Public water system record

City of Logan

Serves Logan, Phillips County, KS · 440 people served

Federal records show no health-based violations and 5 monitoring/reporting issues for City of Logan in the last ten years.

  • KS2014701
  • LOGAN
  • KS
  • 440 served

System profile

Source water Groundwater
ZIP 67646
EPA system ID KS2014701

Verify this system on EPA ECHO →

Health-based violations, last 10 years
0
Resolved
0
Unresolved
0
Any acute record
No
Monitoring issues, last 10 years
5

Key facts

  • City of Logan draws water from 8 wells.
  • Most recent formal enforcement: compliance order (no penalty) by Kansas, May 1998.
  • Record on file since 1980, with 41 health-based violations before October 19, 2016.

Check whether City of Logan serves your address

Address suggestions by Mapbox

Health-based violations

Since October 2016

Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.

None since October 2016.

Monitoring and reporting issues

Since October 2016

Missed tests or reports, not contaminants found above a limit.

Issue Start date Status
Lead and Copper Rule
Monitoring and reporting
Jan 1, 2025 Resolved
Revised Total Coliform Rule
Monitoring violation
Jun 1, 2023 Resolved
Chlorine
Monitoring and reporting
Apr 1, 2023 Resolved
Groundwater Rule
Monitoring and reporting
Oct 1, 2022 Resolved
Lead and Copper Rule
Monitoring and reporting
Dec 30, 2018 Resolved

Full record since 1980

EPA's records for City of Logan go back to 1980. Before October 19, 2016 they list 41 health-based violations (36 resolved, 5 archived by EPA without a recorded fix) and 6 monitoring or reporting violations.

Violations that began in Health-based Monitoring and reporting
1980s 7 0
1990s 24 2
2000s 10 4
October 19, 2016 to 2019 0 1
2020s 0 4

Most recent health-based violation before October 19, 2016: Selenium, began January 2002, Resolved.

