | Monitoring and reporting |
|---|---|---|
| 1990s | 0 | 2 |
| 2000s | 0 | 9 |
| 2010 to October 18, 2016 | 5 | 6 |
| October 19, 2016 to 2019 | 8 | 2 |
Most recent health-based violation before October 19, 2016: Haloacetic Acids (HAA5), began July 2016, Resolved.
Show all 5 health-based violations before October 19, 2016
| Contaminant | Start date | Status |
|---|---|---|
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.061 mg/L, federal limit 0.06 mg/L (at or just above the limit)
|
Jul 1, 2016 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.067 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
|
Jul 1, 2015 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.064 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
|
Apr 1, 2015 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.073 mg/L, federal limit 0.06 mg/L (1.2 times the limit)
|
Jan 1, 2015 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.068 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
|
Oct 1, 2014 | Resolved |
Enforcement actions
Kentucky regulators took 1 formal enforcement action against McKinney Water District in 2016. The most recent was a compliance order with a penalty in October 2016.
| Date | By | Action | Violations covered |
|---|---|---|---|
| Oct 11, 2016 | Kentucky | Compliance order with a penalty | 16 violations (9 health-based): Haloacetic Acids (HAA5), Public Notice, Consumer Confidence Rule |
What the violations mean
Haloacetic Acids (HAA5)
8 incidentsHaloacetic acid byproducts exceeded the federal limit
Long-term exposure to HAAs may increase cancer risk
Where the water comes from
McKinney Water District buys its water from Stanford Water Works and Eubank Water System. It lists no wells or intakes of its own.
Buys water from
- Stanford Water Works Stanford, KY
- Eubank Water System Eubank, KY
Annual water quality report
McKinney Water District must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.
Where the state allows it, systems serving fewer than 10,000 people may publish the report in a local newspaper or news site instead of mailing it, and must provide a copy on request.
Find a posted report with EPA's Consumer Confidence Report search
Testing your own water
To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Kentucky.
Certified drinking water labs by state EPA guidance for private wells