Public water system record
City of Buffalo
Serves Buffalo, Wilson County, KS · 218 people served
Federal records show 1 health-based violation and 4 monitoring/reporting issues for City of Buffalo in the last ten years. The most serious issue in this window was a resolved Total Trihalomethanes (TTHMs) violation.
System profile
- Health-based violations, last 10 years
- 1
- Resolved
- 1
- Unresolved
- 0
- Any acute record
- No
- Monitoring issues, last 10 years
- 4
Key facts
- City of Buffalo buys its water from Public Wholesale WSD 23.
- Highest measured level in the last 10 years: Total Trihalomethanes (TTHMs), 0.081 mg/L, federal limit 0.08 mg/L (at or just above the limit), 2018.
- Most recent enforcement action: boil water order by Kansas, June 2000.
- Record on file since 1992, with 24 health-based violations before October 19, 2016.
Check whether City of Buffalo serves your address
Health-based violations
Since October 2016Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.
| Contaminant | Rule family | Start date | Status | Acute |
|---|---|---|---|---|
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.081 mg/L, federal limit 0.08 mg/L (at or just above the limit)
|
220 | Jan 1, 2018 | Resolved | No |
Monitoring and reporting issues
Since October 2016Missed tests or reports, not contaminants found above a limit.
| Issue | Start date | Status |
|---|---|---|
|
Revised Total Coliform Rule
Monitoring violation
|
Dec 1, 2023 | Resolved |
|
Chlorine
Monitoring and reporting
|
Oct 1, 2023 | Resolved |
|
Haloacetic Acids (HAA5)
Monitoring and reporting
|
Feb 1, 2019 | Resolved |
|
Total Trihalomethanes (TTHMs)
Monitoring and reporting
|
Feb 1, 2019 | Resolved |
Full record since 1992
EPA's records for City of Buffalo go back to 1992. Before October 19, 2016 they list 24 health-based violations (24 resolved) and 24 monitoring or reporting violations.
| Violations that began in | Health-based | Monitoring and reporting |
|---|---|---|
| 1990s | 3 | 3 |
| 2000s | 20 | 20 |
| 2010 to October 18, 2016 | 1 | 1 |
| October 19, 2016 to 2019 | 1 | 2 |
| 2020s | 0 | 2 |
Most recent health-based violation before October 19, 2016: Total Coliform, began September 2012, Resolved.
Show all 24 health-based violations before October 19, 2016
| Contaminant | Start date | Status |
|---|---|---|
|
Total Coliform
Contaminant limit exceeded
|
Sep 1, 2012 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.11 mg/L, federal limit 0.08 mg/L (1.4 times the limit)
|
Oct 1, 2009 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.096 mg/L, federal limit 0.06 mg/L (1.6 times the limit)
|
Oct 1, 2009 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.117 mg/L, federal limit 0.08 mg/L (1.5 times the limit)
|
Jul 1, 2009 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.11 mg/L, federal limit 0.06 mg/L (1.8 times the limit)
|
Jul 1, 2009 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.127 mg/L, federal limit 0.08 mg/L (1.6 times the limit)
|
Apr 1, 2009 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.135 mg/L, federal limit 0.06 mg/L (2.3 times the limit)
|
Apr 1, 2009 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.128 mg/L, federal limit 0.08 mg/L (1.6 times the limit)
|
Jan 1, 2009 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.128 mg/L, federal limit 0.06 mg/L (2.1 times the limit)
|
Jan 1, 2009 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.12 mg/L, federal limit 0.08 mg/L (1.5 times the limit)
|
Oct 1, 2008 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.117 mg/L, federal limit 0.06 mg/L (2 times the limit)
|
Oct 1, 2008 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.102 mg/L, federal limit 0.06 mg/L (1.7 times the limit)
|
Jul 1, 2008 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.104 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
|
Jul 1, 2008 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.061 mg/L, federal limit 0.06 mg/L (at or just above the limit)
|
Apr 1, 2008 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.065 mg/L, federal limit 0.06 mg/L (1.1 times the limit)
|
Jan 1, 2008 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.081 mg/L, federal limit 0.08 mg/L (at or just above the limit)
|
Jan 1, 2008 | Resolved |
|
Surface Water Treatment Rule
Treatment technique failure
|
Jun 1, 2003 | Resolved |
|
Surface Water Treatment Rule
Treatment technique failure
|
May 1, 2003 | Resolved |
|
Surface Water Treatment Rule
Treatment technique failure
|
Apr 1, 2002 | Resolved |
|
Surface Water Treatment Rule
Treatment technique failure
|
Nov 1, 2000 | Resolved |
|
Surface Water Treatment Rule
Treatment technique failure
|
Jun 1, 2000 | Resolved |
|
Total Coliform
Contaminant limit exceeded
|
Jun 1, 1996 | Resolved |
|
Total Coliform (acute)
Contaminant limit exceeded
|
Jul 1, 1992 | Resolved |
|
Total Coliform
Contaminant limit exceeded
|
Jul 1, 1992 | Resolved |
Enforcement actions
Kansas regulators issued 1 boil water order to City of Buffalo in 2000. The most recent was a boil water order in June 2000.
| Date | By | Action | Violations covered |
|---|---|---|---|
| Jun 19, 2000 | Kansas | Boil water order | 1 violation (1 health-based): Surface Water Treatment Rule |
What the violations mean
Total Trihalomethanes (TTHMs)
1 incidentDisinfection byproduct levels exceeded the federal limit
Long-term TTHM exposure may increase bladder cancer risk
Where the water comes from
City of Buffalo buys its water from Public Wholesale WSD 23. It lists no wells or intakes of its own.
Buys water from
- Public Wholesale WSD 23 Fredonia, KS
Annual water quality report
City of Buffalo must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.
Systems serving 500 or fewer people may meet the rule by telling customers the report is available on request, so you may need to ask City of Buffalo for a copy.
Find a posted report with EPA's Consumer Confidence Report search
Testing your own water
To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Kansas.
Certified drinking water labs by state EPA guidance for private wells