Show all 41 health-based violations before October 19, 2016
Contaminant Start date Status
Selenium
Contaminant limit exceeded
Measured 0.158 mg/L, federal limit 0.05 mg/L (3.2 times the limit)
Jan 1, 2002 Resolved
Nitrate (acute)
Contaminant limit exceeded
Measured 18.11 mg/L, federal limit 10 mg/L (1.8 times the limit)
Oct 1, 2001 Resolved
Nitrate (acute)
Contaminant limit exceeded
Measured 20.97 mg/L, federal limit 10 mg/L (2.1 times the limit)
Jul 1, 2001 Resolved
Nitrate (acute)
Contaminant limit exceeded
Measured 18.76 mg/L, federal limit 10 mg/L (1.9 times the limit)
Apr 1, 2001 Resolved
Selenium
Contaminant limit exceeded
Measured 0.1346 mg/L, federal limit 0.05 mg/L (2.7 times the limit)
Jan 1, 2001 Resolved
Nitrate (acute)
Contaminant limit exceeded
Measured 29.22 mg/L, federal limit 10 mg/L (2.9 times the limit)
Jan 1, 2001 Resolved
Nitrate (acute)
Contaminant limit exceeded
Measured 21.02 mg/L, federal limit 10 mg/L (2.1 times the limit)
Oct 1, 2000 Resolved
Nitrate (acute)
Contaminant limit exceeded
Measured 18.14 mg/L, federal limit 10 mg/L (1.8 times the limit)
Jul 1, 2000 Resolved
Nitrate (acute)
Contaminant limit exceeded
Measured 15.16 mg/L, federal limit 10 mg/L (1.5 times the limit)
Jan 1, 2000 Resolved
Selenium
Contaminant limit exceeded
Measured 0.1232 mg/L, federal limit 0.05 mg/L (2.5 times the limit)
Jan 1, 2000 Resolved
Selenium
Contaminant limit exceeded
Measured 0.1288 mg/L, federal limit 0.05 mg/L (2.6 times the limit)
Oct 1, 1999 Resolved
Nitrate (acute)
Contaminant limit exceeded
Measured 19.19 mg/L, federal limit 10 mg/L (1.9 times the limit)
Oct 1, 1999 Resolved
Selenium
Contaminant limit exceeded
Measured 0.095 mg/L, federal limit 0.05 mg/L (1.9 times the limit)
Jul 1, 1999 Resolved
Nitrate (acute)
Contaminant limit exceeded
Measured 17.17 mg/L, federal limit 10 mg/L (1.7 times the limit)
Jul 1, 1999 Resolved
Selenium
Contaminant limit exceeded
Measured 0.1359 mg/L, federal limit 0.05 mg/L (2.7 times the limit)
Apr 1, 1999 Resolved
Nitrate (acute)
Contaminant limit exceeded
Measured 13.28 mg/L, federal limit 10 mg/L (1.3 times the limit)
Apr 1, 1999 Resolved
Selenium
Contaminant limit exceeded
Measured 0.1257 mg/L, federal limit 0.05 mg/L (2.5 times the limit)
Jan 1, 1999 Resolved
Nitrate (acute)
Contaminant limit exceeded
Measured 17.99 mg/L, federal limit 10 mg/L (1.8 times the limit)
Jan 1, 1999 Resolved
Selenium
Contaminant limit exceeded
Measured 0.1328 mg/L, federal limit 0.05 mg/L (2.7 times the limit)
Oct 1, 1998 Resolved
Nitrate (acute)
Contaminant limit exceeded
Measured 22.47 mg/L, federal limit 10 mg/L (2.2 times the limit)
Oct 1, 1998 Resolved
Selenium
Contaminant limit exceeded
Measured 0.1282 mg/L, federal limit 0.05 mg/L (2.6 times the limit)
Jul 1, 1998 Resolved
Nitrate (acute)
Contaminant limit exceeded
Measured 20.13 mg/L, federal limit 10 mg/L (2 times the limit)
Jul 1, 1998 Resolved
Selenium
Contaminant limit exceeded
Measured 0.094 mg/L, federal limit 0.05 mg/L (1.9 times the limit)
Apr 1, 1998 Resolved
Nitrate (acute)
Contaminant limit exceeded
Measured 18.34 mg/L, federal limit 10 mg/L (1.8 times the limit)
Apr 1, 1998 Resolved
Selenium
Contaminant limit exceeded
Measured 0.0689 mg/L, federal limit 0.05 mg/L (1.4 times the limit)
Jan 1, 1998 Resolved
Nitrate (acute)
Contaminant limit exceeded
Measured 18.57 mg/L, federal limit 10 mg/L (1.9 times the limit)
Jan 1, 1998 Resolved
Nitrate (acute)
Contaminant limit exceeded
Measured 20.36 mg/L, federal limit 10 mg/L (2 times the limit)
Oct 1, 1997 Resolved
Nitrate (acute)
Contaminant limit exceeded
Measured 18.62 mg/L, federal limit 10 mg/L (1.9 times the limit)
Jul 1, 1997 Resolved
Nitrate (acute)
Contaminant limit exceeded
Measured 14.17 mg/L, federal limit 10 mg/L (1.4 times the limit)
Apr 1, 1997 Resolved
Nitrate (acute)
Contaminant limit exceeded
Measured 13.15 mg/L, federal limit 10 mg/L (1.3 times the limit)
Jan 1, 1997 Resolved
Selenium
Contaminant limit exceeded
Measured 0.0839 mg/L, federal limit 0.05 mg/L (1.7 times the limit)
Oct 1, 1996 Resolved
Nitrate (acute)
Contaminant limit exceeded
Measured 13.4 mg/L, federal limit 10 mg/L (1.3 times the limit)
Oct 1, 1996 Resolved
Selenium
Contaminant limit exceeded
Measured 0.1224 mg/L, federal limit 0.05 mg/L (2.4 times the limit)
Oct 1, 1995 Resolved
Total Coliform
Contaminant limit exceeded
Mar 1, 1993 Resolved
Selenium
Contaminant limit exceeded
Oct 1, 1988 Archived
Selenium
Contaminant limit exceeded
Mar 26, 1986 Resolved
Selenium
Contaminant limit exceeded
Mar 26, 1986 Resolved
Selenium
Contaminant limit exceeded
Jan 15, 1985 Archived
Selenium
Contaminant limit exceeded
Oct 1, 1983 Archived
Selenium
Contaminant limit exceeded
Oct 1, 1982 Archived
Selenium
Contaminant limit exceeded
Oct 1, 1980 Archived

Enforcement actions

Kansas regulators took 1 formal enforcement action against City of Logan in 1998. The most recent was a compliance order (no penalty) in May 1998.

Date By Action Violations covered
May 19, 1998 Kansas Compliance order (no penalty) 31 violations (30 health-based): Selenium, Nitrate

Where the water comes from

City of Logan draws water from 8 wells.

Annual water quality report

City of Logan must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.

Systems serving 500 or fewer people may meet the rule by telling customers the report is available on request, so you may need to ask City of Logan for a copy.

Find a posted report with EPA's Consumer Confidence Report search

Testing your own water

To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Kansas.